Hunter Panels Ventilated Nailbase Insulation Panels
 
         
SECTION 07220
 
         
VENTILATED NAILBASE INSULATION PANELS
 
         
          ** NOTE TO SPECIFIER ** Hunter Panels, manufacturers of rigid polyisocyanurate insulation for commercial and residential buildings, including new construction and retrofit projects.

This section is based on the products of Hunter Panels, which is located at:
15 Franklin Street
Portland, Maine 04101
Phone: (207) 761-5678
Toll Free: (888) 746-1114
Fax: (207) 775-1769
E-mail: info@hpanels.com
Internet: www.hunterpanels.com

Hunter Panels is the developer and producer of high performance ventilated nailbase insulation panels for steep slope roofing applications greater than 3 inches in 12 inches. . A universally accepted substrate for all major types of roof coverings. Hunter panels offers superior compressive strength, competitive pricing and the highest R-value per inch of any insulating material on the planet.

Our products complement the development of sustainable design practices and fundamentally enhance the building's effectiveness in the environment by reducing energy consumption. Our products components include OSB and plywood that are USGBC certified and our insulating foam contains a recycled content to promote sustainable design practices and significantly reduce energy consumption. It's our way of helping keep the world green.
         
 
          PART 1GENERAL
 
          1.1SECTION INCLUDES
          ** NOTE TO SPECIFIER ** Delete any paragraphs below not applicable to project.
 
          A.Section includes ventilated nailbase insulation panel system.
 
          1.2RELATED SECTIONS
          ** NOTE TO SPECIFIER ** Delete sections below not relevant to this project; add others as required.
 
          A.Section 05300 - Metal Deck.
 
          B.Section 06110 - Wood Framing: Structural deck sheathing.
 
          C.Section 06114 - Wood Blocking.
 
          D.Section 06150 - Wood Decking.
 
          E.Section 07260 - Vapor Retarders.
 
          F.Section 07310 - Roof Shingles.
 
          G.Section 07320 - Roof Tiles.
 
          1.3REFERENCES
          ** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section; add others as required.
 
          A.ASTM C 209 - Methods of Testing Insulating Board, Structural and Decorative.
 
          B.ASTM C 1289 - Specifications for Faced Rigid Cellular Polyisocyanurate Thermal Insulating Board.
 
          C.ASTM C 1303 - Standard Test Method for Estimating the Long Term Change in the Thermal Resistance of Unfaced Closed Cell Plastic Foams by Slicing and Scaling Under Controlled Laboratory Conditions.
 
          D.ASTM D 1621 - Test Methods for Compressive Properties of Rigid Cellular Plastics.
 
          E.ASTM D 2126 - Test Method for Response of Rigid Cellular Plastics to Thermal and Humid Aging.
 
          F.ASTM E 84 - Surface Burning Characteristics of Building Materials.
 
          G.ASTM E 96 - Test Method for Water Vapor Transmission of Materials.
 
          H.CAN/ULC S770 - Standard Test Method for Determination of Long Term Thermal Resistance of Closed Cell Plastic Thermal Insulating.
 
          I.UL 1256 - Fire Test of Roof Deck Constructions.
 
          J.PS2 - Performance Standard for Wood-based Structural-use Panels.
 
          1.4SYSTEM DESCRIPTION
 
          A.Physical properties (Foam Core):
          1.Compressive Strength: ASTM D 1621 and ASTM C 1289, Type II, 20 psi (138 kPa) minimum for Grade 2 and 25 psi (172 kPa) for Grade 3.
          2.Dimensional Stability: ASTM D 2126, 2 percent linear change (7 days).
          3.Moisture Vapor Transmission: ASTM E 96, < 1 perm ((57.5ng/(Pa•s•m2)).
          4.Water Absorption: ASTM C 209, < 1 percent by volume.
          5.Flame Spread (foam core): ASTM E 84, <450.
          6.Service Temperature: -100 degrees to 250 degrees F (-73 degrees C to 122 degrees C).
 
          B.Foam Core R Values: Based on Long Term Thermal Resistance in accordance with ASTM C 1289, using techniques from CAN/ULC S770 based on ASTM C 1303.
 
          C.UL Assemblies: Insulated metal deck assemblies - UL 1256 (nos. 120, 123) TGDY. R20624 Shingle Deck Accessory; Cool-Vent roof insulation is classified for use with any Class A, B, or C asphalt glass mat or asphalt organic shingles, metal or tile roof coverings.
          ** NOTE TO SPECIFIER ** Delete the following paragraphs if LEED is not applicable.
 
          D.USGBC LEED requirements:
          1.OSB or plywood must be FSC certified. Manufacturer of vented nailbase to supply USGBC Chain-of-Custody number.
          2.Polyisocyanurate to have a minimum of 17 percent recycled content by weight.
 
          1.5SUBMITTALS
 
          A.Submit under provisions of Section 01300.
 
          B.Product Data: Manufacturer's data sheets on roof panels and fasteners to be used, including:
          1.Preparation instructions and recommendations.
          2.Storage and handling requirements and recommendations.
          3.Installation methods.
          ** NOTE TO SPECIFIER ** Delete the following paragraphs if LEED is not applicable.
 
          C.LEED Submittals: Provide documentation of how the requirements of Credit will be met:
          1.List of proposed materials with recycled content. Indicate post-consumer recycled content and pre-consumer recycled content for each product having recycled content.
          2.Product Data and certification letter indicating percentages by weight of post-consumer and pre-consumer recycled content for products having recycled content.
          3.Provide USGBC Chain of Custody number for OSB or plywood materials.
 
          D.Manufacturer's Certificate: Certify panels will conform to specified performance requirements.
 
          1.6QUALITY ASSURANCE
 
          A.Manufacturer Qualifications: Manufacturer shall be a company that regularly manufactures and assembles ventilated nailbase insulation in house with no outside fabrication operations.
 
          1.7DELIVERY, STORAGE, AND HANDLING
 
          A.Store products off the ground, in dry conditions, under cover and in manufacturer's unopened packaging until ready for installation.
 
          B.The manufacturer's plastic wrapping is provided for protection during shipment only. Replace any panels that become wet before insulation
 
          PART 2PRODUCTS
 
          2.1MANUFACTURERS
 
          A.Acceptable Manufacturer: Insulating panels shall be Cool Vent produced by Hunter Panels, which is located at: 15 Franklin St. ; Portland, ME 04101; Toll Free Tel: 888-746-1114; Tel: 207-761-5678; Fax: 877-775-1769; Email: request info; Web: www.hunterpanels.com
          ** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
          B.Substitutions: Not permitted.
 
          C.Requests for substitutions will be considered in accordance with provisions of Section 01600.
 
          2.2PANEL CONSTRUCTION
 
          A.Panels shall consist of a top layer of APA rated Oriented Strand Board (OSB) or Plywood, a middle layer of vented air space consisting of 1 inch (25.4 mm) thick wood spacers and a bottom layer of black fiber reinforced faced polyisocyanurate foam insulation.
          1.Polyisocyanurate foam insulation shall conform to ASTM C 1289, Type II with a compressive strength of:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the paragraph not required.
          a.Grade 2 (20 psi (138 kPa) minimum) .
          b.Grade 3 (25 psi (172 kPa) minimum).
          2.Multiple top layer substrate shall conform to PS2 and shall be as follows:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the paragraph not required.
          a.OSB with a thickness of:
          ** NOTE TO SPECIFIER ** Select one of the two following OSB types and delete the paragraph that is not required. Include FSD LEED certification if required.
          1)Type:
          a)Standard sheathing grade.
          b)FSC LEEDS certified.
          ** NOTE TO SPECIFIER ** Select one of the following OSB thicknesses and delete the paragraphs that are not required.
          2)With a thickness of:
          a)7/16 inch (11.1 mm).
          b)5/8 inch (15.9 mm).
          b.CDX Plywood:
          ** NOTE TO SPECIFIER ** Select one of the two following plywood types and delete the paragraph that is not required. Include FSD LEED certification if required.
          1)Type:
          a)Standard sheathing grade.
          b)Fire-treated.
          c)FSC LEEDS certified.
          ** NOTE TO SPECIFIER ** Select one of the following plywood thicknesses and delete the paragraphs that are not required.
          2)With a thickness of:
          a)5/8 inch (15.9 mm).
          b)3/4 inch (19.1 mm).
          3.Wood spacers shall be solid wood. Other materials such as woodfiber, EPS, or strips of foam will not be acceptable. Spacers shall be not more than 12 inches (304.8 mm) apart in the both the horizontal and vertical direction.
 
          B.Vented airspace shall be a minimum of 1 inch (25 mm) in depth and provide not less than 92 percent overall free air movement through the panel. It shall have 55 percent or greater lateral free air movement. Panels shall be manufactured to provide cross directional ventilation without additional material being incorporated into the construction. Provide an airspace of:
          ** NOTE TO SPECIFIER ** Select one of the following airspace thicknesses and delete the paragraph not required.
          1.1 inch (25 mm) air space.
          2.1.5 inch (38 mm) air space.
          3.2 inch (51 mm) air space.
 
          C.Panel with wood substrate as specified shall be factory rabbetted 1/8 inch (3.2 mm) on all sides to prove for expansion of substrate.
 
          2.3PANEL TYPES
          ** NOTE TO SPECIFIER ** Select the required panel paragraphs from the following list. Delete the paragraphs not required. If more than one product is required identify the location of the materials required on the Drawings.
 
          A.Cool-Vent panels shall be 4 feet by 8 feet (1220 mm by 2440 mm) with an air space consisting of a minimum 1 inch (25.4 mm) and an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 2.5 inches (64 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 2.8 inches (71 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 3.0 inches (76 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 3.3 inches (81 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 3.5 inches (89 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 3.8 inches (96 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 4.0 inches (102 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 4.3 inches (108 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 4.5 inches (114 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 4.8 inches (120 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 5.0 inches (127 mm), R Value 21.7 flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 5.3 inches (133 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 5.5 inches (140 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 5.8 inches (146 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 6.0 inches (152 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          B.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 5/8 inch (15.9 mm) OSB or CDX and a vented airspace of 1 inch (25 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 2.6 inches (66 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 2.9 inches (74 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 3.1 inches (79 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 3.4 inches (86 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 3.6 inches (91 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 3.9 inches (99 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 4.1 inches (104 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 4.3 inches (109 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 4.6 inches (118 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 4.9 inches (124 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 5.1 inches (130 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 5.4 inches (137 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 5.6 inches (142 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 5.9 inches (150 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 6.1 inches (155 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          C.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 3/4 inch (19 mm) CDX and a vented airspace of 1 inch (25 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 2.7 inches (69 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 3.0 inches (76 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 3.2 inches (81 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 3.5 inches (89 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 3.7 inches (94 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 4.0 inches (102 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 4.2 inches (107 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 4.5 inches (114 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 4.7 inches (119 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 5.0 inches (127 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 5.2 inches (132 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 5.5 inches (140 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 5.7 inches (145 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 6.0 inches (152 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 6.2 inches (158 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          D.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 7/16 inch (11.1 mm) OSB and a vented airspace of 1.5 inches (38 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 3.0 inches (76 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 3.3 inches (81 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 3.5 inches (89 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 3.8 inches (94 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 4.0 inches (102 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 4.3 inches (107 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 4.5 inches (114 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 4.8 inches (119 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 5.0 inches (127 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 5.3 inches (132 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 5.5 inches (140 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 5.8 inches (145 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 6.0 inches (152 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 6.3 inches (158 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 6.5 inches (165 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          E.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 5/8 inch (15.9 mm) OSB or CDX and a vented airspace of 1.5 inches (38 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 3.1 inches (79 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 3.4 inches (84 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 3.6 inches (91 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 3.9 inches (97 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 4.1 inches (104 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 4.4 inches (109 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 4.6 inches (117 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 4.9 inches (122 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 5.1 inches (130 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 5.4 inches (135 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 5.6 inches (142 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 5.9 inches (147 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 6.1 inches (155 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 6.4 inches (160 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 6.6 inches (168 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          F.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 3/4 inch (19.1 mm) CDX and a vented airspace of 1.5 inches (38 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 3.2 inches (81 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 3.5 inches (86 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 3.7 inches (94 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 4.0 inches (99 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 4.2 inches (107 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 4.5 inches (112 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 4.7 inches (119 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 5.0 inches (124 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 5.2 inches (132 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 5.5 inches (137 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 5.7 inches (145 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 6.0 inches (150 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 6.2 inches (157 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 6.5 inches (163 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 6.7 inches (170 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          G.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 7/16 inch (11.1 mm) OSB and a vented airspace of 2 inches (51 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 3.5 inches (89 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 3.8 inches (99 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 4.0 inches (102 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 4.3 inches (107 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 4.5 inches (114 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 4.8 inches (119 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 5.0 inches (127 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 5.3 inches (132 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 5.5 inches (140 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 5.8 inches (145 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 6.0 inches (152 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 6.3 inches (157 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 6.5 inches (165 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 6.8 inches (170 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 7.0 inches (178 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          H.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 5/8 inch (15.9 mm) OSB or CDX and a vented airspace of 2 inches (51 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 3.6 inches (91 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 3.9 inches (97 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 4.1 inches (104 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 4.4 inches (109 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 4.6 inches (117 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 4.9 inches (122 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 5.1 inches (130 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 5.4 inches (135 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 5.6 inches (142 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 5.9 inches (147 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 6.1 inches (155 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 6.4 inches (160 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 6.6 inches (168 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 6.9 inches (173 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 7.1 inches (180 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          I.Cool-Vent panels: 4 feet by 8 feet (1220 mm by 2440 mm) with multiple top layer substraight of 3/4 inch (19.1 mm) CDX and a vented airspace of 2 inches (51 mm). Panel shall have an overall thickness, R-value, and flute spanability as follows:
          ** NOTE TO SPECIFIER ** Select the required panel thickness paragraph from the following list. Delete the paragraphs not required. If more than one thickness is required identify the location of the materials required on the Drawings.
          1.Thickness 3.7 inches (94 mm), R Value 6.0, flute spanability 2-5/8 inches (67 mm).
          2.Thickness 4.0 inches (99 mm), R Value 7.8, flute spanability 4-3/8 inches (111.13 mm).
          3.Thickness 4.2 inches (107 mm), R Value 9.0, flute spanability 4-3/8 inches (111.13 mm).
          4.Thickness 4.5 inches (112 mm), R Value 10.9, flute spanability 4-3/8 inches (111.13 mm).
          5.Thickness 4.7 inches (119 mm), R Value 12.1, flute spanability 4-3/8 inches (111.13 mm).
          6.Thickness 5.0 inches (124 mm), R Value 14.0, flute spanability 4-3/8 inches (111.13 mm).
          7.Thickness 5.2 inches (132 mm), R Value 15.3, flute spanability 4-3/8 inches (111.13 mm).
          8.Thickness 5.5 inches (137 mm), R Value 17.2, flute spanability 4-3/8 inches (111.13 mm).
          9.Thickness 5.7 inches (144 mm), R Value 18.5, flute spanability 4-3/8 inches (111.13 mm).
          10.Thickness 6.0 inches (150 mm), R Value 20.4, flute spanability 4-3/8 inches (111.13 mm).
          11.Thickness 6.2 inches (157 mm), R Value 21.7, flute spanability 4-3/8 inches (111.13 mm).
          12.Thickness 6.5 inches (163 mm), R Value 23.7, flute spanability 4-3/8 inches (111.13 mm).
          13.Thickness 6.7 inches (170 mm), R Value 25.0, flute spanability 4-3/8 inches (111.13 mm).
          14.Thickness 7.0 inches (175 mm), R Value 26.9, flute spanability 4-3/8 inches (111.13 mm).
          15.Thickness 7.2 inches (183 mm), R Value 28.1, flute spanability 4-3/8 inches (111.13 mm).
 
          2.4PANEL FASTENERS
 
          A.Fasteners shall be FM Approved Hunter Panel SIP/SD Panel Fasteners for steel deck or Hunter Panel SIP/WD Panel fasteners for wood deck. Fasteners have a 3/16 inch (5 mm) shank, and are a corrosion resistant type with oversized heads. Length of fasteners shall be as recommended by the panel manufacturer. Fasteners shall be equal to the panel depth plus a minimum of 1inch (25 mm) penetration into the structural substrate.
 
          PART 3EXECUTION
          ** NOTE TO SPECIFIER ** See Hunter Panel Installation Guide for recommended fastening patterns and installation methods. Coordinate roof covering installation requirements with roof covering manufacturer.
 
          3.1EXAMINATION
 
          A.Do not begin installation until structural deck has been properly prepared.
 
          B.Verify deck, adjacent materials, and structural backing is dry and ready to receive insulation.
 
          C.Verify deck surface is flat, free of fins or protrusions and irregularities.
 
          D.If deck preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
 
          3.2PREPARATION
          ** NOTE TO SPECIFIER ** The incorporation of a vapor barrier or retarder within the roofing assembly is highly recommended when the project is located in Zones 1, 2 or 3 of the United States. Cool-Vent is not intended to substitute for a vapor barrier. Vapor barrier or retarder when used shall have a perm rating of 0.5 or less as determined by ASTM E-96.
 
          A.Apply vapor barrier and or retarder, as specified by the Architect or required by the local building code, to decking prior to the installation.
 
          B.Apply proper ridge and soffit vents to create an effective eave to ridge venting system in conjunction with Cool-Vent.
 
          3.3INSTALLATION
          ** NOTE TO SPECIFIER **Select paragraph A and paragraph B or C for steel decks. Select paragraph A and paragraph C or D for wood decks. Delete the paragraphs not required. If more than one paragraph is required indicate the location of each material on the Drawings.
 
          A.Install panels with the wood (OSB/Plywood) side face up. Place panels in the manufacturers recommended pattern. Fasten the panels through the panel spacers using Hunter Panels approved threaded fasteners. Only factory assembled panels will be accepted.
          ** NOTE TO SPECIFIER **For metal deck select one of the following two paragraphs and delete the paragraph not required. Caution: Fasteners may not be positioned on a wood spacer due to flute span. DO NOT OVERTORQUE THE FASTENER. This will cause a concave depression of the wood substrate of the Hunter Panel leading to a possible aesthetic concern and possible crushing of the foam. Foam performance properties will not be affected.
 
          B.For application into steel deck the minimum number of fasteners shall be 18 per 4 foot by 8 foot (1220 mm by 2440 mm) panel for slopes up to 7 inches (178 mm) in 12 inches (304 mm). Fasteners in metal deck shall penetrate the top flute of the steel to a depth of 1 inch (25 mm).
 
          C.For application into steel deck the minimum number of fasteners shall be 24 per 4 foot by 8 foot (1220 mm by 2440 mm) panel for slopes over 8 inches (203 mm) in 12 inches (304 mm). Fasteners in metal deck shall penetrate the top flute of the steel to a depth of 1 inch (25 mm).
 
          3.4PROTECTION
 
          A.Protect installed products until completion of project.
 
          B.Cover the top and edges of unfinished roof panel work to protect it from the weather and to prevent accumulation of water in the cores of the panels.
 
          C.Do not leave panels exposed to moisture. Wet panels shall be removed or allowed to completely dry prior to application of vapor barrier and/or roof covering.
 
          D.Apply only enough Cool-Vent per day that can be covered by a required and approved synthetic underlayment and approved shingles, slate, tile or standing seam.
 
         
END OF SECTION