. This section is based on the products of Bamco, Inc., which is located at: 30 Baekland Avenue. Middlesex, NJ 08846. Toll Free Te1: (800) 245-0210. Tel: (732) 302-0889. Fax: (732) 302-9456. Email: ctellone@bamcoinc.com. Web: www.bamcoinc.org. . BAMCO inc. offers state-of-the-art exterior metal panel systems for commercial, institutional, governmental, manufacturing, and residential projects. We currently service customers in over 27 states.Founded in 1986 as an installer of aggregate and cement boarded panels, BAMCO naturally gravitated to the advantages of metal panel systems. By 1991, BAMCO inc. had begun designing and fabricating its own line of composite metal panel systems. BAMCO now provides design, engineering, estimating, fabrication, testing, and installation services with a comprehensive and highly skilled staff of engineers, project managers, field and shop superintendents and construction professionals for a full-service experience designed to reduce the costs, lead times and workload of our valued customers. . | ||||||||||||||||||||||||||||||||||||||||||||||||||
| PART 1 | GENERAL | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.1 | SECTION INCLUDES | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Metal Wall Panels. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.2 | RELATED SECTIONS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Section 05100: Structural Metal Framing: Framing and blocking. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Section 06100: Rough Carpentry: Framing and Blocking. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Section 07210: Building Insulation: Wall insulation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Section 07620: Sheet Metal Flashing and Trim. Edges, copings and related flashings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Section 07920: Joint Sealers. | |||||||||||||||||||||||||||||||||||||||||||||||||
| F. | Section 09200: Plaster and Gypsum Wall Finishes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.3 | REFERENCES | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | American Architectural Manufacturer's Association (AAMA): | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | AAMA 501.1 - Standard test method for metal curtain walls for water penetration using dynamic pressure. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | AAMA 508.5 - Voluntary Test Method and Specification for Pressure Equalized Rain Screen Wall Cladding Systems. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | AAMA 2605 - Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | American Society of Civil Engineers (ASCE): | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | ASCE 7- Minimum Design Loads for Buildings and Other Structures. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | ASTM International (ASTM): | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | ASTM B 117 - Standard Practice for Operating Salt Spray (Fog) Apparatus. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | ASTM C 481 - Standard Test Method for Laboratory Aging of Sandwich Constructions. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | ASTM D 1308 - Standard Test Method for Effect of Household Chemicals on Clear and Pigmented Organic Finishes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | ASTM D 1781 - Standard Test Method for Climbing Drum Peel for Adhesives. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | ASTM D 2244 - Standard Practice for Calculation of Color Tolerances and Color Differences from Instrumentally Measured Color Coordinates. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | ASTM D 2247 - Standard Practice for Testing Water Resistance of Coatings in 100 Percent Relative Humidity. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | ASTM D 2794 - Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | ASTM D 3359 - Standard Test Methods for Measuring Adhesion by Tape Test. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 9. | ASTM D 3363 - Standard Test Method for Film Hardness by Pencil Test. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 10. | ASTM D 4214 - Standard Test Methods for Evaluating the Degree of Chalking of Exterior Paint Films. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 11. | ASTM E 72 - Standard Test Methods of Conducting Strength Tests of Panels for Building Construction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 12. | ASTM E 84 - Test Methods for Surface Burning Characteristics of Building Materials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 13. | ASTM E 119 - Test Methods for Fire Tests of Building Construction and Materials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 14. | ASTM E 283 - Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors under Specified Pressure Differences across the Specimen. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 15. | ASTM E 330 - Test Method for Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 16. | ASTM E 331 - Test Method for Water Penetration of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 17. | ASTM E 1886 - Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 18. | ASTM E 1996 - Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors and Impact Protective Systems Impacted by Windborne Debris in Hurricanes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Underwriters Laboratories, Inc. (UL): | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | UL 263 - Fire Resistance Tests of Building Construction and Materials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | UL 723 - Test for Surface Burning Characteristics of Building Materials. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | UL Fire Resistance Directory. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | UL 1715 Room Corner Test. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.4 | PERFORMANCE REQUIREMENTS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Air Infiltration: Maximum 0.01 cfm/sf in accordance with ASTM E 283 at a static-air-pressure difference of 6.24 lbf/sf (300 Pa), using minimum 73 1/8 inch by 49 1/4 inches (1857 mm by 1251mm) test panel that includes horizontal and vertical joints. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Water Penetration: Dynamic Testing: No uncontrolled water penetration per AAMA 501.1 at a minimum pressure differential of 25 lb/sf (1.20 kPa) using a minimum 73 1/8 inch by 49 1/4 inches (1857 mm by 1251mm) test panel that includes horizontal and vertical joints. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Structural Performance: Provide metal wall panel assemblies capable of withstanding the effects of indicated loads and stresses within limits and under conditions indicated, per ASTM E 72: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Wind Loads: Determine loads based on uniform pressure indicated on Drawings or calculated per IBC 2003 whichever is more stringent. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Deflection Limits: Withstand test pressures of inward and outward wind-load design pressures with maximum deflection of L/60 of the span with no failure. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Secondary Framing: Design secondary framing system according to AISI "Standard for Cold-Formed Steel Framing - General Provisions." | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Provide bearing surface for metal wall panels at the following locations: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Horizontal Panel System: At vertical joints 4 inches minimum (102 mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Vertical Panel System: At horizontal stack joints 4 inches minimum (102 mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Horizontal Panel Joint Performance: Static test per ASTM E 331 with horizontal seals removed - 1 inch (25 mm) in 10 feet (3050 mm) lengths to simulate seal defects. No uncontrolled water penetration permitted at a pressure of 25 lb/sf (.90 kPa). | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Pressure Equalization of Horizontal Joinery: Passes the Criteria for a Pressure Equalized Horizontal Joint in accordance with AAMA 508-05, a test method for Pressure Equalized Rain Screen Wall Systems. | |||||||||||||||||||||||||||||||||||||||||||||||||
| F. | Seismic Performance: Comply with ASCE 7, "Minimum Design Loads for Buildings and Other Structures": Section 9, "Earthquake Loads." | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.5 | SUBMITTALS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Submit under provisions of Section 01300. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Product Data: Manufacturer's data sheets on each product to be used, including: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Preparation instructions and recommendations. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Storage and handling requirements and recommendations. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Installation methods. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Shop Drawings: Submit shop drawings detailing plan, elevation and section views as necessary to determine proper fabrication and installation methods. Coordinate locations with those found in the contract drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | LEED Submittals: Credit MR 4.1/MR4.2, Manufacturer's Product Data indicating the following: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Percentages by weight of post-consumer and pre-consumer recycled content. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Indicate total weight of products provided. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Include statement indicating costs for each product having recycled content. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Selection Samples: For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns. | |||||||||||||||||||||||||||||||||||||||||||||||||
| F. | Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square, that represent the actual product, color, and patterns. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.6 | QUALITY ASSURANCE | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Manufacturer Qualifications: All primary products specified in this section will be supplied by a single manufacturer with a minimum of ten (10) years experience. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Installer Qualifications: All products listed in this section are to be installed by a single installer with a minimum of five (5) years demonstrated experience in installing products of the same type and scope as specified. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Calculations supporting structural performance of the wall panels shall be prepared by a professional structural engineer. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Fire Resistance Ratings: Where indicated by design designations, provide metal wall panels tested per ASTM E 119 or UL Standard 263 by a testing and inspecting agency acceptable to authorities having jurisdiction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Fire-Test-Response Characteristics per ASTM E 84 or UL Standard 723: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Flame spread index: 25 or less. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Smoke developed index: 450 or less. | |||||||||||||||||||||||||||||||||||||||||||||||||
| F. | FM Global Listing: Class 1 Insulating Wall or Ceiling Panel per FMG 4880. | |||||||||||||||||||||||||||||||||||||||||||||||||
| G. | UL Listing for UL 1715 room corner test. | |||||||||||||||||||||||||||||||||||||||||||||||||
| H. | NFPA 286 room corner test. | |||||||||||||||||||||||||||||||||||||||||||||||||
| I. | NFPA 285 ISMA test. | |||||||||||||||||||||||||||||||||||||||||||||||||
| J. | Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Finish areas designated by Architect. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Do not proceed with remaining work until workmanship, color, and sheen are approved by Architect. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Refinish mock-up area as required to produce acceptable work. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.7 | DELIVERY, STORAGE, AND HANDLING | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Store products in manufacturer's unopened packaging until ready for installation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Store and dispose of hazardous materials, and materials contaminated by hazardous materials, in accordance with requirements of local authorities having jurisdiction. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.8 | PROJECT CONDITIONS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1.9 | WARRANTY | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | At project closeout, provide to Owner or Owners Representative an executed copy of the manufacturer's standard limited warranty against manufacturing defect, outlining its terms, conditions, and exclusions from coverage. | |||||||||||||||||||||||||||||||||||||||||||||||||
| PART 2 | PRODUCTS | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.1 | MANUFACTURERS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Acceptable Fabricator: Bamco, Inc.; 30 Baekland Avenue, Middlesex, NJ 08846. ASD. Tel: (732) 302-0889. Tel: (800) 245-0210. Fax: (732) 302-9456. Email: ctellone@bamcoinc.com. Web: www.bamcoinc.org. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Raw Materials Manufacturers: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | ALUCOBOND material manufactured by Alcan Composites USA, Inc.; 208 West 5th Street, Benton, KY 42025 (800-626-3365 or 270-527-4200). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | REYNOBOND PE material manufactured by Alcoa Architectural Products (USA); 50 Industrial Boulevard, Eastman, Georgia 31023 (800-841-7774 or 478-374-4746). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | ALPOLIC material manufactured by Mitsubishi Chemical FP America 1nc.; 401 Volvo Parkway, Chesapeake, Virginia, 23320 (800-422-7270 or 757-548-7826). | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Substitutions: Not permitted. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Requests for substitutions will be considered in accordance with provisions of Section 01600. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.2 | PERFORMANCE REQUIREMENTS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Wind Loads: If system tests are not available, construct mock-ups and perform tests under the direction of an independent third party laboratory, showing compliance with the following minimum standards: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Design panels to withstand the Design Wind Load based upon the local building code, but in no case less than 20 pounds per square foot (psf) and 30 psf on parapet and corner panels. Wind load testing shall be conducted in accordance with ASTM E 330 to obtain the following results: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Normal to the plane of the wall between supports, deflection of the secured perimeter-framing members shall not exceed L/175 or 3/4 inches (19mm), whichever is less. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Normal to the plane of the wall, the maximum panel deflection shall not exceed L/60 of the full span. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Maximum anchor deflection shall not exceed 1/16 inch (1.5mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| d. | At 1 1/2 times design pressure, permanent deflections of framing members shall not exceed L/100 of span length and components shall not experience failure or gross permanent distortion. At connection points of framing members to anchors, permanent set shall not exceed 1/16 (1.5mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Air/Water Infiltration: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Air Infiltration - When tested in accordance with ASTM E 283, air infiltration at 1.57 psf must not exceed 0.06 cfm / sq ft of wall area. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Water Infiltration - Design water infiltration to drain any water leakage occurring at the joints. No water infiltration in any system under a differential static pressure of 6.24 psf after 15 minutes of exposure in accordance with ASTM E331. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Pressure Equalized Rain Screen Systems must comply with AAMA 508-05 Voluntary Test Method and Specification for Pressure Equalized Rain Screen Wall Cladding Systems. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.3 | AIR / MOISTURE BARRIERS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Self Adhering Wall Membrane: Self-adhesive, rubberized asphalt/polyethylene waterproofing membrane meeting the following physical properties: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Thickness 3/64 in. (1 mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Minimum Tensile Strength, Membrane: 400 psi (2.8 MPa). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Minimum Tensile Strength, Film: 5000 psi (34.5 MPa). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Minimum Elongation, to Failure of Rubberized Asphalt: 200 percent. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Minimum Puncture Resistance: 40 lbs (178 N). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Lap Peel Adhesion at Minimum Application Temperature: 4 lbs/in. width (700 N/m). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Maximum Permeance to Water Vapor Transmission: 0.05 perms/(Pa.s.m2) (2.9 ng). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Air permeance of in-place membrane: 0.0002 cfm/sqft (<0.001 L/s/sm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Building Wrap: Spunbonded polyolefin membrane that resists air flow, bulk water and wind driven rain meeting the following physical properties: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Air Penetration: 0.001 cfm/sq ft at 75 Pa, when tested in accordance with ASTM E2178. Type I per ASTM E1677. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Water Vapor Transmission: 28 perms, when tested in accordance with ASTM E96, Method B. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Water Penetration Resistance: Minimum 280 cm when tested in accordance with AATCC Test Method 127. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Basis Weight: Minimum 2.7 oz/sq yd, when tested in accordance with TAPPI Test Method T-410. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Air Resistance: Air infiltration at >1500 seconds, when tested in accordance with TAPPI Test Method T-460. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Tensile Strength: Minimum 38/35 lbs/in., when tested in accordance with ASTM D882, Method A. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Tear Resistance: 12/10 lbs., when tested in accordance with ASTM D1117. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Surface Burning Characteristics: Class A, when tested in accordance with ASTM E84. Flame Spread: 10, Smoke Developed: 10. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.4 | WALL PANELS | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | General: Two sheets of aluminum sandwiching a solid core of extruded thermoplastic material formed in a continuous process with no glues or adhesives between dissimilar materials. The core material shall be free of voids and/or air spaces and not contain foamed insulation material. Products laminated sheet by sheet in a batch process using glues or adhesives between materials shall not be acceptable. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Plans, elevations, details, characteristics, and other requirements indicated are based upon standards by one manufacturer. It is intended that other manufacturers, receiving prior approval, may be acceptable, provided their details and characteristics comply with size and profile requirements, and material/performance standards. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | System must not have any visible fasteners, telegraphing or fastening on the panel faces or any other compromise of a neat and flat appearance. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | System must comply with the applicable provisions of the "Metal Curtain Wall, Window, Storefront, and Entrance Guide Specifications Manual" by AAMA and ANSI/AAMA 302.9 requirements for aluminum windows. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Fabricate panel system to dimension, size, and profile indicated on the Contract Drawings based on a design temperature of 70 F (21 C). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Fabricate panel system so that no restraints can be placed on the panel, which might result in compressive skin stresses. Detail installation such that the panels remain flat regardless of temperature change and at all times remain air and water tight. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | The finish side of the panel must have a removable plastic film applied prior to fabrication, which shall remain on the panel during fabrication, shipping, and erection to protect the surface from damage. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Alucobond Composite Panels: Two sheets of aluminum sandwiching a solid core of extruded thermoplastic material formed in a continuous process with no glues or adhesives between dissimilar materials. The core material must be free of voids and/or air spaces and not contain foamed insulation material. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Face Sheet Thickness: 0.0197 (0.50mm) inch nominal. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Alloy: Aluminum AA3000 Series. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Panel Thickness / Weight: 0.157 inches (4mm): 1.12 lbs./sq ft. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Panel Thickness / Weight: 0.236 inches (6mm): 1.59 lbs./sq ft. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Core: Standard. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Core: Fire Rated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Tolerances: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Panel Bow: Maximum 0.8 percent of any 1828mm (72 inch) panel dimension. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Panel Flatness: Maximum deviation less than 1/8 inch (3mm) in 5 feet (1524mm) on panel in any direction for assembled units. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Alcoa Reynobond Composite Panels: Aluminum composite material composed of a thermoplastic compound core sandwiched between two aluminum sheets formed into a continuous process. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Face Sheet Thickness: .020 inches (0.50mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Alloy: Aluminum - 3105 H25. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Panel Thickness / Weight: 0.157 inches (4mm): 1.12 lbs./sq ft. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Panel Thickness / Weight: 0.236 inches (6mm): 1.59 lbs./sq ft. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Core: Standard. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Core: Fire Rated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Bond integrity, per ASTM D 1781-76 and ASTM C 481 Cycle B, shall be a minimum of 40 in lb/ in. (Peel strength). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Tolerances: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Panel Bow: Maximum 0.8 percent of any 1828mm (72 inch) panel dimension. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Panel Flatness: Maximum deviation less than 1/8 inch (3mm) in 5 feet (1524mm) on panel in any direction for assembled units. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Mitsubishi Alpolic Composite Panels: Aluminum composite composed of a thermoplastic compound core sandwiched between two aluminum sheets formed into a continuous process. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Face Sheet Thickness: .020 inches (0.50mm). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Alloy: Aluminum - 3105 H14. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Panel Thickness / Weight: 0.157 inches (4mm): 1.12 lbs./sq ft. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Panel Thickness / Weight: 0.236 inches (6mm): 1.5 lbs./sq ft. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Core: Standard. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Core: Fire Rated. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Tolerances: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Panel Bow: Maximum 0.8 percent of any 1828mm (72 inch) panel dimension. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Panel Flatness: Maximum deviation less than 1/8 inch (3mm) in 5 feet (1524mm) on panel in any direction for assembled units. | |||||||||||||||||||||||||||||||||||||||||||||||||
| E. | Spacers: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Hat Chanel: 18 gauge galvanized steel fabrication. 7/8 inch (21mm) depth. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Z- Girts: 18 gauge galvanized steel fabrication. 7/8 inch (21mm) depth. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.5 | WALL SYSTEM FABRICATION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | System Type: Bamco C-500 Rout and Return Wet Seal. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | System utilizes an extruded horizontal and vertical tongue and groove extrusion system. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Reveal joint is a wet seal silicone type. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Perimeter extrusions reinforce and encapsulate panel returns, eliminating any exposed cut edges and exposed fasteners. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Building Wrap as specified in this section encapsulates building envelope prior to installation of wall panels. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | System Type: Bamco D-500 Rout and Return Dry (Rainscreen) Joint. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Extruded horizontal and vertical tongue and groove extrusion system. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Reveal joint is open dry joint rain screen principle. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Perimeter extrusions reinforce and encapsulate panel returns, eliminating any exposed cut edges and exposed fasteners. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Self Adhering membrane as specified in this section encapsulates building envelope prior to installation of wall panels. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | No field sealant is required in joints unless specifically noted on drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | System Type: Bamco G-500 Rout and Return Gasket. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | System utilizes an extruded horizontal and vertical guttering system with all panels having independent weep holes. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Reveal joint seal is a hard silicone gasket placed within the perimeter extrusions. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Perimeter extrusions reinforce and encapsulate panel returns, eliminating any exposed cut edges and exposed fasteners. Standard reveal color is black. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Building Wrap as specified in this section encapsulates building envelope prior to installation of wall panels. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | No field sealant required in joints unless specifically noted on drawings. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2.6 | FINISHES | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Finish Type: Alucobond PVDF Finish: Kynar 500 or Hylar 5000 based Polyvinylidene Fluoride (PVDF) meeting the requirements of AAMA 2605. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Coating Thickness: 1.0 mil (0.2 mil). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Coating Thickness: 0.50 mil ( 0.05 mil). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Coats: Two (2) Coat Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Coats: Three (3) Coat Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Coats: Mica Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Color: Standard color(s) as selected by the owner / architect / engineer from manufacturer's standard color palette. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Color: Custom color(s) to match samples contained in the Contract Documents. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Finish Type: Alcoa PVDF Finish: Fluoropolymer coating utilizing 70 percent Kynar 500 resins. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Coats: Two (2) Coat Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Coats: Three (3) Coat Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Color: Standard color(s) as selected by the owner / architect / engineer from manufacturer's standard color palette. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Color: Custom color(s) to match samples contained in the Contract Documents. | |||||||||||||||||||||||||||||||||||||||||||||||||
| C. | Finish Type: Alpolic FEVE Lumiflon Finish: Alkyl Vinyl Ether (FEVE) resin meeting the requirements of AAMA 2605. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Coats: Two (2) Coat Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Coats: Three (3) Coat Finish. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Color: Standard color(s) as selected by the owner / architect / engineer from manufacturer's standard color palette. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Color: Custom color(s) to match samples contained in the Contract Documents. | |||||||||||||||||||||||||||||||||||||||||||||||||
| D. | Finish Performance: | |||||||||||||||||||||||||||||||||||||||||||||||||
| 1. | Coating Thickness: 1.0 mil (+/- 0.2 mil). | |||||||||||||||||||||||||||||||||||||||||||||||||
| 2. | Hardness: ASTM D 3363; HB minimum using Eagle Turquoise Pencil. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3. | Impact: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Test method: ASTM D 2794; Gardner Variable Impact Tester with 5/8 inch (15mm) mandrel. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Coating shall withstand reverse impact of 1.5 inch pounds per mil substrate thickness. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Coating shall adhere tightly to metal when subjected to #600 Scotch Tape pick-off test. Slight minute cracking permissible. No removal of film to substrate. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 4. | Adhesion: Coating will not pick off when subjected to an 11 inch by 11 inch by 1/16 inch (28mm x 28mm x 1.5mm) grid and taped with #600 Scotch Tape in accordance with ASTM D 3359. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 5. | Humidity Resistance: No formation of blisters when subject to condensing water fog at 100 percent relative humidity and 100 F (37.8 C) for 4000 hours in accordance with ASTM D 2247. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 6. | Salt Spray Resistance: Expose coating system to 4000 hours, using 5 percent NaCl solution in accordance with ASTM B 117. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Corrosion creepage from scribe line: 1/16 inch (1.5mm) max. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Blister Rating: Minimum of 8 within the test specimen field. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 7. | Weather Exposure (Exterior): Ten-year exposure at 45 degree angle facing south Florida exposure. | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Color Change: Maximum of 5 Delta E units as calculated in accordance with ASTM D 2244. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Chalk Rating: 8, in accordance with ASTM D 4214. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Checking, Crazing, Adhesion loss: None. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 8. | Chemical Resistance: | |||||||||||||||||||||||||||||||||||||||||||||||||
| a. | Muriatic Acid: 10 percent solution for an exposure time of 15 minutes in accordance with ASTM D 1308 No loss of film adhesion or visual change when viewed by the unaided eye. | |||||||||||||||||||||||||||||||||||||||||||||||||
| b. | Sulfuric Acid: 20 percent solution for an exposure time of 18 hours in accordance with ASTM D 1308. No loss of film adhesion or visual change when viewed by the unaided eye. | |||||||||||||||||||||||||||||||||||||||||||||||||
| c. | Nitric Acid: 70 solution of reagent grade vapor for an exposure time of 30 minutes. Maximum color change of 5 Delta E units as calculated in accordance with ASTM D 2244. | |||||||||||||||||||||||||||||||||||||||||||||||||
| PART 3 | EXECUTION | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.1 | EXAMINATION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Do not begin installation until substrates have been properly prepared. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.2 | PREPARATION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Clean surfaces thoroughly prior to installation. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.3 | INSTALLATION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Install in accordance with manufacturer's instructions. | |||||||||||||||||||||||||||||||||||||||||||||||||
| 3.4 | PROTECTION | |||||||||||||||||||||||||||||||||||||||||||||||||
| A. | Protect installed products until completion of project. | |||||||||||||||||||||||||||||||||||||||||||||||||
| B. | Touch-up, repair or replace damaged products before Substantial Completion. | |||||||||||||||||||||||||||||||||||||||||||||||||