InPro Corporation Expansion Joint Cover Assemblies
 
         
SECTION 05810
 
         
EXPANSION JOINT COVER ASSEMBLIES
 
         
Copyright 2003 - 2007 ARCAT, Inc. - All rights reserved

          ** NOTE TO SPECIFIER ** JointMaster, InPro Corporation; interior, exterior, seismic, and fire barrier expansion joint covers .

This section is based on expansion joint cover assemblies manufactured by InPro Corporation, which is located at:
P.O. Box 406
S 80 W 18766 Apollo Drive
Muskego, WI 53150
Te1: (800)222-5556
Tel: (262) 679-9010
Fax: (262) 679-9127
E-mail: jjohnson@inprocorp.com
Website: www.inprocorp.com .

JointMaster, InPro Corporation manufactures a wide range of expansion joint cover assemblies, including a number of systems designed for seismic conditions and for installation in fire rated construction. .
 
          PART 1GENERAL
 
          1.1SECTION INCLUDES
          ** NOTE TO SPECIFIER ** Delete items below not required for project.
 
          A.Interior floor expansion joint covers.
 
          B.Interior wall expansion joint covers.
 
          C.Interior ceiling expansion joint covers.
 
          D.Roof expansion joint covers.
 
          E.Exterior wall expansion joint covers.
 
          F.Exterior floor expansion joint covers.
 
          G.Exterior ceiling expansion joint covers.
 
          H.Parking deck expansion joint covers.
 
          I.Fire rated expansion joint covers.
 
          1.2RELATED SECTIONS
          ** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
          A.Section 03300 - Cast-In-Place Concrete.
 
          B.Section 04810 - Unit Masonry Assemblies.
 
          C.Section 07900 - Joint Sealers.
 
          D.Section 09210 - Gypsum Plaster.
 
          E.Section 09260 - Gypsum Board Assemblies.
 
          F.Section 09511 - Suspended Acoustical Ceilings.
 
          G.Section 09650 - Resilient Flooring.
 
          H.Section 09720 - Wall Covering.
 
          1.3REFERENCES
          ** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
 
          A.UL 2079 - Tests for Fire Resistance of Building Joint System; Underwriters Laboratories Inc.; 1998.
 
          B.ASTM A 176 - Standard Specification for Stainless and Heat-Resisting Chromium Steel Plate, Sheet, and Strip; 1999.
 
          C.ASTM B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes; 2000.
 
          D.ASTM D 2000 - Standard Classification System for Rubber Products in Automotive Applications; 2001.
 
          E.ASTM E 1399 - Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems; 1997 (Reapproved 2000).
 
          F.ASTM E 1966 - Standard Test Method for Fire Resistive Joint Systems.
 
          G.ASTM E 2393 - Standard Practice for On-Site Inspection of Installed Fire Resistive Joint System and Perimeter Fire Barriers.
 
          1.4SUBMITTALS
 
          A.Submit under provisions of Section 01300.
 
          B.[ Product Data ]: For each type of expansion joint cover assembly, provide manufacturer's product specifications.
 
          C.Shop Drawings: Shop drawing submittal should include Placement drawings which show line diagrams, elevations, sections, details and layout for each joint length. These drawings must include a Joint System Schedule which denotes specific information for each joint system in tabular form. The tables should include the model number for each joint system item, location as cross-referenced in the drawings, nominal joint width and system movement capability, material colors and finishes, fire-resistive ratings, design loading criteria and any other options.
 
          D.Samples: 5 inch (127mm) long samples of each assembly.
 
          E.Product Test Reports (where applicable): If applicable, the manufacturer will provide independent evaluations by a recognized testing agency. In the case of fire-rated applications, the Test Reports should include Fire Test Certification Listing Documents.
 
          F.Fire-Rated Joint Assemblies: Where indicated in the drawings, provide architectural joint system and fire-barrier assemblies identical to those depicted and tested for fire resistance per ASTM E 1966 or UL 2079. The following are some of the recognized independent laboratories conducting tests of fire-resistive systems:
          1.Underwriters Laboratories Inc., Northbrook, IL; (847) 272-8800; www.ul.com.
          2.Omega Point Laboratories, Elmendorf, TX; (210) 635-8100; www.opl.com.
          3.Southwest Research Institute, San Antonio, TX; (210) 522-2311; www.swri.com.
          4.Factory Mutual, Norwood, MA; (781) 762-4300; www.fmglobal.com.
          5.Intertek Testing Services, Antioch, CA; (925) 756-6606; www.itsqs.com.
 
          1.5QUALITY ASSURANCE
 
          A.Manufacturer Qualifications: Company with not less than 5 years of experience in the design, engineering, and fabrication of expansion joint cover assemblies.
 
          B.Installer Qualifications: Firm acceptable to manufacturer and with not less than 3 years of successful experience in the installation of systems similar to those required for this project.
 
          C.Single Source for Products: Architectural joint systems are to be supplied from a single manufacturer. Where fire-rated joint systems are required, both the joint system and fire barrier assembly must be obtained from a single manufacturer. The total system, mechanical joint and fire barrier, must be as shown in the Fire Test Certification Listing Documents.
 
          1.6DELIVERY, STORAGE, AND HANDLING
 
          A.Protect finished metal surfaces with temporary protective covering.
 
          B.Deliver assemblies to project site in manufacturer's clean, unopened cartons or crates.
 
          C.Store components in original containers in a clean, dry location until installed. Protect from weather and constructions activities.
 
          1.7WARRANTY
 
          A.Warranty: InPro JointMaster offers a 3-year warranty on all architectural joint system products, manufacturer v. installer and qualifications for an extended warranty period.
 
          PART 2PRODUCTS
 
          2.1MANUFACTURERS
 
          A.Acceptable Manufacturer: InPro Corporation, which is located at: S80 W18766 Apollo Dr. ; Muskego, WI 53150; Toll Free Tel: 800-222-5556; Tel: 262-679-9010; Email: request info; Web: www.inprocorp.com
          ** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
          B.Substitutions: Not permitted.
 
          C.Requests for substitutions will be considered in accordance with provisions of Section 01600.
 
          2.2EXPANSION JOINT COVER ASSEMBLIES - GENERAL
          ** NOTE TO SPECIFIER ** Delete the following joint movement and allowable loading criteria if standard (not custom designed) systems are acceptable for project conditions.
 
          A.Joint Movement: Design and fabricate expansion joint cover assemblies to permit the following amount of movement without disengagement or other damage:
          1.Horizontal: Maximum x-axis joint movement of _____ inches (____ mm).
          2.Vertical: Maximum y-axis joint movement of _____ inches (___ mm).
          3.Lateral: Maximum z-axis joint movement of _____ inches (____ mm).
 
          B.Allowable Loading: Design and fabricate expansion joint cover assemblies to accommodate the following loading without distortion or damage:
          ** NOTE TO SPECIFIER ** Select one of the following three paragraphs; if no requirement is specified, systems designed for 50 psf will be provided.
          1.Uniform Loading: Maximum 50 psf (2394 Pa).
          2.Uniform Loading: Maximum 100 psf (4788 Pa).
          3.Uniform Loading: Maximum 200 psf (9576 Pa).
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs; the second option is for heavy duty systems only..
          4.Concentrated Loading: Maximum 300 pounds (1334 N)
          5.Concentrated Loading: Maximum 2,000 pounds (8896 N).
          6.Maximum Allowable Stress:
          a.Aluminum Extrusions: 12,000 psi (82.7 MPa).
          b.Aluminum Plate: 28,000 psi (193 MPa).
          c.Aluminum Sheet: 16,000 psi (110.3 MPa).
          d.Stainless Steel Plate: 36,000 psi (248 MPa).
          e.Bronze Sheet: 14,000 psi (96.5 MPa).
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs; if no requirement is specified, systems designed for 1/8 inch deflection will be provided.
          7.Maximum Deflection: 1/16 inch. (1.6 mm).
          8.Maximum Deflection: 1/8 inch (3.2 mm).
          ** NOTE TO SPECIFIER ** Delete the following paragraph if no fire-rated expansion joint covers are required.
 
          C.Expansion Joint Fire Barrier Assemblies: Rated architectural joint systems and fire-barrier assemblies must comply with applicable requirements of UL 2079 and ASTM E 1966.
          1.Provide minimum 2 hour rating, or not less than fire rating of adjacent construction.
          2.Hose Stream Test: Wall/wall and wall/ceiling fire-barrier assemblies shall be subjected to hose stream testing.
 
          D.Factory fabricate special transitions and corner fittings as required by project conditions. Miter and weld elastomeric seals as applicable.
 
          E.Aluminum: Alloy 6063-T6, in accordance with ASTM B 221; mill finish.
 
          F.Stainless Steel: ASTM A 176, Type 430, 16 gage, satin finish.
 
          G.EPDM: ASTM D 2000.
 
          H.Provide appropriate fasteners, adhesives, and accessories as required to properly complete expansion joint cover installation, prepackaged with expansion joint covers in maximum lengths possible.
 
          2.3INTERIOR JOINT SYSTEMS FOR FLOORS, WALLS, AND CEILINGS
          ** NOTE TO SPECIFIER ** Delete expansion joint cover types not required. If more than one type for a particular application is needed, either schedule on drawings or add statements to specifications, describing locations for each expansion joint cover type. Delete options not needed under cover types retained.
 
          A.Expansion Joint Cover Assemblies: JointMaster 100 Series; aluminum frame with continuous Santoprene seal.
          1.Floors, Flush:
          a.Recessed Frame, Flat: JointMaster-101-A01 (floor/floor).
          1)Frame Height: 1 inch (25 mm).
          2)Frame Height: 1-1/2 inches (38 mm).
          3)Frame Height: 2 inches (50 mm).
          b.Recessed Frame, Corner: JointMaster-101-A02 (floor/wall).
          1)Wall frame recessed 3/8 inch (9.5 mm).
          2)Wall frame recessed 5/8 inch (16 mm).
          3)Wall frame recessed 1 inch (25 mm).
          4)Frame Height: 1 inch (25 mm).
          5)Frame Height: 1-1/2 inches (38 mm).
          6)Frame Height: 2 inches (50 mm).
          c.Surface Mounted Frame: JointMaster-104-A01 (floor/floor) and -104-A02 (floor/wall).
          d.New Floor to Old Floor: Combination recessed and surface mounted frame; JointMaster-107-A01.
          e.Joint Width: 1 inch (25 mm).
          f.Joint Width: 2 inches (50 mm).
          g.Joint Width: 3 inches (75 mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          h.Integral vinyl vapor barrier.
          i.Reactofire fire blanket system.
          j.Reactofire mineral wool and silicone sealant system.
          2.Floors, 1/8 inch (3 mm) Thick Flooring:
          a.Surface Mounted Frame: JointMaster-105-A01 (floor/floor) and -105-A02 (floor/wall).
          b.Combination recessed and surface mounted frame; JointMaster-108-A01.
          c.Joint Width: 1 inch (25 mm).
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 3 inches (75 mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          f.Integral vinyl vapor barrier.
          g.Reactofire fire blanket system.
          h.Reactofire mineral wool and silicone sealant system.
          3.Floors, 1/4 inch (6.4 mm) Thick Flooring:
          a.Surface Mounted Frame: JointMaster-106-A01 (floor/floor) and -106-A02 (floor/wall).
          b.New Floor to Old Floor: Combination recessed and surface mounted frame; JointMaster-109-A01.
          c.Joint Width: 1 inch (25 mm).
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 3 inches (75 mm).
          ** NOTE TO SPECIFIER ** The following five paragraphs are optional, delete if not required.
          f.Stainless steel decorative caps.
          g.Brass decorative caps.
          h.Integral vinyl vapor barrier.
          i.Reactofire fire blanket system.
          j.Reactofire mineral wool and silicone sealant system.
          4.Drywall Finish, Exposed Frame:Natural anodized finish.
          a.Flat: JointMaster-112-A07 (wall/wall and ceiling/ceiling).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Reactofire fire blanket system.
          2)Reactofire mineral wool and silicone sealant system.
          b.Corner: JointMaster-112-A09 (wall/corner and wall/ceiling).
          c.Joint Width: 1 inch (25 mm).
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 3 inches (75 mm).
          5.Drywall Finish, Concealed Frame: Concealed by joint compound.
          a.Flat: JointMaster-113-A07 (wall/wall and ceiling/ceiling).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Reactofire fire blanket system.
          2)Reactofire mineral wool and silicone sealant system.
          b.Corner: JointMaster-113-A09 (wall/corner and wall/ceiling).
          c.Joint Width: 1 inch (25 mm).
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 3 inches (75 mm).
          6.Wall/Ceiling, Surface Mounted Exposed Frame:
          a.Flat: JointMaster-104-A07 (wall/wall and ceiling/ceiling).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Reactofire fire blanket system.
          2)Reactofire mineral wool and silicone sealant system.
          b.Corner: JointMaster-104-A09 (wall/corner and wall/ceiling).
          c.Joint Width: 1 inch (25 mm).
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 3 inches (75 mm).
          7.Acoustic Ceiling, Concealed Frame: Designed for installation in suspended acoustical ceiling; JointMaster-115-A24 (ceiling/ceiling) and -115-A18 (ceiling/wall).
          a.Joint Width: 2 inches (50 mm).
          b.Joint Width: 3 inches (75 mm).
          c.Joint Width: 4 inches (100 mm).
          8.Wall/Ceiling, Recessed Frame, Flat: Frame recessed 5/8 inch (16 mm); JointMaster-101-A07 (wall/wall and ceiling/ceiling).
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 2 inches (50 mm).
          c.Joint Width: 3 inches (75 mm).
          ** NOTE TO SPECIFIER ** The following four paragraphs are optional, delete if not required.
          d.Stainless steel decorative caps.
          e.Brass decorative caps.
          f.Reactofire fire blanket system.
          g.Reactofire mineral wool and silicone sealant system.
          9.Wall/Ceiling, Recessed Frame, Corner:
          a.One flush wall frame; JointMaster-101-A09 (wall/corner and wall/ceiling).
          b.Joint Width: 1 inch (25 mm).
          c.Joint Width: 2 inches (50 mm).
          d.Joint Width: 3 inches (75 mm).
          10.Floors - Flush, 1/8 inch (2mm) thick flooring and 1/4 inch (6.4mm) thick flooring.
          a.Combination recessed and flush frame. 120-A01 (floor/floor) and 120-A02 (floor/wall).
          b.Joint Width -1 inch (25mm).
          c.Joint Width -1 1/2 inches (38mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          d.Vapor barrier.
          e.Reactofire blanket.
          f.Reactofire mineral wool and silicone sealant system.
 
          B.Expansion Joint Cover Assemblies: JointMaster 200 Series Recessed Modular Floor System.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          1.2 inch (50 mm) Joint Width: With stainless steel spring clips:
          a.Floor/Floor:JointMaster-221-A01, with flush aluminum plate and dual Santoprene seals.
          b.Floor/Floor: JointMaster-222-A01, with 1/8 inch (3 mm) recessed aluminum pan and dual Santoprene seals.
          c.Floor/Floor: JointMaster-223-A01, with 3/8 inch (9 mm) recessed aluminum pan and dual Santoprene seals.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Stainless steel decorative caps.
          2)Brass decorative caps.
          d.Floor/Wall: JointMaster-223-A02, with 3/8 inch (9 mm) recessed aluminum half pan and single Santoprene seal.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Stainless steel decorative caps.
          2)Brass decorative caps.
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          e.Continuous EPDM vapor barrier.
          f.Reactofire fire blanket system.
          g.Reactofire mineral wool and silicone sealant system.
          2.4 inch (100 mm) Joint Width: With steel centering bar:
          a.Floor/Floor: JointMaster-221-A01, with flush aluminum plate and dual Santoprene seals.
          b.Floor/Floor: JointMaster-222-A01, with 1/8 inch (3 mm) recessed aluminum pan and dual Santoprene seals.
          c.Floor/Floor: JointMaster-223-A01, with 3/8 inch (9 mm) recessed aluminum pan and dual Santoprene seals.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Stainless steel decorative caps.
          2)Brass decorative caps.
          d.Floor/Wall: JointMaster-223-A02, with 3/8 inch (9 mm) recessed aluminum half pan and single Santoprene seal.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Stainless steel decorative caps.
          2)Brass decorative caps.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          e.Continuous EPDM vapor barrier.
          f.Reactofire fire blanket system.
          3.6 inch (150 mm) Joint Width: With steel centering bar:
          a.Floor/Floor: JointMaster-221-A01, with flush aluminum plate and dual Santoprene seals.
          b.Floor/Floor: JointMaster-222-A01, with 1/8 inch (3 mm) recessed aluminum pan and dual Santoprene seals.
          c.Floor/Floor: JointMaster-223-A01, with 3/8 inch (9 mm) recessed aluminum pan and dual Santoprene seals.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Stainless steel decorative caps.
          2)Brass decorative caps.
          d.Floor/Wall: JointMaster-223-A02, with 3/8 inch (9 mm) recessed aluminum half pan and single Santoprene seal.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          1)Stainless steel decorative caps.
          2)Brass decorative caps.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          e.Continuous EPDM vapor barrier.
          f.Reactofire fire blanket system.
 
          C.Expansion Joint Cover Assemblies: JointMaster 800 Series.
          1.Floor Cover Plate: Continuous aluminum plate fastened on one side of joint; JointMaster-801-A01 (floor/floor) and -801-A02 (floor/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 2 inches (50 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          c.Reactofire mineral wool and silicone sealant system.
          2.Floor Plate to Floor Covering: Continuous aluminum plate fastened on one side of joint and designed to accommodate flooring on opposite side; JointMaster-802-A01 (floor/floor).
          a.Joint Width: 2 inches (50 mm).
          ** NOTE TO SPECIFIER ** Select Frame Flooring Thickness from the following options. Delete those not required.
          b.Frame Flooring Thickness: 1/8 inch (3 mm).
          c.Frame Flooring Thickness: 1/4 inch (6 mm).
          d.Frame Flooring Thickness: 3/8 inch (10 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          e.Reactofire mineral wool and silicone sealant system.
          3.Spring Clip Floor Cover Plate: Continuous aluminum plate held in place by stainless steel spring clips concealed within joint.
          a.Floor: JointMaster-804-A01 (floor/floor) and -804-A02 (floor/wall).
          b.Wall/Ceiling: JointMaster-804-A07 (wall/wall and ceiling/ceiling) and -804-A09 (wall/corner and wall/ceiling).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          c.Joint Width: 1 inch (25 mm).
          d.Joint Width: 1-1/2 inches (38 mm).
          e.Joint Width: 2 inches (50 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          f.Reactofire mineral wool and silicone sealant system.
          4.Surface Mount Variable Degree Plate for Walls/Ceilings: Continuous aluminum variable degree plate with continuous vinyl gasket and adjustable retainer; JointMaster-811-A07 (wall/wall and ceiling/ceiling) and -811-A09 (wall/corner or wall/ceiling).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 2 inches (50 mm).
          c.Joint Width: 3 inches (75 mm).
          d.Joint Width: 4 inches (100 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          e.Reactofire mineral wool and silicone sealant system.
          5.Acoustical Ceilings, Variable degree: Continuous dual durometer pleated vinyl seal designed for pop riveting to acoustical ceiling tees and fastening to wall; JointMaster-821-V24 (ceiling/ceiling) and -821-V23 (ceiling/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 2 inches (50 mm).
          6.Floor Cover Plate: Hinged aluminum plate fastened on one side of joint; JointMaster 806-A01 (floor/floor) and 806-A02 (floor/wall)
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width - 2 inches (50mm).
          b.Joint Width - 3 inches (76mm).
          c.Joint Width - 6 inches (152mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          d.Vapor barrier.
          e.Reactofire blanket.
          f.Reactofire mineral wool and silicone sealant system.
 
          D.Seismic Joint Cover Assemblies: Glide plate type; JointMaster 300 Series.
          1.Floor, "No Bump" Glide Plate: Aluminum frame and continuous aluminum glide plate with crenellated surface.
          a.Recessed Frame: JointMaster-300-A01 (floor/floor) and -300-A02 (floor/wall).
          b.Surface Mounted Frame: JointMaster-312-A01 (floor/floor) and -312-A02 (floor/wall).
          c.New to Old Floor: JointMaster-320-A01 combination recessed and surface mounted aluminum frame.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          d.Joint Width: 1 inch (25 mm).
          e.Joint Width: 2 inches (50 mm).
          f.Joint Width: 3 inches (75 mm).
          g.Joint Width: 4 inches (100 mm).
          h.Joint Width: 6 inches (150 mm).
          2.Recessed frame/flush frame for use with vinyl wall covering; JointMaster 318-A07 (wall/wall) and 318-A09 (wall/corner).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width - 2 inches (50mm).
          b.Joint Width - 3 inches (75mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          c.Vapor barrier.
          d.Reactofire blanket.
          e.Reactofire mineral wool and silicone sealant system.
          3.Carpeted Floors: Recessed aluminum frame with continuous aluminum pivot and spring steel support plate designed for minimum visual impact in carpeted areas; JointMaster-316-A01 (floor/floor) and -316-A02 (floor/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 2 inches (50 mm).
          b.Joint Width: 3 inches (75 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          c.Integral vinyl vapor barrier.
          d.Reactofire fire blanket system.
          4.Walls/Ceilings: Recessed drywall aluminum frame with vinyl gaskets, with continuous aluminum center plate; JointMaster-300-A07 (wall/wall) and -300-A09 (wall/corner).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 2 inches (50 mm).
          c.Joint Width: 3 inches (75 mm).
          d.Joint Width: 4 inches (100 mm).
          e.Joint Width: 6 inches (150 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          f.Reactofire fire blanket system.
          g.Reactofire mineral wool and silicone sealant system.
 
          E.Seismic Joint Cover Assemblies: Center plate type; JointMaster 400 Series; aluminum frame with continuous tapered plate held in place by steel centering bar with compression spring assembly.
          1.Floor, Recessed Frame: JointMaster-430-A01 (floor/floor) and -430-A02 (floor/wall).
          a.Plate: Aluminum.
          b.Plate: Stainless steel.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          c.Joint Width: 2 inches (50 mm).
          d.Joint Width: 3 inches (75 mm).
          e.Joint Width: 4 inches (100 mm).
          f.Joint Width: 6 inches (150 mm).
          g.Joint Width: 8 inches (200 mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          h.Continuous EPDM sheet vapor barrier.
          i.Reactofire fire blanket system.
          j.Reduced sightline configuration for carpeted areas.
          2.Floor, Surface Mounted Frame:
          a.Flat: Combination recessed and surface mounted aluminum frame with continuous tapered aluminum center plate held in place by steel centering bar with compression spring assembly; JointMaster-461-A01 (floor/floor).
          b.Flat:Surface mounted aluminum frame with continuous tapered aluminum center plate held in place by steel centering bar with compression spring assembly; JointMaster-471-A01 (floor/floor).
          c.Corner: Surface mounted aluminum floor and wall frame with continuous tapered aluminum half plate; JointMaster-471-A02 (floor/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 3 inches (75 mm).
          f.Joint Width: 4 inches (100 mm).
          g.Joint Width: 6 inches (150 mm).
          h.Joint Width: 8 inches (200 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          i.Continuous EPDM sheet vapor barrier.
          j.Reactofire fire blanket system.
          3.Wall/Ceiling:
          a.Flat:Semi-recessed continuous aluminum drywall frame with elevated aluminum plate; JointMaster-481-A07 (wall/wall and ceiling/ceiling).
          b.Flat: Surface mounted continuous aluminum frame with elevated aluminum plate; JointMaster-491-A07 (wall/wall and ceiling/ceiling).
          c.Corner: Semi-recessed continuous aluminum drywall frame with elevated bent aluminum plate; JointMaster-481-A09 (wall/corner and wall/ceiling).
          d.Corner:Surface mounted continuous aluminum frame with elevated bent aluminum plate; JointMaster-491-A09 (wall/corner and wall/ceiling).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          e.Joint Width: 2 inches (50 mm).
          f.Joint Width: 3 inches (75 mm).
          g.Joint Width: 4 inches (100 mm).
          h.Joint Width: 6 inches (150 mm).
          i.Joint Width: 8 inches (200 mm).
          j.Joint Width: 12 inches (300 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          k.Reactofire fire blanket system.
 
          F.Seismic Floor Joint Cover Assemblies: "Pop-Up" type; JointMaster 500 Series; recessed aluminum frame with tapered central pan held in place by steel centering bar and compression spring assembly, designed to pop up under seismic movement; JointMaster-501-A01 (floor/floor) and -501-A02 (floor/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          1.Joint Width: 2 inches (50 mm).
          2.Joint Width: 3 inches (75 mm).
          3.Joint Width: 4 inches (100 mm).
          4.Joint Width: 6 inches (150 mm).
          5.Joint Width: 8 inches (200 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          6.Continuous EPDM sheet vapor barrier.
          7.Reactofire fire blanket system.
 
          G.Seismic Floor Joint Cover Assemblies: Heavy Duty Glide Plate JointMaster 700 Series; recessed heavy duty aluminum frame.
          1.Heavy Duty Center Bar System: Continuous aluminum plate with steel centering bar mechanism; JointMaster-721-A01 (floor/floor) and -721-A02 (floor/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 2 inches (50 mm).
          b.Joint Width: 4 inches (100 mm).
          c.Joint Width: 6 inches (150 mm).
          d.Joint Width: 8 inches (200 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          e.Continuous EPDM sheet vapor barrier.
          f.Reactofire fire blanket system.
          2.Recessed Mount Heavy Duty Center Bar System: JointMaster 741-A01 (floor/floor) and 741-A02 (floor/wall):
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width - 2 inches (50mm).
          b.Joint Width - 4 inches (101mm).
          c.Joint Width - 6 inches (152mm).
          ** NOTE TO SPECIFIER ** The following three paragraphs are optional, delete if not required.
          d.Vapor barrier.
          e.Reactofire blanket.
          f.Reactofire mineral wool and silicone sealant system.
          3.Surface Mount Heavy Duty Center Bar System: JointMaster 757-A01 (floor/floor) and 757-A02 (floor/wall) and JointMaster 767-A01 (floor/floor):
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width - 4 inches (101mm).
          b.Joint Width - 6 inches (152mm).
          c.Joint Width - 8 inches (203mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          d.Vapor barrier.
          e.Reactofire mineral wool and silicone sealant system.
 
          2.4EXTERIOR SYSTEMS
          ** NOTE TO SPECIFIER ** Delete expansion joint cover types not required for project, or delete this entire article if no exterior systems are required. If more than one type is needed, either schedule on drawings or add statements to specifications, describing locations for each expansion joint cover type.
 
          A.Seismic Joint Cover Assemblies: JointMaster 600 Series.
          1.Walls and Ceilings, Elastomeric Seal: Continuous Santoprene seal retained by continuous aluminum frame at each side of joint; JointMaster-611-A07 (wall/wall and ceiling/ceiling).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 2 inches (50 mm).
          b.Joint Width: 3 inches (75 mm).
          c.Joint Width: 4 inches (100 mm).
          d.Joint Width: 6 inches (150 mm).
          e.Joint Width: 8 inches (200 mm).
          f.Joint Width: 12 inches (300 mm).
          ** NOTE TO SPECIFIER ** The following two paragraph is optional, delete if not required.
          g.Reactofire fire blanket system.
          h.Reactofire mineral wool and silicone sealant system.
          2.Walls and Ceilings, Elastomeric Seal: Continuous Santoprene seal and continuous integral backseal retained by continuous aluminum frame at each side of joint; JointMaster-615-A07 (wall/wall and ceiling/ceiling) and -615-A09 (wall/corner and wall/ceiling).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 2 inches (50 mm).
          b.Joint Width: 3 inches (75 mm).
          c.Joint Width: 4 inches (100 mm).
          d.Joint Width: 6 inches (150 mm).
          e.Joint Width: 8 inches (200 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          f.Reactofire fire blanket system.
          g.Reactofire mineral wool and silicone sealant system.
          3.Walls and Ceilings, 12 Inch (300 mm) Wide Joints: Continuous Santoprene seal retained by continuous aluminum frame at each side of joint and continuous center frame assembly mounted on expandable pantograph assembly; JointMaster-616-A07 (wall/wall and ceiling/ceiling) and -616-A09 (wall/corner and wall/ceiling).
          a.Joint Width: 12 inches (300 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          b.Reactofire mineral wool and silicone sealant system.
          4.Walls, Surface Mounted Center Bar System: Continuous surface mounted aluminum frame with elevated continuous aluminum plate retained by centering bar mechanism; JointMaster-651-A07 (wall/wall) and -651-A09 (wall/corner).
          a.Vapor Barrier: Continuous EPDM sheet.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          b.Joint Width: 1 inch (25 mm).
          c.Joint Width: 2 inches (50 mm).
          d.Joint Width: 4 inches (100 mm).
          e.Joint Width: 6 inches (150 mm).
          ** NOTE TO SPECIFIER ** Wall/Corner joints are not available in 8 and 12 inch widths.
          f.Joint Width: 8 inches (200 mm).
          g.Joint Width: 12 inches (300 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          h.Reactofire fire blanket system.
          5.Roof Joints: Continuous surface mounted aluminum frame with elevated continuous aluminum plate retained by centering bar mechanism; JointMaster-661-A01 (roof/roof) and -661-A02 (roof/wall).
          a.Vapor Barrier: Continuous EPDM sheet.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          b.Joint Width: 1 inch (25 mm).
          c.Joint Width: 2 inches (50 mm).
          d.Joint Width: 4 inches (100 mm).
          e.Joint Width: 6 inches (150 mm).
          ** NOTE TO SPECIFIER ** Roof/Wall joints are not available in 8 and 12 inch widths.
          f.Joint Width: 8 inches (200 mm).
          g.Joint Width: 12 inches (300 mm).
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          h.Reactofire fire blanket system.
          6.Roof Joints: Elastomeric bellows.
          a.Roof Cants: 4 inch (100 mm) metal flanges for setting in mastic; JointMaster-672-A01 (cant/cant) and -672-A02 (cant/wall).
          b.Roof Curbs: Preformed metal curb flanges for setting in mastic; JointMaster-674-A01 (curb/curb) and -674-A02 (curb/wall).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          c.Joint Width: 2 inches (50 mm).
          d.Joint Width: 3 inches (75 mm).
          e.Joint Width: 4 inches (100 mm).
          f.Joint Width: 6 inches (150 mm).
          g.Joint Width: 8 inches (200 mm).
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional, delete if not required.
          h.Continuous EPDM sheet vapor barrier.
          i.Preformed intersections and transitions as shown on drawings.
 
          B.Parking and Bridge Deck Joint Assemblies: JointMaster Exterior Series; elastomeric compression seals.
          1.Hollow cellular elastomeric compression seal with embedded wings; JointMaster CR Series (floor/floor).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 1-1/2 inches (38 mm).
          c.Joint Width: 2 inches (50 mm).
          d.Joint Width: 2-1/4 inches (57 mm).
          e.Joint Width: 2-3/4 inches (70 mm).
          f.Joint Width: 3-1/4 inches (81 mm).
          2.Accordian folded elastomeric compression seal with embedded wings; JointMaster WM Series (floor/floor).
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1-3/4 inches (44 mm).
          b.Joint Width: 2-1/4 inches (57 mm).
          c.Joint Width: 2-3/4 inches (70 mm).
          3.Hollow cellular elastomeric compression seal adhesive bonded to sides of joint; JointMaster AR Series (floor/floor) architectural.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 1-1/2 inches (38 mm).
          1)Minimum width: 15/16 inch (24 mm).
          2)Maximum width: 1-7/8 inch (47 mm).
          c.Joint Width: 1-1/2 inches (38 mm).
          1)Minimum width: 1-1/8 inches (28 mm).
          2)Maximum width: 2-1/8 inches (53 mm).
          d.Joint Width: 2 inches (50 mm).
          e.Joint Width: 2-1/8 inches (53 mm).
          f.Joint Width: 2-3/8 inches (60 mm).
          g.Joint Width: 2-7/8 inches (72 mm).
          h.Joint Width: 3-1/2 inches (88 mm).
          4.Hollow cellular elastomeric compression seal adhesive bonded to sides of joint; JointMaster BR Series (floor/floor), engineered for bridge decks.
          ** NOTE TO SPECIFIER ** Select Joint width(s) from the following options. Delete those not required.
          a.Joint Width: 1 inch (25 mm).
          b.Joint Width: 1-1/4 inches (31 mm).
          c.Joint Width: 1-3/8 inches (34 mm).
          d.Joint Width: 1-1/2 inches (38 mm).
          e.Joint Width: 1-3/4 inches (44 mm).
          f.Joint Width: 2 inches (50 mm).
          g.Joint Width: 2-1/4 inches (56 mm).
          h.Joint Width: 2-3/4 inches (69 mm).
 
          C.Foam Seal Joint Systems:
          ** NOTE TO SPECIFIER ** Select Joint System(s) from the following options. Delete those not required.
          1.Low density closed cell, cross linked ethylene vinyl acetate polyethylene co-polymer foam joint sealant. Floor/floor, floor/wall, wall/wall and wall/corner.
          a.Joint Width - 3/4 inch (19mm) to 4 inches (100mm) in 1/4 inch (6.35mm) increments.
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          b.Reactofire mineral wool and silicone sealant system.
          2.Open cell polyurethane, pre-compressed, foam joint sealant impregnated with manufacturer's weatherproofing agent, with colored silicone face.
          a.Joint Width - 1/2 inch (13mm) to 4 inch (100mm) in 1/2 inch (6.35mm) increments and 5 inch (127mm) to 8 inch (203mm) in 1 inch (25mm) increments.
          ** NOTE TO SPECIFIER ** The following paragraph is optional, delete if not required.
          b.Reactofire mineral wool and silicone sealant system.
 
          PART 3EXECUTION
 
          3.1EXAMINATION
 
          A.Verify that substrates are in proper condition to receive installation of expansion joint covers.
          1.Confirm that blockout dimensions are appropriate for recessed systems.
          2.Confirm that selected expansion joint covers are appropriate for actual joint dimensions.
 
          3.2PREPARATION
 
          A.Clean substrate before installation to remove dust, debris, and loose particles.
 
          3.3INSTALLATION
 
          A.General: Install expansion joint covers in strict accordance with manufacturer's instructions. Align work level and flush with adjacent surfaces, and rigidly anchor to substrate. Make allowances for structural gap that varies at time of installation from nominal design gap.
          ** NOTE TO SPECIFIER ** Delete paragraph below if no selected expansion joint covers include centering bars or spring clips.
 
          B.Metal Frames: Perform cutting and fitting required to install the joint system. All frames must be set on, and in continuous contact with solid substrate. Anchor at internvals as required by Manufacturer’s systems.
          ** NOTE TO SPECIFIER ** Delete paragraph below if no expansion joint covers are to be installed in fire rated construction.
 
          C.Fire Rated Assemblies: Where expansion joint covers are required in fire rated construction, install fire rated systems to comply with manufacturer's requirements and in strict conformance with tested assemblies.
          ** NOTE TO SPECIFIER ** Delete paragraph below if no required expansion joint covers include vapor barriers.
 
          D.Vapor Barriers: Where required, install in strict accordance with manufacturer's instructions to assure continuous protection. Install drainage fittings where required by project circumstances.
 
          3.4INSPECTION
 
          A.Prior to payment by the general contractor, a designated inspector will select a random 10 percent of the joint systems and have the assembly covers removed for inspection. The purpose of this will be to inspect the concrete substrates, filler materials, anchorage of the joint assembly and fire barrier systems that are hidden from view.
 
          B.Corrective action will be designated as required. Should a majority of the 10 percent scope be deemed as unacceptable, the Inspector will require that additional lengths be opened for inspection. This process will continue until the Inspector and general contractor are satisfied and the Manufacturer’s warranties are secured.
 
          3.5ADJUSTING AND CLEANING
 
          A.Verify that expansion joint covers are plumb and level and are rigidly secured to substrate; make any adjustments required.
 
          B.Clean expansion joint covers and immediate areas of installation, using materials and methods recommended by manufacturer. Remove from project site packaging and debris caused by installation.
 
         
END OF SECTION