MasterFormat: 95
SpecWizard: customize this spec    Download this Sectional Overhead Doors Specification for   WORD | WP | RTF | TEXT
Find over 500 more construction specifications | Arcat.com
         
Overhead Door Corporation Sectional Overhead Doors
 
         
SECTION 08360
 
         
SECTIONAL OVERHEAD DOORS
 
         
Copyright 2007 - 2013 ARCAT, Inc. - All rights reserved

          ** NOTE TO SPECIFIER ** Overhead Door Corporation; Commercial Sectional Overhead Door products.
.
This section is based on the products of Overhead Door Corporation, which is located at:
2501 S. State Highway 121 Bus. Suite 200
Lewisville, TX 75067
Toll Free Tel: 800-929-3667
Tel: 469-549-7100
Fax: 972-906-1499
Email: request info
Web: www.overheaddoor.com
[ Click Here ] for additional information.


Overhead Door Corporation pioneered the upward-acting door industry, inventing the first upward-acting door in 1921 and the first electric door opener in 1926. Today, we continue to be the industry leader through the strength of our product innovation, superior craftsmanship and outstanding customer support, underscoring a legacy of quality, expertise and integrity. That's why design and construction professionals specify Overhead Door Corporation products more often than any other brand.

This specification includes Overhead Door Corp. Commercial Sectional Overhead Door products including Insulated Sectional Overhead Doors, Steel Sectional Overhead Doors, Glazed Aluminum Sectional Overhead Doors, and Knockout Sectional Overhead Doors. Contact Overhead Door for support in selecting doors to meet your criteria.
 
          PART 1GENERAL
 
          1.1SECTION INCLUDES
          ** NOTE TO SPECIFIER ** Delete items below not required for project.
 
          A.Insulated Sectional Overhead Doors.
 
          B.Steel Sectional Overhead Doors.
 
          C.Glazed Aluminum Sectional Overhead Doors.
 
          D.Electric Operators and Controls.
 
          E.Operating Hardware, tracks, and support.
 
          1.2RELATED SECTIONS
          ** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
          A.Section 03300 - Cast-In-Place Concrete: Prepared opening in concrete. Execution requirements for placement of anchors in concrete wall construction.
 
          B.Section 04810 - Unit Masonry Assemblies: Prepared opening in masonry. Execution requirements for placement of anchors in masonry wall construction.
 
          C.Section 05500 - Metal Fabrications: Steel frame and supports.
 
          D.Section 06114 - Wood Blocking and Curbing: Rough wood framing and blocking for door opening.
 
          E.Section 07900 - Joint Sealers: Perimeter sealant and backup materials.
 
          F.Section 08710 - Door Hardware: Cylinder locks.
 
          G.Section 09900 - Paints and Coatings: Field painting.
 
          H.Section 11150 - Parking Control Equipment: Remote door control.
 
          I.Section 16130 - Raceway and Boxes: Empty conduit from control station to door operator.
 
          J.Section 16150 - Wiring Connections: Electrical service to door operator.
 
          1.3REFERENCES
          ** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
 
          A.ANSI/DASMA 102 - American National Standard Specifications for Sectional Overhead Type Doors.
 
          1.4DESIGN / PERFORMANCE REQUIREMENTS
          ** NOTE TO SPECIFIER ** Use the applicable building code to determine the actual loading required and edit the following paragraph accordingly. Coordinate with the manufacturer for the selection of doors to meet the required criteria.
 
          A.Wind Loads: Design and size components to withstand loads caused by pressure and suction of wind acting normal to plane of wall as calculated in accordance with applicable code.
          1.Design pressure of ________ lb/sq ft (________kPa).
          ** NOTE TO SPECIFIER ** Edit the following paragraph for power operators as required. Delete if not required.
 
          B.Wiring Connections: Requirements for electrical characteristics.
          1.115 volts, single phase, 60 Hz.
          2.230 volts, single phase, 60 Hz.
          3.230 volts, three phase, 60 Hz.
          4.460 volts, three phase, 60 Hz.
 
          C.Single-Source Responsibility: Provide doors, tracks, motors, and accessories from one manufacturer for each type of door. Provide secondary components from source acceptable to manufacturer of primary components.
 
          1.5SUBMITTALS
 
          A.Submit under provisions of Section 01300.
 
          B.Product Data: Manufacturer's data sheets on each product to be used, including:
          1.Preparation instructions and recommendations.
          2.Storage and handling requirements and recommendations.
          3.Installation methods.
 
          C.Shop Drawings: Indicate plans and elevations including opening dimensions and required tolerances, connection details, anchorage spacing, hardware locations, and installation details.
 
          D.Manufacturer's Certificates: Certify products meet or exceed specified requirements.
 
          E.Operation and Maintenance Data.
 
          1.6QUALITY ASSURANCE
 
          A.Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with minimum five years documented experience.
 
          B.Installer Qualifications: Authorized representative of the manufacturer with minimum five years documented experience.
 
          C.Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories, Inc. acceptable to authority having jurisdiction as suitable for purpose specified.
 
          1.7DELIVERY, STORAGE, AND HANDLING
 
          A.Store products in manufacturer's unopened labeled packaging until ready for installation.
 
          B.Protect materials from exposure to moisture until ready for installation.
 
          C.Store materials in a dry, ventilated weathertight location.
 
          1.8PROJECT CONDITIONS
 
          A.Pre-Installation Conference: Convene a pre-installation conference just prior to commencement of field operations, to establish procedures to maintain optimum working conditions and to coordinate this work with related and adjacent work.
 
          1.9WARRANTY
          ** NOTE TO SPECIFIER ** Warranty paragraph for Series 418, 422, 426, 432, 416, 429, 424, 430, 511 and 521 commercial sectional doors is 1 Year and covered under General Conditions of Contract.
          ** NOTE TO SPECIFIER ** Include the following warranty paragraph for Thermacore® Series 591, 592, 593, 594, 596, or 599 commercial sectional doors and model RSX®, RMX®, or RHX® commercial door operators provided together as a System.. Delete if not applicable.
 
          A.Warranty: Manufacturer’s limited door and operators System warranty for 10 year against delamination of polyurethane foam from steel face and all other components for 3 years or 20,000 cycles, whichever comes first.
          ** NOTE TO SPECIFIER ** Include the following warranty paragraph for Thermacore® Series 598 commercial sectional doors and model RSX®, RMX®, or RHX® commercial door operators provided together as a System.. Delete if not applicable.
 
          B.Warranty: Manufacturer’s limited door and operators System warranty for 8 year against delamination of polyurethane foam from steel face and all other components for 3 years or 20,000 cycles, whichever comes first.
 
          PART 2PRODUCTS
 
          2.1MANUFACTURERS
 
          A.Acceptable Manufacturer: Overhead Door Corporation, which is located at: 2501 S. State Highway 121 Bus. Suite 200 ; Lewisville, TX 75067; Toll Free Tel: 800-929-3667; Tel: 469-549-7100; Fax: 972-906-1499; Email: request info; Web: www.overheaddoor.com
          ** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
          B.Substitutions: Not permitted.
 
          C.Requests for substitutions will be considered in accordance with provisions of Section 01600.
 
          2.2INSULATED SECTIONAL OVERHEAD DOORS
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 592 Series Thermacore® Insulated Steel Doors are available up to a maximum width of 40 feet 2 inches and a maximum height of 32 feet 1 inch. Edit as required to suit project requirements.
 
          A.Insulated Steel Sectional Overhead Doors: 592 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with PVC thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed, textured.
          c.Exterior Steel: .015 inch (.38 mm), hot-dipped galvanized.
          d.End Stiles: 16 gauge with thermal break.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 17.50; U-value of 0.057.
          h.Air Infiltration: 0.08 cfm at 15 mph; 0.08 cfm at 25 mph.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional. Note that Pass-Doors and Knockout Lower Door Sections are not available together. Select one of the following two paragraphs and delete the one not required.
          i.Pass-Door:
          1)Provide with optional pass door.
          j.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          k.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          l.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          m.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color:
          ** NOTE TO SPECIFIER ** Select one of the following exterior finish and color paragraphs and delete the ones not required. Note that the Kynar finish is only available on Series 591, 592, 593 and 594 doors.
          a.Two coat baked-on polyester:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, tan.
          5)Exterior color, gray.
          b.Baked-on Kynar polyvinylidene floruoride high performance coating:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, beige.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information regarding the options available. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
 
          B.Insulated Steel Sectional Overhead Doors: 599 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with PVC thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Flush, textured.
          c.Exterior Steel: .015 inch (.38 mm), hot-dipped galvanized.
          d.End Stiles: 16 gauge with thermal break.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 17.50; U-value of 0.057.
          h.Air Infiltration: 0.08 cfm at 15 mph; 0.08 cfm at 25 mph.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional. Note that Pass-Doors and Knockout Lower Door Sections are not available together. Select one of the following two paragraphs and delete the one not required.
          i.Pass-Door:
          1)Provide with optional pass door.
          j.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          k.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          l.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating Glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating Glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          m.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating Glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color: Two coat baked-on polyester.
          a.Interior color, white.
          b.Exterior color, white.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 591 Series Thermacore® Insulated Steel Doors are available up to a maximum width of 35 feet 2 inches and a maximum height of 24 feet 1 inch. Edit as required to suit project requirements.
 
          C.Insulated Steel Sectional Overhead Doors: 591 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with PVC thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 1-5/8 inches (41 mm).
          b.Exterior Surface: Ribbed, textured.
          c.Exterior Steel: .015 inch (.38 mm), hot-dipped galvanized.
          d.End Stiles: 16 gauge.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 14.86; U-value of 0.067.
          h.Air Infiltration: 0.08 cfm at 15 mph; 0.08 cfm at 25 mph.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional. Note that Pass-Doors and Knockout Lower Door Sections are not available together. Select one of the following two paragraphs and delete the one not required.
          i.Pass-Door:
          1)Provide with optional pass door.
          j.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          k.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          l.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          m.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating Glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color:
          ** NOTE TO SPECIFIER ** Select one of the following exterior finish and color paragraphs and delete the ones not required.
          a.Two coat baked-on polyester:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, tan.
          5)Exterior color, gray.
          b.Baked-on Kynar polyvinylidene floruoride high performance coating:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, beige.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 596 Series Thermacore® Insulated Steel Doors are available up to a maximum width of 36 feet 2 inches and a maximum height of 24 feet 1 inch. Edit as required to suit project requirements.
 
          D.Insulated Steel Sectional Overhead Doors: 596 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with PVC thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Flush, textured.
          c.Exterior Steel: 20 gauge, galvanized.
          d.End Stiles: 16 gauge with thermal break.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 17.40; U-value of 0.057.
          h.Air Infiltration: 0.08 cfm at 15 mph; 0.08 cfm at 25 mph.
          i.Sound Transmission: Class 26.
          ** NOTE TO SPECIFIER ** The following two paragraphs are optional. Note that Pass-Doors and Knockout Lower Door Sections are not available together. Select one of the following two paragraphs and delete the one not required.
          j.Pass-Door:
          1)Provide with optional pass door.
          k.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          l.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          m.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating Glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating Glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          n.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color:
          a.Two coat baked-on polyester:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, tan.
          5)Exterior color, gray.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a. Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 594 Series Thermacore® Insulated Steel Doors are available up to a maximum width of 20 feet 2 inches and a maximum height of 16 feet 1 inch. Edit as required to suit project requirements.
 
          E.Insulated Steel Sectional Overhead Doors: 594 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with hot melt thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 1-3/8 inches (35 mm).
          b.Exterior Surface: Raised panel, textured woodgrain surface.
          c.Exterior Steel: .012 inch (.30 mm), hot-dip galvanized.
          d.End Stiles: 20 gauge.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 12.76; U-value of 0.078.
          h.Air Infiltration: 0.08 cfm at 15 mph; 0.15 cfm at 25 mph.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          i.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          j.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating Glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating Glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color:
          ** NOTE TO SPECIFIER ** Select one of the following exterior finish and color paragraphs and delete the ones not required. Note that the Kynar finish is only available on Series 591, 592, 593 and 594 doors.
          a.Two coat baked-on polyester:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, Desert Tan.
          5)Exterior color, Sandstone.
          6)Exterior color, Almond.
          7)Exterior color, Hunter Green.
          8)Exterior color, Terra Bronze.
          b.Baked-on Kynar polyvinylidene floruoride high performance coating:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, beige.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 593 Series Thermacore® Insulated Steel Doors are available up to a maximum width of 20 feet 2 inches and a maximum height of 16 feet 1 inch. Edit as required to suit project requirements.
 
          F.Insulated Steel Sectional Overhead Doors: 593 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with hot melt thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 1-3/8 inches (35 mm).
          b.Exterior Surface: Ribbed, textured.
          c.Exterior Steel: .015 inch (.38 mm), hot-dip galvanized.
          d.End Stiles: 20 gauge.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 12.76; U-value of 0.078.
          h.Air Infiltration: 0.08 cfm at 15 mph; 0.15 cfm at 25 mph.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          i.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          j.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color:
          ** NOTE TO SPECIFIER ** Select one of the following exterior finish and color paragraphs and delete the ones not required. Note that the Kynar finish is only available on Series 591, 592, 593 and 594 doors.
          a.Two coat baked-on polyester:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, tan.
          5)Exterior color, gray.
          b.Baked-on Kynar polyvinylidene floruoride high performance coating:
          1)Interior color, white.
          ** NOTE TO SPECIFIER ** Select one of the following exterior color paragraphs and delete the ones not required.
          2)Exterior color, white.
          3)Exterior color, brown.
          4)Exterior color, beige.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 598 Series Thermacore® Insulated Steel Doors are available up to a maximum width of 16 feet 2 inches and a maximum height of 14 feet 1 inch. Edit as required to suit project requirements.
 
          G.Insulated Steel Sectional Overhead Doors: 598 Series Thermacore Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Metal/foam/metal sandwich panel construction, with hot melt thermal break and weather-tight ship-lap design meeting joints.
          a.Panel Thickness: 1 inch (25.4 mm).
          b.Exterior Surface: Ribbed, textured.
          c.Exterior Steel: .012 inch (.30 mm), hot-dip galvanized.
          d.End Stiles: 20 gauge.
          e.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          f.Insulation: CFC-free and HCFC-free polyurethane, fully encapsulated.
          g.Thermal Values: R-value of 9.31; U-value of 0.107.
          h.Air Infiltration: 0.24 cfm at 15 mph; 0.46 cfm at 25 mph.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph if required and delete if not required.
          i.High-Usage Package: Provide with optional high-usage package.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required. Partial glazing with two or more sections glazed with 1/4 inch glass or 1/2 inch insulated glass require engineering review by the manufacturer. Full view sash sections are available in widths up to 24 feet 2 inches with 1/8, 1/4 or 1/2 inch insulated glass, up to 30 feet 2 inches with 1/8 inch double strength glass or 1/4 inch acrylic or Lean glazing only. Contact the manufacturer if additional requirements are required.
          j.Partial Glazing of Steel Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          2.Finish and Color: Two coat baked-on polyester with white exterior and white interior color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.EPDM bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 418 Series Insulated Steel Doors are available up to a maximum width of 32 feet 2 inches and a maximum height of 21 feet 1 inch. Edit as required to suit project requirements.
 
          H.Insulated Steel Sectional Overhead Doors: 418 Series Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Insulated steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Flush.
          c.Exterior Steel: 16 gauge, hot-dip galvanized.
          d.Back Cover:
          ** NOTE TO SPECIFIER ** Select one of the following backcover paragraphs and delete those not required.
          1)26 gauge steel.
          2)Poly-Backed.
          3)High Impact Polystyrene Backcover.
          e.Center and End Stiles: 16 gauge steel.
          f.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          g.Insulation: Polystyrene.
          h.Thermal Values:
          1)Polystyrene - R-value of 7.35; U-Value of 0.136.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          i.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          j.Partial Glazing of Steel Panels:
          1)Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          2)Insulated tempered glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Polycarbonate glazing.
          4)1/4 inch (6 mm) Polycarbonate glazing.
          5)1/2 inch (12.5 mm) Polycarbonate glazing.
          6)1/8 inch (3 mm) Tempered Glass.
          7)1/4 inch (6 mm) Tempered Glass.
          8)1/2 inch (12.5 mm) Tempered Glass.
          9)1/4 inch (6 mm) Wire Glass.
          10)1/2 inch (12.5 mm) Insulating Glass.
          11)1/8 inch (3 mm) Double strength glass.
          2.Finish and Color: Two coat baked-on polyester with white exterior and white interior color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 422 Series Insulated Steel Doors are available up to a maximum width of 31 feet 2 inches and a maximum height of 24 feet 1 inch. Edit as required to suit project requirements.
 
          I.Insulated Steel Sectional Overhead Doors: 422 Series Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Insulated steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed.
          c.Exterior Steel: 20 gauge, hot-dip galvanized.
          d.Back Cover:
          ** NOTE TO SPECIFIER ** Select one of the following backcover paragraphs and delete those not required.
          1)26 gauge steel.
          2)Poly-Backed.
          3)High Impact Polystyrene Backcover.
          e.Center and End Stiles: 16 gauge steel.
          f.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          g.Insulation: Polystyrene.
          h.Thermal Values:
          1)Polystyrene - R-value of 7.35; U-value of 0.136.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          i.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          j.Partial Glazing of Steel Panels:
          1)Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          2)Insulated tempered glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Polycarbonate glazing.
          4)1/4 inch (6 mm) Polycarbonate glazing.
          5)1/2 inch (12.5 mm) Polycarbonate glazing.
          6)1/8 inch (3 mm) Tempered Glass.
          7)1/4 inch (6 mm) Tempered Glass.
          8)1/2 inch (12.5 mm) Tempered Glass.
          9)1/4 inch (6 mm) Wire Glass.
          10)1/2 inch (12.5 mm) Insulating Glass.
          11)1/8 inch (3 mm) Double strength glass.
          2.Finish and Color: Two coat baked-on polyester with white exterior and white interior color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          *** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 426 Series Insulated Steel Doors are available up to a maximum width of 30 feet 2 inches and a maximum height of 24 feet 1 inch. Edit as required to suit project requirements.
 
          J.Insulated Steel Sectional Overhead Doors: 426 Series Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Insulated steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed.
          c.Exterior Steel: 24 gauge, hot-dip galvanized.
          d.Back Cover:
          ** NOTE TO SPECIFIER ** Select one of the following backcover paragraphs and delete those not required.
          1)26 gauge steel.
          2)Poly-Backed.
          3)High Impact Polystyrene Backcover.
          e.Center and End Stiles: 16 gauge steel.
          f.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          g.Insulation: Polystyrene.
          h.Thermal Values:
          1)Polystyrene - R-value of 7.35; U-value of 0.136.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          i.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          j.Partial Glazing of Steel Panels:
          1)Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Polycarbonate glazing.
          4)1/4 inch (6 mm) Polycarbonate glazing.
          5)1/2 inch (12.5 mm) Polycarbonate glazing.
          6)1/8 inch (3 mm) Tempered Glass.
          7)1/4 inch (6 mm) Tempered Glass.
          8)1/2 inch (12.5 mm) Tempered Glass.
          9)1/4 inch (6 mm) Wire Glass.
          10)1/2 inch (12.5 mm) Insulating Glass.
          11)1/8 inch (3 mm) Double strength glass.
          2.Finish and Color: Two coat baked-on polyester with white exterior and white interior color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 432 Series Insulated Steel Doors are available up to a maximum width of 20 feet 2 inches and a maximum height of 16 feet 1 inch. Edit as required to suit project requirements.
 
          K.Insulated Steel Sectional Overhead Doors: 432 Series Insulated Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Insulated steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed.
          c.Exterior Steel: Nominal 24 gauge, hot-dip galvanized.
          d.Back Cover:
          ** NOTE TO SPECIFIER ** Select one of the following backcover paragraphs and delete those not required.
          1)26 gauge steel.
          2)Poly-Backed.
          3)High Impact Polystyrene Backcover.
          e.Center and End Stiles: 16 gauge steel.
          f.Spring Counterbalance: Sized to weight of the door, with a helically wound, oil tempered torsion spring mounted on a steel shaft; cable drum of diecast aluminum with high strength galvanized aircraft cable. Sized with a minimum 7 to 1 safety factor.
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)Standard cycle spring: 10,000 cycles.
          2)High cycle spring: 25,000 cycles.
          3)High cycle spring: 50,000 cycles.
          4)High cycle spring: 75,000 cycles.
          5)High cycle spring: 100,000 cycles.
          g.Insulation: Polystyrene.
          h.Thermal Values:
          1)Polystyrene - R-value of 7.35; U-value of 0.136.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          i.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          j.Partial Glazing of Steel Panels:
          1)Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          k.Full Glazed Aluminum Sash Panels:
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Polycarbonate glazing.
          4)1/4 inch (6 mm) Polycarbonate glazing.
          5)1/2 inch (12.5 mm) Polycarbonate glazing.
          6)1/8 inch (3 mm) Tempered Glass.
          7)1/4 inch (6 mm) Tempered Glass.
          8)1/2 inch (12.5 mm) Tempered Glass.
          9)1/4 inch (6 mm) Wire Glass.
          10)1/2 inch (12.5 mm) Insulating Glass.
          11)1/8 inch (3 mm) Double strength glass.
          2.Finish and Color: Two coat baked-on polyester with white exterior and white interior color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Edit the following track size and type paragraphs as required and delete the ones not required.
          a.Size:
          1)2 inch (51 mm).
          2)3 inch (76 mm).
          b.Type:
          1)Standard lift.
          2)Vertical lift.
          3)High lift.
          4)Low headroom.
          5)Follow roof slope.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
 
          2.3STEEL SECTIONAL OVERHEAD DOORS
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 416 Series Steel Doors are available up to a maximum width of 32 feet 2 inches and a maximum height of 21 feet 1 inch. Edit as required to suit project requirements.
 
          A.Sectional Overhead Steel Doors: 416 Series Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Flush.
          c.Section Material: 16 gauge, galvanized steel.
          d.Center and End Stiles: 16 gauge steel.
          e.Springs:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)10,000 cycles.
          2)25,000 cycles.
          3)50,000 cycles.
          4)75,000 cycles.
          5)100,000 cycles.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          f.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          g.Partial Glazing of Steel Panels:
          1)Non-Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          h.Full Glazed Aluminum Sash Panels:
          1)Acrylic glazing.
          2)1/8 inch (3 mm) double strength glass.
          2.Finish and Color: Two coat baked-on polyester, white color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 420 Series Steel Doors are available up to a maximum width of 31 feet 2 inches and a maximum height of 24 feet 1 inch. Edit as required to suit project requirements.
 
          B.Sectional Overhead Steel Doors: 420 Series Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed.
          c.Section Material: 20 gauge, galvanized steel.
          d.Center and End Stiles: 16 gauge steel.
          e.Springs:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)10,000 cycles.
          2)25,000 cycles.
          3)50,000 cycles.
          4)75,000 cycles.
          5)100,000 cycles.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          f.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          g.Partial Glazing of Steel Panels:
          1)Non-Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          h.Full Glazed Aluminum Sash Panels:
          1)Acrylic glazing.
          2)1/8 inch (3 mm) double strength glass.
          2.Finish and Color: Two coat baked-on polyester, white color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 424 Series Steel Doors are available up to a maximum width of 30 feet 2 inches and a maximum height of 24 feet 1 inch. Edit as required to suit project requirements.
 
          C.Sectional Overhead Steel Doors: 424 Series Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed.
          c.Section Material: 24 gauge, galvanized steel.
          d.Center and End Stiles: 16 gauge steel.
          e.Springs:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)10,000 cycles.
          2)25,000 cycles.
          3)50,000 cycles.
          4)75,000 cycles.
          5)100,000 cycles.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          f.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          g.Partial Glazing of Steel Panels:
          1)Non-Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          h.Full Glazed Aluminum Sash Panels:
          1)Acrylic glazing.
          2)1/8 inch (3 mm) double strength glass.
          2.Finish and Color: Two coat baked-on polyester, white color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 430 Series Steel Doors are available up to a maximum width of 20 feet 2 inches and a maximum height of 16 feet 1 inch. Edit as required to suit project requirements.
 
          D.Sectional Overhead Steel Doors: 430 Series Steel Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Steel door assembly with rabbeted meeting rails to provide full-width interlocking structural rigidity.
          a.Panel Thickness: 2 inches (51 mm).
          b.Exterior Surface: Ribbed.
          c.Section Material: Nominal 24 gauge, galvanized steel.
          d.Center and End Stiles: 16 gauge steel.
          e.Springs:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)10,000 cycles.
          2)25,000 cycles.
          3)50,000 cycles.
          4)75,000 cycles.
          5)100,000 cycles.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Delete if not required.
          f.Knockout Lower Door Sections:
          1)Provide with optional knock-out lower door section. Lower two sections are Knock & Lock breakaway sections comprised of two sub-sections which can deflect in either direction when impacted. Exterior is 1/8 inch (3 mm) thick reinforced extruded polymer. Interior is a finished ABS backskin. Lower sections insulated with polystyrene insulation with extruded aluminum end caps.
          2)Panel Thickness: 1-3/4 inches (44 mm).
          3)Exterior Surface: Flush, Textured.
          4)Thermal Values: R-value of 8.56; U-value of 0.17.
          ** NOTE TO SPECIFIER ** Select partial glazing or full glazing from the following glazing paragraphs and edit to select glazing required. Delete those not required or delete entirely if glazing is not required..
          g.Partial Glazing of Steel Panels:
          1)Non-Insulated double strength glass, 24 inch by 7 inch (610 mm by 178 mm) window.
          h.Full Glazed Aluminum Sash Panels:
          1)Acrylic glazing.
          2)1/8 inch (3 mm) double strength glass.
          2.Finish and Color: Two coat baked-on polyester, white color.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. Interior mounted slide lock is standard.
          a.Interior mounted slide lock.
          b.Interior mounted slide lock with interlock switch for automatic operator.
          c.Keyed lock.
          d.Keyed lock with interlock switch for automatic operator.
          ** NOTE TO SPECIFIER ** Select the following paragraph for use with knock-out lower door sections only and delete the ones above.
          e.Locking mechanism designed to maintain security for exterior while permitting break out when impacted from the inside.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
 
          2.4GLAZED ALUMINUM SECTIONAL OVERHEAD DOORS
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 511 Series Aluminum Doors are available up to a maximum width of 16 feet 2 inches and a maximum height of 16 feet 1 inch. Edit as required to suit project requirements.
 
          A.Glazed Sectional Overhead Doors: 511 Series Aluminum Doors by Overhead Door Corporation. Units shall have the following characteristics:
          1.Door Assembly: Stile and rail assembly secured with 1/4 inch (6 mm).diameter through rods.
          a.Panel Thickness: 1-3/4 inches (44 mm).
          b.Center Stile Width: 21/32 inch (17 mm).
          c.End Stile Width: 2-3/4 inches (70 mm).
          d.Intermediate Rail Pair Width: 1-3/8 inches (35 mm).
          e.Top Rail Width:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          1)2-3/8 inches (60 mm).
          2)3-3/4 inches (95 mm).
          f.Bottom Rail Width:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          1)2-3/8 inches (60 mm).
          2)3-3/4 inches (95 mm).
          3)4-1/2 inches (114 mm).
          g.Aluminum Panels: 0.050 inch (1.3 mm) thick, aluminum.
          h.Stiles and Rails: 6063 - T6 aluminum.
          i.Springs:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)10,000 cycles.
          2)25,000 cycles.
          3)50,000 cycles.
          4)75,000 cycles.
          5)100,000 cycles.
          j.Glazing:
          ** NOTE TO SPECIFIER ** Select one of the following glazing paragraphs and delete those not required. Note that 1/4 inch and 1/2 inch Glass is not available on 511 Series in sizes greater than 14 feet 2 inches wide, however Acrylic and Clear Lexan is available in sizes over 14 feet 2 inches wide.
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          ** NOTE TO SPECIFIER ** Select one of the following finish paragraphs and delete those not required.
          2.Finish and Color:
          a.Anodized Finish: Clear anodized.
          b.Anodized Finish: Bronze anodized.
          c.Powder coat finish bronze light.
          d.Powder coat finish bronze medium.
          e.Powder coat finish bronze dark.
          f.Powder Coating Finish: Color as selected by Architect from manufacturer's standard colors.
          3.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          4.Lock: Interior galvanized single unit.
          5.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          6.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          7.Manual Operation: Pull rope.
          8.Manual Operation: Chain hoist.
          9.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
          ** NOTE TO SPECIFIER ** Overhead Door Corporation 521 Series Aluminum Doors are available up to a maximum width of 26 feet 2 inches and a maximum height of 20 feet 1 inch. Edit as required to suit project requirements.
 
          B.Glazed Sectional Overhead Doors: 521 Series Aluminum Doors by Overhead Door Corporation.
          1.Door Assembly: Stile and rail assembly secured with 1/4 inch (6 mm) diameter through rods.
          a.Panel Thickness: 1-3/4 inches (44 mm).
          b.Center Stile Width: 2-11/16 inches (68 mm)
          c.End Stile Width: 3-5/16 inches (84 mm)
          d.Intermediate Rail Pair Width: 3-11/16 inches (94 mm).
          e.Top Rail Width:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          1)2-3/8 inches (60 mm).
          2)3-3/4 inches (95 mm).
          f.Bottom Rail Width:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the one not required.
          1)3-3/4 inches (95 mm).
          2)4-1/2 inches (114 mm).
          g.Aluminum Panels: 0.050 inch (1.3 mm) thick, aluminum.
          h.Stiles and Rails: 6063 - T6 aluminum.
          i.Springs:
          ** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required. 10,000 cycles are standard.
          1)10,000 cycles.
          2)25,000 cycles.
          3)50,000 cycles.
          4)75,000 cycles.
          5)100,000 cycles.
          j.Glazing:
          ** NOTE TO SPECIFIER ** Select one of the following glazing paragraphs and delete those not required.
          1)1/8 inch (3 mm) Acrylic glazing.
          2)1/4 inch (6 mm) Acrylic glazing.
          3)1/8 inch (3 mm) Clear Lexan glazing.
          4)1/4 inch (6 mm) Clear Lexan glazing.
          5)1/2 inch (12.5 mm) Clear Lexan Insulated glazing.
          6)1/8 inch (3 mm) Tempered glass.
          7)1/4 inch (6 mm) Tempered glass.
          8)1/2 inch (12.5 mm) Tempered Insulating glass.
          9)1/4 inch (6 mm) Wire glass.
          10)1/8 inch (3 mm) Double Strength glass.
          11)1/2 inch (12.5 mm) Double Strength Insulating glass.
          12)1/8 inch (3 mm) Low E glazing.
          13)1/4 inch (6 mm) Low E glazing.
          14)1/2 inch (12.5 mm) Low E Insulated glazing.
          15)1/8 inch (3 mm) Solar Bronze glazing.
          16)1/4 inch (6 mm) Solar Bronze glazing.
          17)1/2 inch (12.5 mm) Solar Bronze Insulated glazing.
          18)1/8 inch (3 mm) Obscure glazing.
          19)1/4 inch (6 mm) Obscure glazing.
          20)1/2 inch (12.5 mm) Obscure Insulated glazing.
          21)1/4 inch (6 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          22)3/8 inch (9.5 mm) Twin-Wall Polycarbonate (clear, bronze, white).
          23)5/8 inch (15.87 mm) Triple-Wall Polycarbonate (clear, bronze, white).
          ** NOTE TO SPECIFIER ** Select one of the following finish paragraphs and delete those not required.
          2.Finish and Color:
          a.Anodized Finish: Clear anodized.
          b.Anodized Finish: Bronze anodized.
          c.Powder coat finish bronze light.
          d.Powder coat finish bronze medium.
          e.Powder coat finish bronze dark.
          f.Powder Coating Finish: Color as selected by Architect from manufacturer's standard colors.
          ** NOTE TO SPECIFIER ** The following paragraph is optional. Contact the manufacturer for additional information. Include the Design/Performance Requirements in Part 1 of this specification.
          3.Windload Design: Provide to meet the Design/Performance requirements specified.
          4.Hardware: Galvanized steel hinges and fixtures. Ball bearing rollers with hardened steel races.
          5.Lock: Interior galvanized single unit.
          6.Weatherstripping:
          ** NOTE TO SPECIFIER ** Select the seals required from the following paragraphs and delete those not required. Bottom seal is standard, jamb seals and head seals are optional.
          a.Flexible bulb-type strip at bottom section.
          b.Flexible Jamb seals.
          c.Flexible Header seal.
          7.Track: Provide track as recommended by manufacturer to suit loading required and clearances available.
          ** NOTE TO SPECIFIER ** Select one of the following Operation paragraphs and delete the ones not required. Manual pull rope is standard.
          8.Manual Operation: Pull rope.
          9.Manual Operation: Chain hoist.
          10.Electric Motor Operation: Provide UL listed electric operator, size and type as recommended by manufacturer to move door in either direction at not less than 2/3 foot nor more than 1 foot per second. Operator shall meet UL325/2010 requirements for continuous monitoring of safety devices.
          a.Entrapment Protection: Required for momentary contact, includes radio control operation.
          ** NOTE TO SPECIFIER ** Select one of the following protection paragraphs and delete those not required.
          1)Pneumatic sensing edge up to 18 feet (5.5 m) wide. Constant contact only complying with UL 325/2010.
          2)Electric sensing edge monitored to meet UL 325/2010.
          3)Photoelectric sensors monitored to meet UL 325/2010.
          b.Operator Controls:
          ** NOTE TO SPECIFIER ** Select one of the following control paragraphs and delete those not required.
          1)Push-button operated control stations with open, close, and stop buttons.
          2)Key operated control stations with open, close, and stop buttons.
          3)Push-button and key operated control stations with open, close, and stop buttons.
          ** NOTE TO SPECIFIER ** Select one of the following mounting paragraphs and delete the one not required.
          4)Flush mounting.
          5)Surface mounting.
          ** NOTE TO SPECIFIER ** Select one of the following mounting location paragraphs and delete those not required.
          6)Interior location.
          7)Exterior location.
          8)Both interior and exterior location.
          ** NOTE TO SPECIFIER ** Select special operation features from the following paragraphs and delete those not required. Delete entirely if not required.
          c.Special Operation:
          1)Pull switch.
          2)Vehicle detector operation.
          3)Radio control operation.
          4)Card reader control.
          5)Photocell operation.
          6)Door timer operation.
          7)Commercial light package.
          8)Explosion and dust ignition proof control wiring.
 
          PART 3EXECUTION
 
          3.1EXAMINATION
 
          A.Do not begin installation until openings have been properly prepared.
 
          B.Verify wall openings are ready to receive work and opening dimensions and tolerances are within specified limits.
 
          C.Verify electric power is available and of correct characteristics.
 
          D.If preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
 
          3.2PREPARATION
 
          A.Clean surfaces thoroughly prior to installation.
 
          B.Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
 
          3.3INSTALLATION
 
          A.Install overhead doors and track in accordance with approved shop drawings and the manufacturer's printed instructions.
 
          B.Coordinate installation with adjacent work to ensure proper clearances and allow for maintenance.
 
          C.Anchor assembly to wall construction and building framing without distortion or stress.
 
          D.Securely brace door tracks suspended from structure. Secure tracks to structural members only.
 
          E.Fit and align door assembly including hardware.
          ** NOTE TO SPECIFIER ** Select one of the following paragraph for power operated doors. Delete if not required.
 
          F.Coordinate installation of electrical service. Complete power and control wiring from disconnect to unit components.
 
          3.4CLEANING AND ADJUSTING
 
          A.Adjust door assembly to smooth operation and in full contact with weatherstripping.
 
          B.Clean doors, frames and glass.
 
          C.Remove temporary labels and visible markings.
 
          3.5PROTECTION
 
          A.Do not permit construction traffic through overhead door openings after adjustment and cleaning.
 
          B.Protect installed products until completion of project.
 
          C.Touch-up, damaged coatings and finishes and repair minor damage before Substantial Completion.
 
         
END OF SECTION