SECTION 08331
 
         
OVERHEAD COILING FIRE DOORS
 
         
          ** NOTE TO SPECIFIER ** Overhead Door Corp.; Overhead coiling fire door products.
.
This section is based on the products ofOverhead Door Corp., which is located at:
2501 S. State Hwy. 121 Suite 200
Lewisville, TX 75067
Toll Free Tel: 800-929-3667
Tel: 469-549-7100
Fax: 972-906-1499
Email: request info
Web: www.overheaddoor.com [ Click Here ] for additional information.


Overhead Door Corporation pioneered the upward-acting door industry, inventing the first upward-acting door in 1921 and the first electric door opener in 1926. Today, we continue to be the industry leader through the strength of our product innovation, superior craftsmanship and outstanding customer support, underscoring a legacy of quality, expertise and integrity. That's why design and construction professionals specify Overhead Door Corporation products more often than any other brand.

This specification includes ......... Overhead Door Corporation offers a wide array of rolling steel doors to meet the most demanding fire safety standards, unusual opening sizes and discerning aesthetic requirements. Designed to close automatically in the event of a fire or alarmed event, our fire-rated doors are available for service door and counter applications in commercial, industrial, institutional and retail uses.
 
          PART 1GENERAL
 
          1.1SECTION INCLUDES
          ** NOTE TO SPECIFIER ** Delete items below not required for project.
 
          A.Overhead coiling fire service doors
 
          B.Overhead coiling counter fire doors.
 
          C.Overhead coiling fire doors with integral frames.
 
          1.2RELATED SECTIONS
          ** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
          A.Section 05500 - Metal Fabrications: Support framing and framed opening.
 
          B.Section 06200 - Finish Carpentry: Wood jamb and head trim.
 
          C.Section 08710 - Door Hardware: Product Requirements for cylinder core and keys.
 
          D.Section 09900 - Painting: Field applied finish.
 
          E.Section 16130 - Raceway and Boxes: Conduit from electric circuit to door operator and from door operator to control station.
 
          F.Section 16150 - Wiring Connections: Power to disconnect.
 
          1.3REFERENCES
          ** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
 
          A.ASTM A 653 - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
 
          B.ASTM A 666 - Standard Specification for Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar.
 
          C.ASTM A 924 - Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process.
 
          D.ASTM B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.
 
          E.ASTM B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric).
 
          F.NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum).
 
          G.NEMA MG 1 - Motors and Generators.
 
          H.NFPA-80 - Standard for Fire Doors and Fire Windows.
 
          1.4DESIGN / PERFORMANCE REQUIREMENTS
 
          A.Fire Rated Assemblies: Provide assemblies complying with NFPA 80 and listed in UL Directory or Intertek Testing Services (Warnock Hersey Listed) Directory.
 
          B.Oversize Door Certification: Provide UL Certificate of Inspection or comparable certification acceptable to authorities having jurisdiction, in lieu of label for oversize door assemblies exceeding 120 square feet (11.15 square m) or 24 feet (7.31 m) (7.3 m) in any dimension.
 
          1.5SUBMITTALS
 
          A.Submit under provisions of Section 01300.
 
          B.[ Product Data ]: Manufacturer's data sheets on each product to be used, including:
          1.Preparation instructions and recommendations.
          2.Storage and handling requirements and recommendations.
          3.Details of construction and fabrication.
          4.Installation methods.
 
          C.Shop Drawings: Include detailed plans, elevations, details of framing members, anchoring methods, required clearances, hardware, and accessories. Include relationship with adjacent construction.
          ** NOTE TO SPECIFIER ** Delete selection samples if colors have already been selected.
 
          D.Selection Samples: For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns.
 
          E.Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square, representing actual product, color, and patterns.
 
          F.Manufacturer's Certificates: Certify products meet or exceed specified requirements.
 
          G.Operation and Maintenance Data: Submit lubrication requirements and frequency, and periodic adjustments required.
 
          1.6QUALITY ASSURANCE
 
          A.Manufacturer Qualifications: Company specializing in performing Work of this section with a minimum of five years experience in the fabrication and installation of security closures.
 
          B.Installer Qualifications: Installer Qualifications: Company specializing in performing Work of this section with minimum three years and approved by manufacturer.
          ** NOTE TO SPECIFIER ** Include a mock-up if the project size and/or quality warrant taking such a precaution. The following is one example of how a mock-up on a large project might be specified. When deciding on the extent of the mock-up, consider all the major different types of work on the project.
 
          C.Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.
          1.Finish areas designated by Architect.
          2.Do not proceed with remaining work until workmanship, color, and sheen are approved by Architect.
          3.Refinish mock-up area as required to produce acceptable work.
 
          1.7DELIVERY, STORAGE, AND HANDLING
 
          A.Store products in manufacturer's unopened packaging until ready for installation.
 
          B.Protect materials from exposure to moisture. Do not deliver until after wet work is complete and dry.
 
          C.Store materials in a dry, warm, ventilated weathertight location.
 
          1.8PROJECT CONDITIONS
 
          A.Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.
 
          1.9COORDINATION
 
          A.Coordinate Work with other operations and installation of adjacent materials to avoid damage to installed materials.
 
          PART 2PRODUCTS
 
          2.1MANUFACTURERS
 
          A.Acceptable Manufacturer: Overhead Door Corp., which is located at: 2501 S. State Hwy. 121 Suite 200 ; Lewisville, TX 75067; Toll Free Tel: 800-929-3667; Tel: 469-549-7100; Fax: 972-906-1499; Email: request info; Web: www.overheaddoor.com
          ** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
          B.Substitutions: Not permitted.
 
          C.Requests for substitutions will be considered in accordance with provisions of Section 01600.
          ** NOTE TO SPECIFIER ** 630, 631 and 634 Series fire service comply with NFPA 80 for masonry and non-masonry installation. Customized doors are available for conveyor installations. Contact Overhead Door for additional information.
 
          2.2OVERHEAD COILING FIRE SERVICE DOORS
 
          A.Overhead Coiling Fire service Doors: Overhead Door Corporation Series 630 Fire Doors.
          1.Label: Provide fire doors certified with the following listing.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for the door size(s) required and delete the ones not required.
          a.Rolling fire doors up to 144 sf (13.38 sm) and 12 feet (3.65 m) in width or height shall be labeled:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs to suit the projects requirements and delete the ones not required.
          1)UL and FM 3-Hour Class A Label for non-masonry fire walls.
          2)ULC 3-Hour Label for non-masonry fire walls.
          3)UL and FM 1-1/2 Hour Class B Label for non-masonry fire walls.
          b.Rolling fire doors over 144 sf (13.38 sm) shall receive the UL Oversize Fire Door Label.
          c.Rolling fire doors over 144 sf (13.38 sm) and not exceeding 18 feet (5.49 sm) in height or width shall receive the Factory Mutual Label for Oversize Fire Doors.
          2.Curtain: Interlocking roll-formed slats as specified following. Endlocks shall be attached to each end of alternate slats to prevent lateral movement.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for the door size and profile required and delete the ones not required.
          a.Curved profile type C-187 for doors thru 14 feet (4.27 m) wide by 12 feet (3.65 m) high, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)22 gauge galvanized steel.
          2)20 gauge galvanized steel.
          3)22 gauge stainless steel.
          b.Curved profile type C-187 for doors over 14 feet (4.27 m) thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          c.Curved profile type C-275 for doors thru 14 feet (4.27 m) wide by 12 feet (3.65 m) high, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)22 gauge galvanized steel.
          2)20 gauge galvanized steel.
          3)22 gauge stainless steel.
          d.Curved profile type C-275 for doors over 14 feet (4.27 m) thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          e.Curved profile type C-275 for doors over 20 feet (6.10 m) thru 24 feet (7.31 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          1)18 gauge galvanized steel.
          2)16 gauge galvanized steel.
          f.Flat profile type F-265 for doors thru 14 feet (4.27 m) wide by 12 feet (3.65 m) high, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)22 gauge galvanized steel.
          2)20 gauge galvanized steel.
          3)22 gauge stainless steel.
          g.Flat profile type F-265 for doors over 14 feet (4.27 m) thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          h.Flat profile type F-265 for doors over 20 feet (6.10 m) thru 24 feet (7.31 m) wide, fabricated of 18 gauge galvanized steel.
          ** NOTE TO SPECIFIER ** Select the following paragraph if glazing is required and delete if not required.
          3.Glazing: Fire-rated vision panels, four glazing panels 3 inch by 5/8 inch (76 by 16 mm).
          4.Finish:
          ** NOTE TO SPECIFIER ** Select the following paragraphs for the slat and hood materials required and delete the ones not required.
          a.Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A 653 and finished with a rust-inhibitive, roll coating process, including bonderizing, a 0.2 mils thick baked-on prime paint, and a 0.6 mils thick baked-on polyester (powder coated) top coat. Top coat color shall be:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)Gray polyester top coat.
          2)Tan polyester top coat.
          3)Powder coating finish in color as selected by Architect from manufacturer's standard colors.
          b.Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer.
          c.Stainless Steel: Slats shall be stainless steel finished as follows.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          1)Finish: 2B mill finish.
          2)Finish: No. 4 satin finish.
          ** NOTE TO SPECIFIER ** Select one of the following bottom bar paragraphs and delete the ones not required.
          5.Bottom Bar: Two structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          6.Bottom Bar: Two galvanized structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          7.Bottom Bar: Two stainless steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          8.Bottom Bar: Single structural steel angle 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum for conveyor applications.
          9.Bottom Bar: Single galvanized structural steel angle 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum for conveyor applications.
          10.Guides: Roll-formed steel shapes attached to continuous steel wall angle for doors through 12 feet (3.65 m) wide or high. Three structural steel angles with minimum thickness of 3/16 inch (5 mm) for doors over 12 feet (3.65 m) wide or high . Guides for between jamb doors shall be structural angles.
          ** NOTE TO SPECIFIER ** Select one of the following fastening paragraphs to meet projects installation requirements and delete the one not required.
          a.Fastening Guides to Masonry Fire Walls: UL listed expansion anchors, or by through-bolts on soft brick or hollow block walls, or by bolts on steel jambs, or welded in accordance with manufacturer's listing.
          b.Fastening Guides to Non-Masonry Fire Walls: Comply with the manufacturer's listing.
          11.Brackets:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Hot rolled prime painted steel to support counterbalance, curtain and hood.
          b.Galvanized steel to support counterbalance, curtain and hood.
          12.Counterbalance: Helical torsion spring type housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03 inch per foot of span. Counterbalance shall be adjustable by means of an adjusting tension wheel.
          13.Hood: Equip with thermally controlled, internal, galvanized steel flame baffle as required.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Fabricate of 24 gauge galvanized primed steel minimum for wall openings thru 19 feet (5.79 m) wide.
          b.Fabricate of 22 gauge galvanized primed steel for wall openings over 19 feet (5.79 m) wide.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          c.Provide one intermediate support bracket for wall openings over 13 feet 6 inch (4.15 m) wide
          d.Provide two support brackets for wall openings over 19 feet (5.79 m) wide.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required.
          14.Manual Operation:
          ** NOTE TO SPECIFIER ** Select one of the following manual operation paragraphs and delete the ones not required.
          a.Manual push.
          b.Chain hoist.
          c.Crank operation.
          ** NOTE TO SPECIFIER ** Include the following paragraph if electric motor operation is required and delete if not required.
          15.Electric Motor Operation: Provide UL listed electric operator, size as recommended by manufacturer to move door in either direction.
          a.Sensing Edge Protection:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          1)Pneumatic sensing edge.
          2)Electric sensing edge.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operation with open, close, and stop controls.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following location paragraphs and delete the one not required.
          4)Controls for interior location.
          5)Controls for exterior location.
          6)Controls for both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          7)Controls surface mounted.
          8)Controls flush mounted.
          c.Special Operation:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Vehicle detector operation.
          2)Radio control operation.
          3)Card reader control.
          4)Photocell operation.
          5)Door timer operation.
          6)Commercial light package.
          7)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required. Note that Fire Minuteman is used in conjunction with Fire Sentinel to allow reset of an alarmed door from the floor.
          16.Automatic Closure:
          a.Standard Fire Door: UL approved release mechanism equipped with a 165 degree fusible link.
          b.Fire Sentinel time-relay release mechanism provides an added measure of safety to control the doors' closure.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for Fire Sentinel operation and delete the ones not required.
          1)Model A: 10 second delay on alarm signal and a 10 second delay on power loss.
          2)Model B: 10 second delay on alarm signal and a 10 second delay on power loss.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          b)Provide with optional sounder/strobe alarms that operate during closing cycle.
          3)Model B2: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          4)Model C: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provide with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then mechanically releases.
          5)Model C+: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provided with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then stops door on obstruction.
          c.Fire Minuteman Chain Reset Hoist, designed to eliminate the need to release a fire door's spring tension on fire drop mode and allows one person to reset the door from the floor.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph for use in conjunction with Model C if required. Delete if not required.
          d.Central Fire Alarm: Electric Release Mechanism operated from fire alarm system.
          17.Locking:
          ** NOTE TO SPECIFIER ** Select one of the following optional paragraphs and delete the ones not required.
          a.Interior bottom bar slide bolt for manually operated doors.
          b.Interior slide bolt lock for electric operation with interlock switch.
          c.Cylinder lock for electric operation with interlock switch.
          18.Wall Mounting Condition:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Face-of-wall mounting.
          b.Between jambs mounting.
 
          B.Overhead Coiling Fire service Doors: Overhead Door Corporation Series 631 Fire Doors.
          1.Label: Provide fire doors certified with the following listing.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for the door size(s) required and delete the ones not required.
          a.Rolling fire doors up to 144 sf (13.38 sm) and 12 feet (3.65 m) in width or height shall be labeled:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs to suit the projects requirements and delete the ones not required.
          1)UL 3-Hour Class A Label for non-masonry fire walls.
          2)UL 1-1/2 Hour Class B Label for non-masonry fire walls.
          b.Rolling fire doors over 144 sf (13.38 sm) shall receive the UL Oversize Fire Door Label. Maximum authorized wall opening 14 feet (4.27 m) wide by 12 feet (3.65 m) high.
          2.Curtain: Interlocking roll-formed slats as specified following. Endlocks shall be attached to each end of alternate slats to prevent lateral movement.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for the door size and profile required and delete the ones not required.
          a.Curved profile type C-187 for doors thru 14 feet (4.27 m) wide by 12 feet (3.65 m) high, fabricated of 24 gauge galvanized steel.
          b.Flat profile type F-265 for doors thru 14 feet (4.27 m) wide by 12 feet (3.65 m) high, fabricated of 24 gauge galvanized steel.
          ** NOTE TO SPECIFIER ** Select the following paragraph if glazing is required and delete if not required.
          3.Glazing: Fire-rated vision panels, four glazing panels 3 inch by 5/8 inch (76 by 16 mm).
          4.Finish:
          ** NOTE TO SPECIFIER ** Select the following paragraphs for the slat and hood materials required and delete the ones not required.
          a.Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A 653 and finished with a rust-inhibitive, roll coating process, including bonderizing, a 0.2 mils thick baked-on prime paint, and a 0.6 mils thick baked-on polyester (powder coated) top coat. Top coat color shall be:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)Gray polyester top coat.
          2)Tan polyester top coat.
          3)Powder coating finish in color as selected by Architect from manufacturer's standard colors.
          b.Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer.
          c.Stainless Steel: Slats shall be stainless steel finished as follows.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          1)Finish: 2B mill finish.
          2)Finish: No. 4 satin finish.
          ** NOTE TO SPECIFIER ** Select one of the following bottom bar paragraphs and delete the ones not required.
          5.Bottom Bar: Two structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          6.Bottom Bar: Two galvanized structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          7.Bottom Bar: Single structural steel angle 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum for conveyor applications.
          8.Bottom Bar: Single galvanized structural steel angle 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum for conveyor applications.
          9.Guides: Roll-formed steel shapes attached to continuous steel wall angle for doors through 12 feet (3.65 m) wide. Three structural steel angles with minimum thickness of 3/16 inch (5 mm) for doors over 12 feet (3.65 m) wide. Guides for between jamb doors shall be structural angles.
          ** NOTE TO SPECIFIER ** Select one of the following fastening paragraphs to meet projects installation requirements and delete the one not required.
          a.Fastening Guides to Masonry Fire Walls: UL listed expansion anchors, or by through-bolts on soft brick or hollow block walls, or by bolts on steel jambs, or welded in accordance with manufacturer's listing.
          b.Fastening Guides to Non-Masonry Fire Walls: Comply with the manufacturer's listing.
          10.Brackets:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Hot rolled prime painted steel to support counterbalance, curtain and hood.
          b.Galvanized steel to support counterbalance, curtain and hood.
          11.Counterbalance: Helical torsion spring type housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03 inch per foot of span. Counterbalance shall be adjustable by means of an adjusting tension wheel.
          12.Hood: 24 gauge galvanized primed steel. Provide one intermediate support bracket for wall openings over 13 feet 6 inch (4.15 m) wide.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required.
          13.Manual Operation:
          ** NOTE TO SPECIFIER ** Select one of the following manual operation paragraphs and delete the ones not required.
          a.Manual push.
          b.Chain hoist.
          c.Crank operation.
          ** NOTE TO SPECIFIER ** Include the following paragraph if electric motor operation is required and delete if not required.
          14.Electric Motor Operation: Provide UL listed electric operator, size as recommended by manufacturer to move door in either direction.
          a.Sensing Edge Protection:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          1)Pneumatic sensing edge.
          2)Electric sensing edge.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operation with open, close, and stop controls.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following location paragraphs and delete the one not required.
          4)Controls for interior location.
          5)Controls for exterior location.
          6)Controls for both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          7)Controls surface mounted.
          8)Controls flush mounted.
          c.Special Operation:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Vehicle detector operation.
          2)Radio control operation.
          3)Card reader control.
          4)Photocell operation.
          5)Door timer operation.
          6)Commercial light package.
          7)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required. Note that Fire Minuteman is used in conjunction with Fire Sentinel to allow reset of an alarmed door from the floor
          15.Automatic Closure:
          a.Standard Fire Door: UL approved release mechanism equipped with a 165 degree fusible link.
          b.Fire Sentinel time-relay release mechanism provides an added measure of safety to control the doors' closure.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for Fire Sentinel operation and delete the ones not required.
          1)Model A: 10 second delay on alarm signal and a 10 second delay on power loss.
          2)Model B: 10 second delay on alarm signal and a 10 second delay on power loss.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          b)Provide with optional sounder/strobe alarms that operate during closing cycle.
          3)Model B2: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss with alarm signal.
          4)Model C: 10 second delay on alarm signal and a 10 second delay on power loss.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provide with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then mechanically release.
          5)Model C+: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provided with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then stops door on obstruction.
          c.Fire Minuteman Chain Reset Hoist, designed to eliminate the need to release a fire door's spring tension on fire drop mode and allows one person to reset the door from the floor.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph for use in conjunction with Model C if required. Delete if not required.
          d.Central Fire Alarm: Electric Release Mechanism operated from fire alarm system.
          16.Locking:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          a.Interior bottom bar slide bolt for manually operated doors.
          b.Interior slide bolt lock for electric operation with interlock switch.
          c.Cylinder lock for electric operation with interlock switch.
          17.Wall Mounting Condition:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Face-of-wall mounting.
          b.Between jambs mounting.
 
          C.Overhead Coiling Fire service Doors: Overhead Door Corporation Series 634 Fire Doors.
          1.Label: Provide fire doors certified with the following listing.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for the door size(s) required and delete the ones not required.
          a.Rolling fire doors up to 144 sf (13.38 sm) and 12 feet (3.65 m) in width or height shall be labeled with a UL 4-Hour Label.
          b.Rolling fire doors over 144 sf (13.38 sm) or over 12 feet (3.65 m) shall receive the UL Oversize Fire Door Label.
          2.Curtain: Interlocking roll-formed slats as specified following. Endlocks shall be attached to each end of alternate slats to prevent lateral movement.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for the door size and profile required and delete the ones not required.
          a.Curved profile type C-187 for doors thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          b.Curved profile type C-275 for doors thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          c.Curved profile type C-275 for doors thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          d.Flat profile type F-265 for doors over 14 feet (4.27 m) thru 20 feet (6.10 m) wide, fabricated of:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)20 gauge galvanized steel.
          2)18 gauge galvanized steel.
          3)20 gauge stainless steel.
          e.Flat profile type F-265 for doors over 20 feet (6.10 m) thru 24 feet (7.31 m) wide, fabricated of 18 gauge galvanized steel.
          ** NOTE TO SPECIFIER ** Select the following paragraph if glazing is required and delete if not required.
          3.Glazing: Fire-rated vision panels, four glazing panels 3 inch by 5/8 inch (76 by 16 mm).
          4.Finish:
          ** NOTE TO SPECIFIER ** Select the following paragraphs for the slat and hood materials required and delete the ones not required.
          a.Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A 653 and finished with a rust-inhibitive, roll coating process, including bonderizing, a 0.2 mils thick baked-on prime paint, and a 0.6 mils thick baked-on polyester (powder coated) top coat. Top coat color shall be:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)Gray polyester top coat.
          2)Tan polyester top coat.
          3)Powder coating finish in color as selected by Architect from manufacturer's standard colors.
          b.Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer.
          c.Stainless Steel: Slats shall be stainless steel finished as follows.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          1)Finish: 2B mill finish.
          2)Finish: No. 4 satin finish.
          ** NOTE TO SPECIFIER ** Select one of the following bottom bar paragraphs and delete the ones not required.
          5.Bottom Bar: Two structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          6.Bottom Bar: Two galvanized structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          7.Bottom Bar: Two stainless steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.
          8.Bottom Bar: Tubular locking bottom bar.
          9.Bottom Bar: Single structural steel angle 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum for conveyor applications.
          10.Bottom Bar: Single galvanized structural steel angle 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum for conveyor applications.
          11.Guides: Three structural steel angles with minimum thickness of 3/16 inch (5 mm) mounted to the face of the jamb. Fastened to Masonry Fire Walls with UL listed expansion anchors, or welded to steel jambs in accordance with fire door manufacturer's instructions, or by bolts on steel jambs, or by thru-bolts on hollow masonry or soft brick wall.
          12.Brackets:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Hot rolled prime painted steel to support counterbalance, curtain and hood.
          b.Galvanized steel to support counterbalance, curtain and hood.
          13.Counterbalance: Helical torsion spring type housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03 inch per foot of span. Counterbalance shall be adjustable by means of an adjusting tension wheel.
          14.Hood: Equip with thermally controlled, internal, galvanized steel flame baffle as required.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          a.Fabricate of 24 gauge galvanized primed steel minimum for wall openings thru 19 feet (5.79 m) wide.
          b.Fabricate of 22 gauge galvanized primed steel for wall openings over 19 feet (5.79 m) wide.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          c.Provide one intermediate support bracket for wall openings over 13 feet 6 inch (4.15 m) wide
          d.Provide two support brackets for wall openings over 19 feet (5.79 m) wide.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required.
          15.Manual Operation:
          ** NOTE TO SPECIFIER ** Select one of the following manual operation paragraphs and delete the ones not required.
          a.Manual push.
          b.Chain hoist.
          c.Crank operation.
          ** NOTE TO SPECIFIER ** Include the following paragraph if electric motor operation is required and delete if not required.
          16.Electric Motor Operation: Provide UL listed electric operator, size as recommended by manufacturer to move door in either direction.
          a.Sensing Edge Protection:
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          1)Pneumatic sensing edge.
          2)Electric sensing edge.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operation with open, close, and stop controls.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following location paragraphs and delete the one not required.
          4)Controls for interior location.
          5)Controls for exterior location.
          6)Controls for both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          7)Controls surface mounted.
          8)Controls flush mounted.
          c.Special Operation:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Vehicle detector operation.
          2)Radio control operation.
          3)Card reader control.
          4)Photocell operation.
          5)Door timer operation.
          6)Commercial light package.
          7)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required. Note that Fire Minuteman is used in conjunction with Fire Sentinel to allow reset of an alarmed door from the floor
          17.Automatic Closure:
          a.Standard Fire Door: UL approved release mechanism equipped with a 165 degree fusible link.
          b.Fire Sentinel time-relay release mechanism provides an added measure of safety to control the doors' closure.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for Fire Sentinel operation and delete the ones not required.
          1)Model A: 10 second delay on alarm signal and a 10 second delay on power loss.
          2)Model B: 10 second delay on alarm signal and a 10 second delay on power loss.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          b)Provide with optional sounder/strobe alarms that operate during closing cycle.
          3)Model B2: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          4)Model C: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provide with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then mechanically release.
          5)Model C+: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provided with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then stops door on obstruction.
          c.Fire Minuteman Chain Reset Hoist, designed to eliminate the need to release a fire door's spring tension on fire drop mode and allows one person to reset the door from the floor.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph for use in conjunction with Model C if required. Delete if not required.
          d.Central Fire Alarm: Electric Release Mechanism operated from fire alarm system.
          18.Locking:
          ** NOTE TO SPECIFIER ** Select one of the following optional paragraphs and delete the ones not required.
          a.Interior bottom bar slide bolt for manually operated doors.
          b.Interior slide bolt lock for electric operation with interlock switch.
          c.Cylinder lock for electric operation with interlock switch.
          19.Wall Mounting Condition: Face-of-wall mounting.
 
          2.3OVERHEAD COILING COUNTER FIRE DOORS
 
          A.Overhead Coiling Counter Fire Doors: Overhead Door Corporation Series 640 Counter Fire Doors.
          1.Label: Provide rolling fire doors certified with the following listing.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs to suit the projects requirements and delete the ones not required.
          a.UL and FM 3-Hour Class A Label for masonry fire walls.
          b.UL and FM 1-1/2 Hour Class B Label for non-masonry fire walls.
          2.Curtain: Interlocking slats, Type F-128 fabricated of 22 gauge galvanized steel. Endlocks shall be attached to ends of alternate slats to maintain curtain alignment and prevent lateral slat movement.
          ** NOTE TO SPECIFIER ** Select the following paragraph if glazing is required and delete if not required.
          3.Glazing: Fire-rated vision panels, four glazing panels 3 inch by 5/8 inch (76 by 16 mm).
          4.Finish:
          ** NOTE TO SPECIFIER ** Select the following paragraphs for the slat and hood materials required and delete the ones not required.
          a.Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A 653 and finished with a rust-inhibitive, roll coating process, including bonderizing, a 0.2 mils thick baked-on prime paint, and a 0.6 mils thick baked-on polyester (powder coated) top coat. Top coat color shall be:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          1)Gray polyester top coat.
          2)Tan polyester top coat.
          3)Powder coating finish in color as selected by Architect from manufacturer's standard colors.
          b.Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer.
          5.Bottom Bar:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.
          a.Single primed steel angle bottom bar.
          b.Single primed steel angle bottom bar with 1/4 inch (6 mm) foam astragal.
          c.Tubular locking bottom bar.
          6.Guides:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          a.Roll-formed painted steel shapes.
          b.Roll-formed painted steel shapes with brush smoke seals.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          c.Fastening Guides to Masonry Fire Walls: UL listed expansion anchors, or by through-bolts on soft brick or hollow block walls, or by bolts on steel jambs.
          d.Fastening Guides to Non-Masonry Fire Walls: Comply with the manufacturer's listing.
          7.Brackets: Painted steel to support counterbalance, curtain and hood.
          8.Counterbalance: Helical torsion spring type. Counterbalance shall be housed in a steel tube or pipe barrel.
          9.Hood: Galvanized painted steel. Hood shall be equipped with thermally controlled, internal flame baffle. Hood support provided for wall openings over 13 feet 6 inch (4.15 m) wide.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required and delete if not required.
          a.Provide with exterior brush smoke seal.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required.
          10.Manual Operation:
          ** NOTE TO SPECIFIER ** Select one of the following manual operation paragraphs and delete the ones not required.
          a.Manual push.
          b.Crank operation.
          ** NOTE TO SPECIFIER ** Include the following paragraph if electric motor operation is required and delete if not required.
          11.Electric Motor Operation: Provide UL listed electric operator, size as recommended by manufacturer to move door in either direction.
          ** NOTE TO SPECIFIER ** Select following paragraphs if required and delete if not required.
          a.Sensing Edge Protection: Electric sensing edge.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operation with open, close, and stop controls.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following location paragraphs and delete the one not required.
          4)Controls for interior location.
          5)Controls for exterior location.
          6)Controls for both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.
          7)Controls surface mounted.
          8)Controls flush mounted.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required. Note that Fire Minuteman is used in conjunction with Fire Sentinel to allow reset of an alarmed door from the floor
          12.Automatic Closure:
          a.Standard Fire Door: UL approved release mechanism equipped with a 165 degree fusible link.
          b.Fire Sentinel time-relay release mechanism provides an added measure of safety to control the doors' closure.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs for Fire Sentinel operation and delete the ones not required.
          1)Model A: 10 second delay on alarm signal and a 10 second delay on power loss.
          2)Model B: 10 second delay on alarm signal and a 10 second delay on power loss.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          b)Provide with optional sounder/strobe alarms that operate during closing cycle.
          3)Model B2: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          4)Model C: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signal.
          a)Includes intelligent operation that will not release when fire door is closed and operator voltage is available.
          b)Includes battery back-up.
          c)Can provide 12V DC power to 4 smoke detectors during power loss.
          d)Provide with sounder/strobe alarms that operate during closing cycle.
          ** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.
          e)Provide with multilingual voice annunciator that operates during closing cycle.
          f)Provide with bottom bar sensing edge that will repeat and attempt the close attempt three times then mechanically release.
          5)Model C+: 10 second delay on alarm signal and a 10 second delay on power loss with alarm signa