Download SECTION 14 20 00 ELEVATORS AND DUMBWAITERS for
WORD | RTF | Text | Word Perfect
Find over 500 more CSI Sections
on Arcat.com
Switch to Masterformat 95
 
SECTION 14 20 00
ELEVATORS AND DUMBWAITERS
 
 
Copyright 2016 - 2016 ARCAT, Inc. - All rights reserved
** NOTE TO SPECIFIER ** Nationwide Lifts, Inc. ; residential/commercial elevators and lifts.
This section is based on the products of Nationwide Lifts, Inc. , which is located at:
10-B Holden Ave.
Queensbury, NY 12804
Toll Free Tel: 888-323-8755
Email: request info (info@nwlifts.com)
Web: www.elevators.com
[ Click Here ] for additional information.
Nationwide Lifts has the most complete and innovative product line in the industry. We strive to develop new products and partnerships, giving homes and businesses exactly what they need. With our network of offices and affiliates, Nationwide Lifts is capable of fulfilling your elevator needs anywhere in North America!
 
PART 1 GENERAL
 
1.1
SECTION INCLUDES
 
** NOTE TO SPECIFIER ** Delete items below not required for project.
 
A.
Dumbwaiters. (Jeeves, Jeeves Pro, Jeeves Pro RST)
B.
Residential Elevators. (Freedom Green, Freedom Hydro, Freedom Elite, Visilift 48 Octagonal, Visilift(R) 58 Round)
C.
Limed-Use, Limited Access (LULA) Elevators. (Freedom LULA)
1.2
RELATED SECTIONS
 
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
A.
Section 03 30 00 - Cast-in-Place Concrete.
B.
Section 06 10 00 - Rough Carpentry.
C.
Section 08 11 00 - Metal Doors and Frames.
D.
Section 09 21 16.23 - Gypsum Board Shaft Wall Assemblies.
E.
Section 09 60 00 - Flooring.
F.
Section 28 36 33 - Water Detection Sensors.
G.
Division 16 - Electrical for electrical service and disconnects, wire routing and connections, telephone service.
1.3
REFERENCES
 
** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
 
A.
ANSI/ASME A17.1/CAN/CSA B44 - Safety Code for Elevators and Escalators.
B.
ANSI/NFPA 70 - National Electric Code.
C.
ANSI/NFPA 80 - Fire Doors and Windows.
D.
ANSI/UL 10B - Fire Tests of Door Assemblies.
E.
BADAAG - Americans with Disabilities Act Accessibility Guidelines.
F.
CANSI/NFPA 70 - National Electrical Code.
G.
CAN/CSA C22.1 - Canadian Electrical Code.
H.
ISO 9001: 2000 - Quality Management Systems - Requirements.
I.
Model and Local Building Codes.
1.4
SUBMITTALS
A.
Submit under provisions of Section 01 30 00 - Administrative Requirements.
B.
Product Data: Submit manufacturer/installer's product data, including:
1.
Descriptive brochures or detail drawings of cab and hall fixtures, cab decoration options, and product features.
2.
Power Information: Horsepower, starting current, running current, machine and control heat release, and electrical requirements.
C.
Shop Drawings: Submit manufacturer/installer's shop drawings, including plans, elevations, sections, and details, indicating location of equipment, loads, dimensions, tolerances, materials, components, fabrication, fasteners, hardware, finish, options, accessories, and other information to render totally functional elevators.
D.
Operation and Maintenance Manual: Submit manufacturer/installer's operation and maintenance manual; including operation, maintenance, adjustment, and cleaning instructions; trouble shooting guide; renewal parts catalogs; and electrical wiring diagrams.
E.
Warranty: Submit documentation associated with manufacturer/installer's standard warranty.
1.5
QUALITY ASSURANCE
A.
Manufacturer Qualifications: Minimum 5 year experience manufacturing similar products.
B.
Installer Qualifications: Minimum 2 year experience installing similar products.
C.
Regulatory Requirements:
1.
Elevator design, clearances, construction, workmanship, materials, and installation, unless specified otherwise, shall be in accordance with ANSI/ASME A17.1, handicap accessibility, Americans with Disabilities Act, and other codes having legal jurisdiction.
2.
ANSI/ASME A17.1 shall govern, except where codes having legal jurisdiction include more rigid requirements or conflict with ANSI/ASME A17.1.
3.
Where product is in variance to the published ANSI/ASME A17.1 model code, provide a third party AECO certification demonstrating equivalent function, safety, and performance.
1.6
PRE-INSTALLATION MEETINGS
A.
Pre-installation Meeting:
1.
Convene pre-installation meeting before start of installation of elevators.
2.
Require attendance of parties directly affecting work of this section, including Contractor, Architect, and elevator manufacturer/installer.
3.
Review examination, installation, field quality control, adjusting, cleaning, protection, and coordination with other work.
1.7
DELIVERY, STORAGE, AND HANDLING
A.
Deliver and store products in manufacturer's unopened packaging bearing the brand name and manufacturer's identification until ready for installation.
B.
Handling: Handle materials to avoid damage.
1.8
PROJECT CONDITIONS
A.
Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.
B.
Temporary Electrical Power:
1.
Coordinate availability of temporary, single-phase, 60 Hz, GFCI-protected electricity to be available for installation of elevator components.
C.
Installation of the Elevator:
1.
Coordinate availability of permanent power prior to installation start.
2.
Coordinate availability of clear, rollable access to a 10 foot by 20 foot secure and dry storage area prior to delivery.
3.
Coordinate availability of a clean, dry, and complete hoistway along with temporary installation platform and all required OSHA-compliant barricades prior to delivery.
1.9
SEQUENCING
A.
Ensure that products of this section are supplied to affected trades in time to prevent interruption of construction progress.
1.10
WARRANTY
A.
Residential Manufacturer/Installer Standard Warranty: Manufacturer/installer shall guarantee materials and workmanship of equipment installed under these specifications and make good, defects not due to ordinary wear or to improper use, which may develop after completion of installation or acceptance thereof by beneficial use, whichever is earlier.
1.
Provide a 10-Year Warranty on mechanical components.
2.
Provide a 3-Year Warranty on electrical components.
3.
Provide a 1-Year Warranty on labor.
B.
Commercial Manufacturer/Installer Standard Warranty: Manufacturer/installer shall guarantee materials and workmanship of equipment installed under these specifications and make good, defects not due to ordinary wear or to improper use, which may develop after completion of installation or acceptance thereof by beneficial use, whichever is earlier.
1.
Provide a 3-Year Warranty on mechanical components.
2.
Provide a 3-Year Warranty on electrical components.
3.
Provide a 1-Year Warranty on labor.
1.11
MAINTENANCE SERVICE
A.
Elevator maintenance service shall be performed by elevator manufacturer/installer.
B.
Elevators shall receive regular maintenance on each unit for period below after completion of work specified herein or acceptance thereof by beneficial use, whichever is earlier.
 
** NOTE TO SPECIFIER ** Delete one of the two following paragraphs.
 
1.
Maintenance Period: 12 months.
2.
Maintenance Period: 3 months.
C.
Trained employees shall make periodic examinations and perform work including necessary adjusting, greasing, oiling, and replacing parts to keep elevators in operation, except parts that require replacement because of accidents, vandalism, misuse, or negligence by parties other than manufacturer/installer.
D.
Manufacturer/installer shall perform all Work, except emergency minor adjustment call-back service as follows:
 
** NOTE TO SPECIFIER ** Delete one of the two following paragraphs.
 
1.
During regular working hours.
2.
On overtime.
E.
Manufacturer/installer shall provide emergency minor adjustment call-back service as follows:
 
** NOTE TO SPECIFIER ** Delete one of the two following paragraphs.
 
1.
During regular working hours.
2.
24 hours, 7 days a week.
PART 2 PRODUCTS
 
2.1
MANUFACTURERS
A.
Acceptable Manufacturer: Nationwide Lifts, Inc. , which is located at: 10-B Holden Ave.; Queensbury, NY 12804; Toll Free Tel: 888-323-8755; Email: request info (info@nwlifts.com); Web: www.elevators.com
 
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
B.
Substitutions: Not permitted.
C.
Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.
2.2
DUMBWAITERS
 
** NOTE TO SPECIFIER ** Jeeves EconoLift: These dumbwaiters are simple and cost effective. They are available in 2 standard sizes, with custom sizes available. The cab is constructed of birch plywood. The cab has a roll-up gate. Landing doors are available, but the homeowner usually provides doors to match the home. Delete if not required.
 
A.
Dumbwaiter: Jeeves EconoLift as manufactured by Nationwide Lifts, Inc.
 
** NOTE TO SPECIFIER ** Delete model not required.
 
1.
Model: Econo-Lift 100 Dumbwaiter.
 
** NOTE TO SPECIFIER ** Delete door location not required.
 
a.
Doors: Same side.
b.
Doors: Front and back.
c.
Car Size: 20 inches W x 20 inches D x 30 inches H (508 mm x 508 mm x 762 mm).
d.
Capacity: 100 lb. (45 kg).
e.
Stops: Up to 3 stops.
f.
Travel: Up to 27 feet (8230 mm).
g.
Travel Speed; 30 feet per minute (9 m/minute).
h.
Power: Provide dedicated 115 V, 15 A circuit in a lockable fused disconnect.
2.
Model: Econo-Lift 150 Dumbwaiter:
 
** NOTE TO SPECIFIER ** Delete door location not required.
 
a.
Doors: Same side.
b.
Doors: Front and back.
c.
Car Size: 24 inches W x 24 inches D x 30 inches H (610 mm x 610 mm x 762 mm).
d.
Capacity: 150 lb. (68 kg).
e.
Stops: Up to 3 stops.
f.
Travel: Up to 27 feet (8230 mm).
g.
Travel Speed; 30 feet per minute (9 m/minute).
h.
Power: Provide dedicated 115 V, 15 A circuit in a lockable fused disconnect.
3.
Model: Econo-Lift 150 Dumbwaiter:
 
** NOTE TO SPECIFIER ** Delete door location not required.
 
a.
Doors: Same side.
b.
Doors: Front and back.
c.
Car Size: 24 inches W x 24 inches D x 30 inches H (610 mm x 610 mm x 762 mm).
d.
Capacity: 150 lb. (68 kg).
e.
Stops: Up to 3 stops.
f.
Travel: Up to 17 feet 10 inches (2388 mm).
g.
Travel Speed; 30 feet per minute (9 m/minute).
h.
Power: Provide dedicated 115 V, 15 A circuit in a lockable fused disconnect.
4.
Provide car constructed of Birch plywood with roll-up gate.
5.
Hoistway Door Operation: Swing.
 
** NOTE TO SPECIFIER ** Delete door construction not required.
 
a.
Provide hoistway door constructed of plain steel.
b.
Provide hoistway door constructed of stainless steel #4 mechanical finish.
c.
Provide hoistway door constructed of wood.
d.
Hoistway door constructed as indicated on drawings and provided in related Sections.
 
** NOTE TO SPECIFIER ** Delete interlock type not required.
 
e.
Provide single contact door lock (HC-1).
f.
Provide double contact door lock (HC-2).
6.
Hoistway Door Controls: Wall mounted push button station:
 
** NOTE TO SPECIFIER ** Delete type not required.
 
a.
Provide illuminated station with landing buttons as required.
b.
Provide non-illuminated station with landing buttons as required.
 
** NOTE TO SPECIFIER ** Delete machine location not required.
 
7.
Machine room location shall be located adjacent to hoistway at the bottom floor behind the rail wall as indicated.
8.
Machine location shall be located within the hoistway on the bottom floor as indicated.
9.
Machine location shall be located within the hoistway overhead as indicated.
 
** NOTE TO SPECIFIER ** Jeeves Pro: These dumbwaiters are built for commercial applications. They are available in 2 standard sizes, with custom sizes available. The cab is constructed of powder coated steel. Stainless steel upgrade is available. The cab has a bi-parting gate. Landing doors are available in bi-parting, swing, or slide-up. Delete if not required.
 
B.
Dumbwaiter: Jeeves Pro as manufactured by Nationwide Lifts, Inc.
 
** NOTE TO SPECIFIER ** Delete model not required.
 
1.
Model: Jeeves Pro 125 Dumbwaiter:
 
** NOTE TO SPECIFIER ** Delete door location not required.
 
a.
Doors: Same side.
b.
Doors: Front and back.
c.
Car Size: 24 inches W x 24 inches D x 24 inches H (610 mm x 610 mm x 610 mm).
d.
Capacity: 125 lb. (57 kg).
e.
Stops: Up to 6 stops.
f.
Travel: Up to 80 feet (24384 mm).
g.
Travel Speed; 30 feet per minute (9 m/minute).
h.
Controls; 24 V Jamb mounted push buttons with car status lights.
i.
Power: Provide dedicated 115 V, 20 A circuit in a lockable fused disconnect.
2.
Model: Jeeves Pro 250 Dumbwaiter:
 
** NOTE TO SPECIFIER ** Delete door location not required.
 
a.
Doors: Same side.
b.
Doors: Front and back.
c.
Car Size: 28 inches W x 28 inches D x 28 inches H (711mm x 711 mm x 711 mm).
d.
Capacity: 250 lb. (113 kg).
e.
Stops: Up to 6 stops.
f.
Travel: Up to 80 feet (24384 mm).
g.
Travel Speed; 30 feet per minute (9 m/minute).
h.
Controls; 24 V Jamb mounted push buttons with car status lights.
i.
Power: Provide dedicated 115 V, 20 A circuit in a lockable fused disconnect.
 
** NOTE TO SPECIFIER ** Delete car construction not required.
 
3.
Car: Provide car constructed of powder coated steel.
4.
Car: Provide car constructed of stainless steel.
5.
Car Gate: Bi-parting.
 
** NOTE TO SPECIFIER ** Delete hoistway door type not required.
 
6.
Hoistway Door Operation: Bi-parting.
7.
Hoistway Door Operation: Swing.
8.
Hoistway Door Operation: Slide-up.
9.
Hoistway Door:
a.
Provide emergency release.
b.
Provide hoistway door constructed of powder coated plain steel.
c.
Provide hoistway door constructed of stainless steel #4 mechanical finish.
d.
Hoistway door constructed as indicated on drawings and provided in related Sections.
 
** NOTE TO SPECIFIER ** Delete interlock type not required.
 
e.
Provide single contact door lock (HC-1).
f.
Provide double contact door lock (HC-2).
10.
Hoistway Door Controls: Wall mounted push button station:
a.
Provide illuminated station with landing buttons as required.
b.
Provide non-illuminated station with landing buttons as required.
11.
Machine room location shall be located adjacent to hoistway at the bottom floor behind the rail wall as indicated.
12.
Machine room location shall be located within the hoistway on the bottom floor as indicated.
 
** NOTE TO SPECIFIER ** Jeeves Pro RST: The Jeeves Pro RST dumbwaiters are designed to meet the specific needs of restaurants. The cab, gate, and doors are constructed of stainless steel. Removable shelves are available upon request. The mechanical components are prepared for the extensive use that restaurants demand. Delete if not required.
 
C.
Dumbwaiter: Jeeves Pro RST as manufactured by Nationwide Lifts, Inc.
1.
Capacity: 250 lbs.
 
** NOTE TO SPECIFIER ** Delete car size not required.
 
2.
Car Size: 20 inches W x 30 inches D x 36 inches H standard (508 mm x 762 mm x 914 mm).
3.
Car Size: Custom. Refer to drawings.
4.
Travel Speed: 30 feet per minute (9 m/minute).
5.
Travel: Up to 6 stops and 80 feet (24384 mm).
 
** NOTE TO SPECIFIER ** Delete opening location not required.
 
6.
Openings: In-line.
7.
Openings: Opposite.
 
** NOTE TO SPECIFIER ** Delete loading location not required.
 
8.
Loading: Floor loading.
9.
Loading: Counter loading.
10.
Car: Provide car constructed of stainless steel.
11.
Car Gate: Slide up.
12.
Hoistway Door Operation: Bi-parting.
a.
Provide emergency release.
b.
Provide hoistway door constructed of stainless steel #4 mechanical finish.
 
** NOTE TO SPECIFIER ** Delete interlock type not required.
 
c.
Provide single contact door lock (HC-1).
d.
Provide double contact door lock (HC-2).
13.
Power: Provide dedicated 115 V, 20 A circuit in a lockable fused disconnect.
14.
Hoistway Door Controls: Jamb mounted push button station:
 
** NOTE TO SPECIFIER ** Delete controls type not required.
 
a.
Provide illuminated station with landing buttons as required.
b.
Provide non-illuminated station with landing buttons as required.
 
** NOTE TO SPECIFIER ** Delete machine location not required.
 
15.
Machine room location shall be located adjacent to hoistway at the bottom floor behind the rail wall as indicated.
16.
Machine location shall be located within the hoistway on the bottom floor or overhead as indicated.
 
** NOTE TO SPECIFIER ** Jeeves Pro 500 LB dumbwaiter: Delete if not required. Delete if not required.
 
D.
Dumbwaiter: Jeeves Pro 500 as manufactured by Nationwide Lifts, Inc.
1.
Capacity: 500 lbs.
 
** NOTE TO SPECIFIER ** Delete car size not required.
 
2.
Car Size: 36 inches W x 36 inches D x 48 inches H standard (914 mm x 914 mm x 1219 mm).
3.
Car Size: Custom. Refer to drawings.
4.
Travel Speed: 30 feet per minute (9 m/minute).
5.
Travel: Up to 6 stops and 80 feet (24384 mm).
 
** NOTE TO SPECIFIER ** Delete opening location not required.
 
6.
Openings: In-line.
7.
Openings: Opposite.
 
** NOTE TO SPECIFIER ** Delete loading location not required.
 
8.
Loading: Floor loading.
9.
Loading: Counter loading.
10.
Car: Provide car constructed of stainless steel.
11.
Car Gate: Slide up.
12.
Hoistway Door Operation: Bi-parting.
a.
Provide emergency release.
b.
Provide hoistway door constructed of stainless steel #4 mechanical finish.
 
** NOTE TO SPECIFIER ** Delete interlock type not required.
 
c.
Provide single contact door lock (HC-1).
d.
Provide double contact door lock (HC-2).
13.
Power: Provide dedicated 220 V, 20 A circuit in a lockable fused disconnect.
14.
Hoistway Door Controls: Jamb mounted push button station:
a.
Provide illuminated station with landing buttons as required.
b.
Provide non-illuminated station with landing buttons as required.
15.
Machine room location shall be located adjacent to hoistway at the bottom floor behind the rail wall as indicated.
16.
Machine location shall be located within the hoistway on the bottom floor or overhead as indicated.
 
** NOTE TO SPECIFIER ** Delete if not required.
 
2.3
RESIDENTIAL ELEVATORS
 
** NOTE TO SPECIFIER ** Nationwide Lifts' Freedom Green is a residential elevator designed to provide a luxurious, yet affordable means of transportation while providing environmentally conscious homeowners a green solution. The Freedom Green's smooth operation is ensured by its variable frequency drive system technology. With a variety of cab finishes and colors, the Freedom Green allows you to customize your cab for a more personalized look. The Freedom Green offers many standard features that are costly extras on many other elevators. This makes it the ideal choice when selecting a luxury elevator for your home
 
A.
Elevator: Freedom Green as manufactured by Nationwide Lifts, Inc.
1.
Code Compliance: ASME A17.1 Section 5.3 (Residential Elevators)
2.
Load Capacity: 950 lbs (431 kg).
3.
Load Capacity: 1000 lbs (454 kg).
 
** NOTE TO SPECIFIER ** Not allowed in all regions.
 
4.
Load Capacity: 1400 lbs (635 kg).
5.
Rated Speed: 40 fpm (0.20m/s).
6.
Power Supply: 230V, 1PH, 60Hz, 30A
7.
Lighting Supply: 115V, 60Hz, 15A
8.
Audio Supply: Functional phone line.
9.
Drive System: Automatic
a.
3HP winding drum with variable frequency drive
10.
Temperature Range: -10 to + 40 degrees C, (14 to 104 degrees F).
11.
Maximum Travel: 50 feet (15240 mm).
12.
Control System: PLC with error log and troubleshooting indicators.
13.
Levels: Up to 5 stops.
14.
Openings: Up to 3 openings.
 
** NOTE TO SPECIFIER ** Delete pit depth not required.
 
15.
Pit Depth: Cab with accordion gate: 6 inches (152 mm), minimum, 8 inches (203 mm) recommended.
16.
Pit Depth: Cab with 2-speed gate: 8 inches (203 mm) minimum, 12 inches (305 mm) recommended.
 
** NOTE TO SPECIFIER ** Delete hoistway overhead not required.
 
17.
Minimum Overhead: 92 inches (2337 mm) for standard 80 inches (2032 mm) cab with accordion gate.
18.
Minimum Overhead: 108 inches (2743 mm) for 96 inches (2438 mm) cab with accordion gate.
19.
Minimum Overhead: 96 inches (2438 mm) for cab with 78 inches (1981 mm) 2-speed gate
20.
Minimum Overhead: 102 inches (2591 mm) for cab with 84 inches (2134 mm) 2-speed gate
21.
Minimum Overhead: 117 inches (2972 mm) for cab with 94 inches (2388 mm) 2-speed gate
 
** NOTE TO SPECIFIER ** Delete cab size not required.
 
22.
Cab Size: 36 inches by 48 inches (914 mm by 1219 mm).
23.
Cab Size: 36 inches by 54 inches (914 mm by 1372 mm).
24.
Cab Size: 36 inches by 60 inches (914 mm by 1524 mm).
25.
Cab Size: 40 inches by 48 inches (1016 mm by 1219 mm).
26.
Cab Size: 40 inches by 54 inches (1016 mm by 1372 mm).
27.
Cab Size: 44 inches by 48 inches (1118 mm by 1219 mm).
28.
Cab Size: 40 inches by 60 inches (1016 mm by 1524 mm). Requires 1400 lbs (635 kg) capacity.
29.
Cab Size: 44 inches by 54 inches (1118 mm by 1372 mm). Requires 1400 lbs (635 kg) capacity.
30.
Cab Size: 48 inches by 48 inches (1219 mm by 1219 mm). Requires 1400 lbs (635 kg) capacity.
31.
Cab Size: Custom. Maximum size 15 sf (1.4 sm).
 
** NOTE TO SPECIFIER ** Delete configuration not required.
 
32.
Platform Configuration: Enter/exit same side.
33.
Platform Configuration: Enter/exit opposite sides (front and rear).
34.
Platform Configuration: Enter/exit 90 degrees (front and side).
35.
Cab Lighting: Automatic LED Lighting
36.
Cab Phone: Hands-free, recessed in wall.
37.
Safety Features:
 
** NOTE TO SPECIFIER ** Delete safety features not required.
 
a.
Provide cab emergency stop switch.
b.
Provide cab gate switch.
c.
Provide pit stop switch
d.
Provide car top stop switch.
e.
Provide battery backup lowering.
f.
Provide battery backup lighting.
g.
Provide upper and lower final limit switches.
h.
Provide safety brakes.
i.
Provide slack cable switch.
j.
Provide shoring pins for service.
k.
Provide auxiliary safety circuit for service.
 
** NOTE TO SPECIFIER ** Delete hall station faceplate not required.
 
38.
Hall Station / COP Finish: Stainless steel.
39.
Hall Station / COP Finish: Brass.
40.
Hall Station / COP Finish: Bronze.
 
** NOTE TO SPECIFIER ** Delete cab panel not required.
 
41.
Cab Panel: Melamine (gray, almond, oak, maple, cherry).
42.
Cab Panel: Hardwood veneer (oak, maple, cherry, walnut, mahogany).
43.
Cab Panel: Recessed hardwood veneer (oak, maple, cherry, walnut, mahogany).
44.
Cab Panel: Raised hardwood (oak, maple, cherry, walnut, mahogany).
45.
Cab Panel: Stainless steel walls.
46.
Cab Panel: Glass walls.
47.
Cab Flooring: As indicated. Refer to Drawings.
 
** NOTE TO SPECIFIER ** Delete cab ceiling not required.
 
48.
Cab Ceiling: White Melamine.
49.
Cab Ceiling: Match cab walls.
 
** NOTE TO SPECIFIER ** Delete cab gate not required.
 
50.
Cab Gate: Center-parting dual bi-fold gate. (vinyl, clear, or metallic) manual or automatic.
51.
Cab Gate: Accordion gate (vinyl, clear, or metallic) manual or automatic.
52.
Cab Gate: 2-speed sliding gate (stainless steel, primed steel, or glass)
53.
Cab Gate: 3-speed sliding gate (stainless steel, primed steel, or glass)
 
** NOTE TO SPECIFIER ** Delete landing doors not required.
 
54.
Landing Doors: Swing doors by others (EMI interlocks provided with elevator).
55.
Landing Doors: 2-speed sliding door (stainless steel, primed steel, or glass).
56.
Landing Doors: 3-speed sliding door (stainless steel, primed steel, or glass).
57.
Landing Doors: Fire-rated 2-speed sliding doors (stainless steel, primed steel, or glass).
 
** NOTE TO SPECIFIER ** Delete cab height not required.
 
58.
Cab Height: Standard as provided by manufacturer.
59.
Cab Height: Custom. Refer to drawings.
 
** NOTE TO SPECIFIER ** Delete options not required.
 
60.
Touch screen car operating panel.
61.
Keypad lock (need PIN to run to a level).
62.
Integration with home automation.
63.
Keyed call stations.
64.
Upgraded accordion gates.
65.
Automatic accordion gate operator.
66.
Automatic swing door operator.
67.
Veneer wrap on 2-speed doors.
 
** NOTE TO SPECIFIER ** Freedom Hydro: The Freedom Hydro is an economical and reliable hydraulic home elevator. This elevator requires a nearby machine room to house the pump/tank and controller. This elevator has several options for cab finishes, gates, and doors.
 
68.
Melamine or unfinished veneer walls are standard. Raised hardwood and glass walls are optional.
69.
Capacity of 1000 lbs. Standard sizes of 36 inches x 48 inches and 40 inches x 54 inches. Custom sizes available up to 15 sq ft. Travel speed is 40 ft per min. Travels up to 6 stops and 50 ft.
B.
Freedom Hydro as manufactured by Nationwide Lifts, Inc.
 
** NOTE TO SPECIFIER ** Insert levels served.
 
1.
Number of Levels Serviced:
a.
____ levels.
 
** NOTE TO SPECIFIER ** Insert total travel distance.
 
2.
Travel.
a.
____ feet ____ inches.
3.
Drive System.
a.
Roped Hydraulic (hole-less).
b.
Submersible pump unit.
4.
Safety Features.
a.
Overspeed valve.
b.
Safety brake system.
c.
Emergency alarm and stop switch.
d.
Final limit switches.
e.
Gate switch.
f.
Landing door interlocks.
5.
Electrical Requirements.
a.
230V, 30A service to a fused, lockable disconnect with auxiliary contact.
b.
115V, 15A service to a fused, lockable disconnect (for lighting circuit).
c.
Functional phone line.
6.
Controls.
a.
Fully automatic push button in cab and at landings.
b.
Automatic car lighting.
c.
Position indicator in cab.
d.
Microprocessor based controller.
7.
Speed: 40 fpm (0.20 m/s).
 
** NOTE TO SPECIFIER ** Delete capacity not required.
 
8.
Capacity: 950 lbs (431 kg).
9.
Capacity: 1000 lbs (454 kg).
 
** NOTE TO SPECIFIER ** Not allowed in all region
 
10.
Capacity: 1400 lbs (635 kg).
 
** NOTE TO SPECIFIER ** Delete car size not required.
 
11.
Car Size: 36 inches by 48 inches (914 mm by 1219 mm).
12.
Car Size: 36 inches by 54 inches (914 mm by 1372 mm).
13.
Car Size: 36 inches by 60 inches (914 mm by 1524 mm).
14.
Car Size: 40 inches by 48 inches (1016 mm by 1219 mm).
15.
Car Size: 40 inches by 54 inches (1016 mm by 1372 mm).
16.
Car Size: 44 inches by 48 inches (1118 mm by 1219 mm).
17.
Car Size: 40 inches by 60 inches (1016 mm by 1524 mm). Requires 1400 lbs (635 kg). capacity
18.
Car Size: 44 inches by 54 inches (1118 mm by 1372 mm). Requires 1400 lbs (635 kg) capacity.
19.
Car Size: 48 inches by 48 inches (1219 mm by 1219 mm). Requires 1400 lbs (635 kg) capacity.
 
** NOTE TO SPECIFIER ** Delete configuration not required.
 
20.
Platform Configuration: Enter/exit same side.
21.
Platform Configuration: Enter/exit opposite sides (front and rear).
22.
Platform Configuration: Enter/exit 90 degrees (front and side).
 
** NOTE TO SPECIFIER ** Delete finishes not required.
 
23.
Cab Fixtures Finish: Stainless Steel.
24.
Cab Fixtures Finish: Oil Rubbed Bronze.
25.
Cab Fixtures Finish: Brass.
 
** NOTE TO SPECIFIER ** Delete gate not required.
 
26.
Cab Gate: Folding accordion gate.
27.
Cab Gate: Sliding 2-speed gate.
 
** NOTE TO SPECIFIER ** Delete cab gate finish not required.
 
28.
Cab Gate Finish: White Vinyl.
29.
Cab Gate Finish: Clear Acrylic.
30.
Cab Gate Finish: Aluminum.
31.
Cab Gate Finish: Unfinished Veneer. - Cherry.
32.
Cab Gate Finish: Unfinished Veneer. - Maple.
33.
Cab Gate Finish: Unfinished Veneer. - Oak.
 
** NOTE TO SPECIFIER ** Delete landing door not required.
 
34.
Landing Doors: Solid core wood doors at each landing, provided by GC.
35.
Landing Doors: Sliding 2-speed doors, provided by Nationwide Lifts.
 
** NOTE TO SPECIFIER ** Delete landing door finish not required.
 
36.
Landing Door Finish: By GC.
37.
Landing Door Finish: Primed for paint.
38.
Landing Door Finish: Stainless Steel.
39.
Landing Door Finish: Unfinished Veneer - Cherry.
40.
Landing Door Finish: Unfinished Veneer - Maple.
41.
Landing Door Finish: Unfinished Veneer - Oak.
 
** NOTE TO SPECIFIER ** Delete cab wall finish not required.
 
42.
Cab Wall Finish: Melamine - Cherry.
43.
Cab Wall Finish: Melamine - Maple.
44.
Cab Wall Finish: Melamine - Oak.
45.
Cab Wall Finish: Melamine - White.
46.
Cab Wall Finish: Unfinished Hardwood Veneer - Cherry.
47.
Cab Wall Finish: Unfinished Hardwood Veneer - Maple.
48.
Cab Wall Finish: Unfinished Hardwood Veneer - Oak.
49.
Cab Wall Finish: Finished Hardwood Veneer - Cherry.
50.
Cab Wall Finish: Finished Hardwood Veneer - Maple.
51.
Cab Wall Finish: Finished Hardwood Veneer - Oak.
52.
Cab Wall Finish: Finished Raised Hardwood Veneer - Cherry.
53.
Cab Wall Finish: Finished Raised Hardwood Veneer - Maple.
54.
Cab Wall Finish: Finished Raised Hardwood Veneer - Oak.
 
** NOTE TO SPECIFIER ** Delete cab ceiling not required.
 
55.
Cab Ceiling: White Melamine.
56.
Cab Ceiling: Match cab walls.
57.
Cab Lighting: LED recessed lights.
 
** NOTE TO SPECIFIER ** Freedom Elite: The Freedom Elite is a heavily upgraded version of the Freedom Green. This elevator has a larger capacity, larger cab, and sliding doors.
 
a.
Freedom Elite as manufactured by Nationwide Lifts, Inc.
58.
Construction: Provide as an upgraded version of the Freedom Green elevator as manufactured by Nationwide Lifts, Inc.
 
** NOTE TO SPECIFIER ** Delete wall panels not required.
 
59.
Panels: Unfinished veneer walls. Standard.
60.
Panels: Melamine.
61.
Panels: Raised hardwood.
62.
Panels: Glass walls.
63.
Capacity: 1400 lbs (635 kg).
 
** NOTE TO SPECIFIER ** Delete platform size not required.
 
64.
Platform Size: 48 inches by 54 inches (1219 mm by 1372 mm).
65.
Platform Size: 40 inches by 54 inches (1016 mm by 1372 mm).
66.
Platform Size: Custom sizes available up to 18 sf (1.7 sm).
67.
Travel Speed: 40 feet per minute (12 m/minute).
 
** NOTE TO SPECIFIER ** Visilift(TM) Octagonal: The Visilift(TM) Octagonal glass elevator has an integrated shaft with a very unique shape. The columns of the hoistway also act as the guide rails. The design of this cable-driven elevator allows for 360 degree views with no visible machinery. Standard unit has polycarbonate panels. Upgrade to silica glass panels is available. Fits well with wrap-around stairs, through a hole in floor, or attaching to balcony. Octagonal shape is unlike most any other elevator. Interior cab size of approximately 42 inches x 42 inches will accommodate a wheelchair. Travels up to 5 stops and 50 ft.
 
2.4
OCTAGONAL GLASS CAB ELEVATOR
A.
Visilift 48 Octagonal as manufactured by Visilift(R) and exclusively distributed by Nationwide Lifts, Inc.
B.
General:
1.
General Classification: Residential - Single Family.
2.
Applied Code: ASME A17.1-2007 Section 5.3 NEC 2008.
3.
Walls: Full Clear Acrylic - Complies With ANSI Z97.1.
4.
Number Of Floors: 2 to 5.
5.
Capacity: 744 Lbs. (337 Kg).
6.
Nominal Speed: 32 Fpm (0.1626 M/S).
7.
Cab Floor Area: 11.91 Square Feet (1.11 Sq. Meters).
8.
Cab Interior Height: 84 Inches (2133 Mm).
9.
Cab Weight: 700 Lbs. (318 Kg).
10.
Total Travel: 515.5 Inches (13,094 mm). Optional 600 Inches Maximum (15,240 mm).
11.
Pit Depth: 4 to12 Inches (102 to 305 Mm).
12.
Power Supply: 50/60 Hz Single Phase 230V.
13.
Machine Power: 230 V single phase 30 A fused disconnect.
14.
Lighting: 115 V 15 A.
15.
Safeties: 2 Type A Instantaneous Safeties In Compliance With ASME A17.1 Sections 2.17.8.1 & 2.17.5.1.
C.
Suspension:
1.
Type: Galvanized Aircraft Cable 2 X 3/8 inch (9.5 mm) Diameter.
2.
Construction: IWRC 7 X 19 RHRL.
3.
Nominal Strength: 14,400 Lbs. (6 531 Mm).
4.
Wt. Of Ropes: 0.243 Lbs/Ft (3.616 G/Cm).
5.
Travel Cable Wt.: 0.228 Lbs/Ft (3.393 G/Cm).
D.
Drivetrain:
1.
Type: Winding Drum.
2.
Motor: 1.5 HP With Integrated Brake.
3.
Transmission: Ultra-Low Vibration 3-Stage Right Angle Helical-Bevel Drive.
4.
Motor Control: Pre-Programmed Variable Frequency Drive.
5.
Door Interlocks: Honeywell Rdi-G-L5b Certified In Compliance With ASME A17.1 Section 2.12.4.3.
6.
Pit/Floor Load: (Ft Of Hoistway * 38) + (# Of Floors * 60) + 2193 Dead Load (Lbs); 3703 Lbs Impact Load (M Of Hoistway * 57) + (# Of Floors * 27.22) + 995 Dead Load (Kg); 1680 Kg Impact Load.
 
** NOTE TO SPECIFIER ** Visilift(TM) Round: The Visilift(TM) Round glass elevator is a round glass elevator with 360 degree views. This cable-driven elevator will accommodate a wheelchair, but does not meet ADA size requirements. This can be used as a residential elevator or a commercial wheelchair lift.
 
7.
This comes standard with polycarbonate panels. Silica glass panels are not available in this size. Fits well with wrap-around stairs, through floor, or attaching to balcony. The smooth, quiet drive system works well in high-end homes. Interior size of approximately 51 inches diameter. Travels up to 5 stops and 50 ft.
2.5
ROUND GLASS CAB ELEVATOR
A.
Visilift 58 Round as manufactured by Visilift(R) and exclusively distributed by Nationwide Lifts, Inc.
B.
General:
1.
General Classification: Residential - Single Family.
2.
Applied Code: ASME A17.1-2007 Section 5.3 NEC 2008.
3.
Walls: Full Clear Acrylic - Complies With ANSI Z97.1.
4.
Number Of Floors: 2 to 5.
5.
Capacity: 839 Lbs. (381 Kg).
6.
Nominal Speed: 32 Fpm (0.1626 M/S).
7.
Cab Floor Area: 13.41 Square Feet (1.25 Sq. Meters).
8.
Cab Interior Height: 84 Inches (2133 Mm).
9.
Cab Weight: 700 Lbs. (318 Kg).
10.
Total Travel: 515.5 Inches (13,094 Mm).
11.
Pit Depth (Option): 4 to12 Inches (102 to 305 Mm).
12.
Power Supply: 50/60 Hz Single Phase 230V.
13.
Machine Power: 230 V single phase 30 A fused disconnect.
14.
Lighting: 115 V 15 A.
15.
Safeties: 2 Type A Instantaneous Safeties In Compliance With ASME A17.1 Sections 2.17.8.1 & 2.17.5.1.
C.
Suspension:
1.
Type: Galvanized Aircraft Cable 2 X 3/8 inch (9.5 mm) Diameter.
2.
Construction: IWRC 7 X 19 RHRL.
3.
Nominal Strength: 14,400 Lbs. (6 531 mm).
4.
Wt. Of Ropes: 0.243 Lbs/Ft (3.616 G/Cm).
5.
Travel Cable Wt.: 0.228 Lbs/Ft (3.393 G/Cm).
D.
Drivetrain:
1.
Type: Winding Drum.
2.
Motor: 1.5 HP With Integrated Brake.
3.
Transmission: Ultra-Low Vibration 3-Stage Right Angle Helical-Bevel Drive.
4.
Motor Control: Pre-Programmed Variable Frequency Drive.
5.
Door Interlocks: Honeywell RDI-G-L5B Certified In Compliance With ASME A17.1 Section 2.12.4.3.
6.
Pit/Floor Load: (Ft Of Hoistway * 38) + (# Of Floors * 60) + 2193 Dead Load (Lbs); 3703 Lbs Impact Load (M Of Hoistway * 57) + (# Of Floors * 27.22) + 995 Dead Load (Kg); 1680 Kg Impact Load.
 
** NOTE TO SPECIFIER ** Freedom Commercial: The LULA is an ideal elevator for adding accessibility to churches, small office buildings, and other public buildings up to 3 levels. It is smaller is size than the Commercial Passenger Elevators, and much easier to integrate into a building. Meets ADA requirements, but will not accommodate a gurney. Must be approved by local authorities.
 
2.6
LIMITED-USE, LIMITED-ACCESS (LULA) ELEVATORS
A.
Freedom Commercial LULA Elevator as manufactured by Nationwide Lifts, Inc.
 
** NOTE TO SPECIFIER ** Insert number of levels served required.
 
1.
Number of Levels Serviced: ____ levels.
2.
Travel Speed: 30 feet per minute (9 m/minute).
3.
Travels Distance: Up to 25 feet (7620 mm).
4.
Drive System:
a.
Roped Hydraulic (hole-less).
b.
Submersible pump unit.
5.
Safety Features:
a.
Overspeed valve.
b.
Safety brake system.
c.
Emergency alarm and stop switch.
d.
Final limit switches.
e.
Gate switch.
f.
Landing door interlocks.
 
** NOTE TO SPECIFIER ** Delete power requirement not required.
 
6.
Elevator Power Requirements: 208V, 3 Phase, 30A service to fused, lockable disconnect with auxiliary contact.
7.
Elevator Power Requirements: 240V, 1 Phase, 40A service to fused, lockable disconnect with auxiliary contact.
8.
Lighting Power Requirements: 120V, 20A service to a fused, lockable disconnect (for lighting circuit).
9.
Communication Requirements; Dedicated phone line.
10.
Controls:
a.
Fully automatic push button in cab and at landings.
b.
Automatic car lighting.
c.
Position indicator in cab.
d.
Microprocessor based controller.
11.
Capacity: 1400 lbs (635 kg).
 
** NOTE TO SPECIFIER ** Delete car size not required.
 
12.
Car Size. 48 inches by 54 inches (1219 mm by 1371 mm).
13.
Car Size. 42 inches by 60 inches (1067 mm by 1524 mm).
 
** NOTE TO SPECIFIER ** Delete platform configuration not required.
 
14.
Platform Configuration: Enter/exit same side.
15.
Platform Configuration: Enter/exit opposite sides (front and rear).
 
** NOTE TO SPECIFIER ** Delete cab fixture finish not required.
 
16.
Cab Fixtures Finish: Stainless Steel. -
17.
Cab Fixtures Finish: Oil Rubbed Bronze.
18.
Cab Fixtures Finish: Brass.
19.
Cab Gate(s): Sliding 2-speed gate.
 
** NOTE TO SPECIFIER ** Delete cab gate finish not required.
 
20.
Cab Gate Finish: Primed for paint.
21.
Cab Gate Finish: Powder Coated Black.
22.
Cab Gate Finish: Powder Coated White.
23.
Cab Gate Finish: Stainless Steel.
24.
Landing Doors: Sliding 2-speed doors.
 
** NOTE TO SPECIFIER ** Delete landing door finish not required.
 
25.
Landing Door Finish: Primed for paint.
26.
Landing Door Finish: Stainless Steel.
 
** NOTE TO SPECIFIER ** Delete cab wall finish not required.
 
27.
Cab Wall Finish: Powder Coated White.
28.
Cab Wall Finish: Powder Coated Black.
29.
Cab Wall Finish: Stainless Steel.
 
** NOTE TO SPECIFIER ** Delete cab wall laminate not required.
 
30.
Cab Wall Laminate Panels: Folkstone.
31.
Cab Wall Laminate Panels: Gray.
32.
Cab Wall Laminate Panels: Mahogany.
33.
Cab Wall Laminate Panels: Oak.
34.
Cab Wall Laminate Panels: None.
 
** NOTE TO SPECIFIER ** Delete cab ceiling not required.
 
35.
Cab Ceiling: White Melamine.
36.
Cab Ceiling: Match cab walls.
37.
Cab Lighting: LED recessed lights.
PART 3 EXECUTION
 
3.1
EXAMINATION
A.
Do not begin installation until substrates have been properly prepared.
B.
Hoistway shall be constructed in accordance with ASME A17.1 - Safety Code for Elevators and Escalators. Comply with State and Local codes.
C.
Hoistway shall be plumb and square within tolerance of manufacturer's requirements.
D.
Hoistway shall provide attachment and support of equipment inside hoistway.
E.
If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
3.2
PREPARATION
A.
Clean surfaces thoroughly prior to installation.
B.
Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
3.3
INSTALLATION
A.
Install in accordance with manufacturer's instructions.
B.
Hoistway doors shall comply with local fire and building code for fire rated openings.
1.
Fire rated doors shall be automatically released in a fire event.
3.4
DUMBWAITER INSTALLATION
A.
Dumbwaiter shall be installed prior to closing the hoistway at the lowest landing.
B.
Dumbwaiter shall be installed in existing hoistway through door rough openings.
3.5
FIELD QUALITY CONTROL
A.
Perform tests of elevator as required by ANSI/ASME A17.1 and governing codes.
3.6
ADJUSTING
A.
Adjust elevators for proper operation in accordance with manufacturer/installer's instructions.
B.
Adjust elevators for smooth acceleration and deceleration of car so not to cause passenger discomfort.
C.
Adjust doors to prevent opening of doors at landing on corridor side, unless car is at rest at that landing, or is in leveling zone and stopping at that landing.
D.
Adjust automatic floor leveling feature at each floor to within 1/4 inch (6 mm) of landing.
E.
Repair minor damages to finish in accordance with manufacturer/installer's instructions and as approved by Architect.
F.
Remove and replace damaged components that cannot be successfully repaired as determined by Architect.
3.7
CLEANING AND PROTECTION
A.
Clean in accordance with manufacturer's recommendations. Clean elevators promptly after installation in accordance with manufacturer/installer's instructions. Do not use cleaning materials or methods that could damage finish.
B.
Protect installed elevators from damage during construction in accordance with the negotiated temporary use agreement between Owner and manufacturer's installer. Protect installed products until completion of project.
C.
Touch-up, repair or replace damaged products and finishes in accordance with manufacturer's instructions before Substantial Completion.
END OF SECTION