Download SECTION 23 82 00 BASEBOARD HEATING UNITS for
WORD | RTF | Text | Word Perfect
Find over 500 more CSI Sections
on Arcat.com
Switch to Masterformat 95
 
SECTION 23 82 00
BASEBOARD HEATING UNITS
 
 
Copyright 2016 - 2016 ARCAT, Inc. - All rights reserved
** NOTE TO SPECIFIER ** Slant/Fin Corp.; boilers and baseboard heating equipment.
This section is based on the products of Slant/Fin Corp., which is located at:
100 Forest Dr.
Greenvale, NY 11548
Tel: 516-484-2600
Fax: 516-484-5921
Email: request info (marketing@slantfin.com)
Web: www.slantfin.com
[ Click Here ] for additional information.
Since 1949: Slant/Fin is America's largest manufacturer of baseboard heating equipment. We are a family owned business whose culture is built around customer service and building of trust and relationships. We are one of the top manufacturers of gas and oil fired hot water and steam boilers with manufacturing facilities in Greenvale, NY, Glen Cove, NY and Mississauga, Canada. Our service areas include all North America as well as some parts of South America and China and Europe.
 
PART 1 GENERAL
 
1.1
SECTION INCLUDES
A.
Baseboard enclosures and finned heating elements.
B.
Finned tube heating elements.
1.2
RELATED SECTIONS
 
** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
A.
Section 23 05 00 - Common Work Results for HVAC.
B.
Section 23 52 23 - Cast-Iron Boilers.
C.
Section 26 05 00 - Common Work Results for Electrical.
1.3
REFERENCES
 
** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
 
A.
Hydronics Institute Division; Air-Conditioning, Heating and Refrigeration Institute (AHRI):
1.
I=B=R Testing and Rating Standard for Finned-Tube (Commercial) Radiation.
1.4
SUBMITTALS
A.
Submit under provisions of Section 01 30 00 - Administrative Requirements.
B.
Product Data: Manufacturer's data sheets on each product to be used, including:
1.
Preparation instructions and recommendations.
2.
Storage and handling requirements and recommendations.
3.
Installation methods.
C.
Shop Drawings: Include system components, utility requirements and connections, relationship with adjacent construction. Include required clearances and access for servicing.
1.5
QUALITY ASSURANCE
A.
Manufacturer Qualifications: Minimum 5 years experience manufacturing similar equipment.
B.
Installer Qualifications: Minimum 2 years experience installing similar equipment.
C.
Performance Ratings: In accordance with the Hydronics Institute's "I=B=R Testing and Rating Standard for Finned-Tube (Commercial) Radiation."
1.6
DELIVERY, STORAGE, AND HANDLING
A.
Store products in manufacturer's unopened packaging until ready for installation.
1.7
PROJECT CONDITIONS
A.
Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.
1.8
WARRANTY
A.
Manufacture's standard limited warranty.
PART 2 PRODUCTS
 
2.1
MANUFACTURERS
 
** NOTE TO SPECIFIER ** First paragraph is Slant/Fin's USA address. The second paragraph is their Canadian address. Delete the paragraph not required.
 
A.
Acceptable Manufacturer: Slant/Fin Corp., which is located at: 100 Forest Dr.; Greenvale, NY 11548; Tel: 516-484-2600; Fax: 516-484-5921; Email: request info (marketing@slantfin.com); Web: www.slantfin.com
B.
Acceptable Manufacturer: Slant/Fin Corp., which is located at: 100 Forest Dr.; Greenvale, NY 11548; Tel: 516-484-2600; Fax: 516-484-5921; Email: request info (marketing@slantfin.com); Web: www.slantfin.com
 
** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
C.
Substitutions: Not permitted.
D.
Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.
 
** NOTE TO SPECIFIER ** This specification covers the major features, attributes and most common options for baseboard heaters including but not limted to mounting and support brackets. For a complete list of optional features and attributes available for each model, please contact a qualified manufacturer's representative or refer to the company's website for more information. Delete baseboard enclosure article if not required.
 
2.2
BASEBOARD ENCLOSURES AND FINNED HEATING ELEMENTS
 
** NOTE TO SPECIFIER ** Delete F and EM series if not required.
 
A.
Basis of Design: F and EM Series as manufactured by Slant/Fin Corporation Louvered and expanded metal, one-piece element covers attaching directly to heating elements.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model F-5 single-tier heating element. 4-3/4 inch (95 mm) height.
2.
Model F-12 two-tier heating element. 11-3/4 inch (298 mm) height.
3.
Model F-19 three-tier heating element. 18-3/4 inch (476 mm) height.
4.
Model EM-5 single-tier heating element. 4-3/4 inch (95 mm) height.
5.
Model EM-12 two-tier heating element. 11-3/4 inch (298 mm) height.
6.
Model EM-19 three-tier heating element. 18-3/4 inch (476 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
7.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
8.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: S-832.
a.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
10.
Heating Element: C-340.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
11.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
12.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
13.
F Series Material: 18 gauge (1.214 mm) steel cover.
14.
EM Series Material: 16 gauge (1.519 mm) steel cover.
 
** NOTE TO SPECIFIER ** Galvanized is the standard finish. Delete finish not required.
 
15.
Finish: Galvanized.
16.
Finish: Baked enamel. Color as determined by the Architect.
17.
Finish: Baked enamel. Color: ______.
18.
Depth: 4-3/8 inch (111 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 ft (610 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm). Other 1/2 ft (152 mm) increments are available
 
19.
Length (ft / mm): ______.
20.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, inside and outside corners.
21.
Wall Brackets: Follow manufacturer's recommended wall bracket spacing.
a.
One Tier: Bracket No. M1.
b.
Two Tier: Bracket No. M2,
1)
2 SC element hangers.
c.
Three Tier: Bracket No. M3.
1)
3 SC element hangers.
22.
SC. Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm) vertical pitch adjustment.
 
** NOTE TO SPECIFIER ** Delete J series if not required.
 
B.
Basis of Design: J Series as manufactured by Slant/Fin Corporation. Sloped top, one-piece cover, fin-tube enclosures.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model JL-10 one tier element. 9-7/8 inch (251 mm) height.
2.
Model JA-14 one-tier element. 14 inch (356 mm) height.
3.
Model JA-21 one-tier element. 21 inch (533 mm) height.
4.
Model JA-21 two-tier element. 21 inch (533 mm) height.
5.
Model JA-28 one-tier element. 28 inch (711 mm) height.
6.
Model JA-28 two-tier element. 28 inch (711 mm) height.
7.
Model JA-28 three-tier element. 28 inch (711 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
8.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
10.
Heating Element: S-832.
a.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (105 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
11.
Heating Element: C-340.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
12.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
13.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
 
** NOTE TO SPECIFIER ** 18 gauge is standard. Delete materials not required.
 
14.
Material: 18 gauge (1.214 mm) steel cover.
15.
Material: 16 gauge (1.519 mm) steel cover.
16.
Material: 14 gauge (1.897 mm) steel cover.
 
** NOTE TO SPECIFIER ** Galvanized is the standard finish. Delete finish not required.
 
17.
Finish: Galvanized.
18.
Finish: Baked enamel. Color as determined by the Architect.
19.
Finish: Baked enamel. Color: ______.
20.
Depth: 5-1/4 inch (133 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 ft (610 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm). Other 1/2 ft (152 mm) increments are available
 
21.
Length (ft / mm): ______.
 
** NOTE TO SPECIFIER ** Internal splice plates are available for JA models only. They are not applicable to JL-10 model. Delete if not required.
 
22.
Internal Splice Plates.
 
** NOTE TO SPECIFIER ** Telescopic joints work with all J series models. Delete if not required.
 
23.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, inside and outside corners.
24.
Wall Brackets: 14 gauge (1.897 mm) drawn die formed steel, securing cover in place with rigid spring lock action. Snap-in center brace supports middle of cover.Follow manufacturer recommendation for spacing between wall brackets.
25.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm) vertical pitch adjustment.
 
** NOTE TO SPECIFIER ** Delete accessories not required.
 
26.
Optional Accessories:
1)
Back Panel: 20 gauge galvanized steel.
2)
Anodized aluminum grilles.
3)
Column covers.
 
** NOTE TO SPECIFIER ** Not available with aluminum grilles.
 
4)
Fully modulating dampers. Knob actuated.
5)
Hanging strips.
6)
Tamper proof lock.
7)
Wall gasketing.
 
** NOTE TO SPECIFIER ** Delete R series if not required.
 
C.
Basis of Design: R Series flat top enclosure as manufactured by Slant/Fin Corporation. One piece cover, fin-tube enclosures.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model RL-10 one-tier element. 9-7/8 inch (251 mm) height.
2.
Model RT-14 one-tier element. 14 inch (356 mm) height.
3.
Model RT-21 one-tier element. 21 inch (533 mm) height.
4.
Model RT 21 two-tier element. 21 inch (533 mm) height.
5.
Model RT-28 one-tier element. 28 inch (711 mm) height.
6.
Model RT-28 two-tier element.28 inch (711 mm) height.
7.
Model RT-28 three-tier element. 28 inch (711 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
8.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
10.
Heating Element: S-832.
a.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
11.
Heating Element: C-340.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
12.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
13.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
 
** NOTE TO SPECIFIER ** 18 gauge is standard. Delete materials not required.
 
14.
Material: 18 gauge (1.214 mm) steel cover.
15.
Material: 16 gauge (1.519 mm) steel cover.
16.
Material: 14 gauge (1.897 mm) steel cover.
 
** NOTE TO SPECIFIER ** Galvanized is the standard finish. Delete finish not required.
 
17.
Finish: Galvanized.
18.
Finish: Baked enamel. Color: As determined by the Architect.
19.
Finish: Baked enamel. Color: ______.
 
** NOTE TO SPECIFIER ** Delete louver location not required.
 
20.
Louver Location: Top.
 
** NOTE TO SPECIFIER ** Not available on model RL-10.
 
21.
Louver Location: Front.
22.
Depth: 5-1/4 inch (133 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 ft (610 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm). Other 1/2 ft (152 mm) increments are available
 
23.
Length (ft / mm): ______.
24.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
25.
Slip joint connectors.
26.
Wall Brackets: 14-gauge (1.897 mm) drawn die formed steel, securing cover in place with rigid spring lock action. Snap-in center brace supports middle of cover. Follow manufacturer recommendation for spacing between wall brackets.
27.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm) vertical pitch adjustment.
 
** NOTE TO SPECIFIER ** Delete accessories not required.
 
28.
Optional Accessories:
 
** NOTE TO SPECIFIER ** Aluminum grille not available for front louver orientation.
 
a.
Anodized aluminum grille.
 
** NOTE TO SPECIFIER ** The damper is not available with the aluminum grilles.
 
b.
Damper. Knob actuated.
c.
Back Panel: 20 gauge galvanized steel.
d.
Access door: 6 by 6 in (152 by 152 mm) field installed.
e.
Inlet grille.
 
** NOTE TO SPECIFIER ** Delete TBG series if not required.
 
D.
Basis of Design: TBG Series as manufactured by Slant/Fin Corporation. Sloped top and bottom, one-piece cover, fin-tube enclosures.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model TBG-17 one tier element. 17 inch (432 mm) height.
2.
Model TBG-24 one tier element. 24 inch (607 mm) height.
3.
Model TBG-24 two tier element. 24 inch (607 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
4.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
5.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
6.
Heating Element: S-832.
a.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
7.
Heating Element: C-340.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
8.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
 
** NOTE TO SPECIFIER ** 16 gauge is standard. Delete materials not required.
 
10.
Material: 16 gauge steel cover
11.
Material: 14 gauge steel cover
 
** NOTE TO SPECIFIER ** Galvanized is the standard finish. Delete finish not required.
 
12.
Finish: Galvanized.
13.
Finish: Baked enamel. Color as determined by the Architect.
14.
Finish: Baked enamel. Color: ______.
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 ft (610 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm). Other 1/2 ft (152 mm) increments are available
 
15.
Length (ft / mm): ______.
 
** NOTE TO SPECIFIER ** Delete the telescopic joints or the slip joint connectors below.
 
16.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
17.
Slip joint connectors.
18.
Wall Brackets: 14-gauge (1.897 mm) drawn die formed steel, securing cover in place with rigid spring lock action. Snap-in center brace supports middle of cover.
19.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm)vertical pitch adjustment.
 
** NOTE TO SPECIFIER ** Delete accessories not required.
 
20.
Optional Accessories:
a.
Anodized aluminum grilles.
 
** NOTE TO SPECIFIER ** Not available with aluminum grilles.
 
b.
Dampers:
c.
Access door: Field installed.
 
** NOTE TO SPECIFIER ** Delete Multi/Pak 80 series if not required.
 
E.
Basis of Design: Multi/Pak 80 Series as manufactured by Slant/Fin Corporation. High output, low profile baseboards. Preassembled at factory.
 
** NOTE TO SPECIFIER ** Delete model not required.
 
1.
Model 80-D. 8-7/8 (226 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
a.
Heating Element: H-1.
1)
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
2)
Fins: 3 by 3-1/4 inch (76 by 83 mm), by 0.024 inch (0.61 mm) thick aluminum.
3)
Fins Density: 48 per ft (157.5 per m).
4)
Active Finned Length: Length minus 4 inch (102 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec).
 
6)
Hot Water Temperature (F / C): ______.
7)
Hot Water Rating (Btu per hr per ft / W per m): ______.
b.
Heating Element: H-4.
1)
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
2)
Fins: 3 by 2-1/2 inch (76 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
3)
Fins Density: 48 per ft (157.5 per m).
4)
Active Finned Length: Length minus 4 inch (102 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
13 milliinches per ft (1 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
145 milliinches per fit (12 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
6)
Hot Water Temperature (F / C): ______.
7)
Hot Water Rating (Btu per hour per foot / W per m): ______.
c.
Heating Element: H-5X.
1)
Tube: 1-1/4 inch (31 mm) diameter copper seamless drawn tubing with one expanded end.
2)
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.020 inch (0.51 mm) thick aluminum.
3)
Fin Density: 48 fins per ft (157.5 fins per m).
4)
Active Finned Length: Length minus 4 inch (102 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
6 milliinches per ft (0.5 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
63 milliinches per fit (5 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 desgrees C) entering air temperature. Delete if not required.
 
6)
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
7)
Hot Water Temperature (F / C): ______.
8)
Hot Water Rating (Btu per hr per ft / W per m): ______.
d.
Heating Element: H-6X.
1)
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe with threaded ends.
2)
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.028 inch (0.71 mm) thick aluminized steel.
3)
Fin Density: 48 fins per ft (157.5 fins per m).
4)
Active Finned Length: Length minus 5 inch (127 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
3 milliinches per ft (0.25 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
41 milliinches per fit (3.42 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
6)
Hot Water Temperature (F / C): ______.
7)
Hot Water Rating (Btu per hour per foot / W per m): ______.
2.
Model 83-A2. 8-7/8 inch (226 mm) height.
a.
Heating Element: H-3.
1)
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
2)
Fins: 2-3/4 by 2-1/2 inch (70 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
3)
Fin Density: 55 fins per ft (180 fins per m).
4)
Active Finned Length: Length minus 4 inch (102 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
6)
Hot Water Temperature (F / C): ______.
7)
Hot Water Rating (Btu per hr per ft / W per m): ______.
3.
Material:
a.
Front Cover: 18 gauge (1.214 mm) galvanized steel.
b.
Back cover: 23 gauge (0.777 mm) galvanized steel.
c.
Support Brackets: 17 gauge (1.367 mm) steel.
1)
Spacing between brackets not to exceed 24 in (610 mm).
4.
Finish: Baked enamel. Color: Nu-white.
5.
Depth: 3-1/2 in (89 mm).
 
** NOTE TO SPECIFIER ** USA standard lengths are 2 to 14 feet (607 to 4267 mm) in 1 foot (305 mm) increments and 3-1/2 ft (1067 mm). Canada standard lengths are 2 to 8 feet (607 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm).
 
6.
Length (ft / mm): ______.
7.
Element Hangers: Channeled steel.
8.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
9.
Element Support: Self-adjusting, polypropylene expansion cradles positioned over support brackets, allowing quiet expansion.
 
** NOTE TO SPECIFIER ** Delete Multi/Pak 90 series if not required.
 
F.
Basis of Design: Multi/Pak 90 as manufactured by Slant/Fin Corporation. Sloped top, two-piece interlocking top and front cover fin-tube enclosures. Factory packaged and prepainted.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model 90-14 one tier element. 14 inch (356 mm) height.
2.
Model-90-21 one tier element. 21 inch (533 mm) height.
3.
Model 90-21 two tier element. 21 inch (533 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
4.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
5.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
6.
Heating Element: S-832.
a.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
7.
Heating Element: C-340
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
8.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
10.
Material: 18 gauge (1.214 mm) steel top and cover.
 
** NOTE TO SPECIFIER ** Nu-White baked enamel is the standard finish. Delete finishes not required.
 
11.
Finish: Galvanized.
12.
Finish: Baked enamel. Color: Nu-WHite.
13.
Finish: Baked enamel. Color as determined by the Architect.
14.
Finish: Baked enamel. Color: ______.
15.
Depth: 5-1/4 inch (133 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 feet (607 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm).
 
16.
Length (ft / mm): ______.
 
** NOTE TO SPECIFIER ** Delete the telescopic joints or the internal splice plates.
 
17.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
18.
Internal Splice Plates.
19.
Wall Brackets: 14-gauge (1.897 mm) drawn die formed steel, securing cover in place with rigid spring lock action. Snap-in center brace supports middle of cover.
20.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm)vertical pitch adjustment.
 
** NOTE TO SPECIFIER ** Delete accessories not required.
 
21.
Optional Accessories:
a.
Anodized aluminum grille.
 
** NOTE TO SPECIFIER ** Not available with aluminum grille.
 
b.
Damper; field installed.
c.
Hanging strip.
d.
Back Panel: 20 gauge galvanized steel.
e.
Tamper proof lock.
f.
Wall gasketing.
 
** NOTE TO SPECIFIER ** Delete Multi/Pak 93 series if not required.
 
G.
Basis of Design: Multi/Pak 93 as manufactured by Slant/Fin Corporation. Flat top, two-piece fin-tube enclosures. Factory packaged and prepainted.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model 93-10 one tier element. 9-3/4 inch (248 mm) height.
2.
Model-93-17 one tier element. 16-3/4 inch (425 mm) height.
3.
Model 93-17 two tier element. 16-3/4 inch (425 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating element not required.
 
4.
Heating Element: H-1.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm), by 0.024 inch (0.61 mm) thick aluminum.
c.
Fins Density: 48 per ft (157.5 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
5.
Heating Element: H-3.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 2-3/4 by 2-1/2 inch (70 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fin Density: 55 fins per ft (180 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
6.
Heating Element: H-4.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 2-1/2 inch (76 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fins Density: 48 per ft (157.5 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** Based on flow rate of 3 ft per sec. See catalogue information for
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hour per foot / W per m): ______.
7.
Heating Element: H-5X
a.
Tube: 1-1/4 inch (31 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 48 fins per ft (157.5 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 desgrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
8.
Heatind Element: H-6X.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe with threaded ends.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.028 inch (0.71 mm) thick aluminized steel.
c.
Fin Density: 48 fins per ft (157.5 fins per m).
d.
Active Finned Length: Length minus 5 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 desgrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hour per foot / W per m): ______.
9.
Heating Element: E-75.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 2-5/16 by 2-1/8 inch (59 by 54 mm) by 0.009 inch (0.23 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fin Density: 55 fins per ft (180 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
e.
Hot Water Temperature (F / C): ______.
f.
Hot Water Rating (Btu per hr per ft / W per m): ______.
10.
Material:
a.
Cover and top: 18 gauge (1214 mm) galvanized steel.
b.
Wall Brackets: 11 gauge (3.038 mm) galvanized steel.
 
** NOTE TO SPECIFIER ** Nu-White baked enamel is standard. Delete finish not required.
 
11.
Finish: Baked enamel. Color: Nu-White.
12.
Finish: Baked enamel. Color as determined by the Architect.
13.
Finish: Baked enamel. Color: ______.
14.
Depth: 3-1/2 inch (89 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 feet (607 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm).
 
15.
Length (ft / mm): ______.
16.
Element Hangers: Channeled steel.
17.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
18.
Element Support: Self-adjusting, polypropylene expansion cradles positioned over support brackets, allowing quiet expansion.
19.
Optional Accessories:
1)
Column covers.
2)
Damper. Factory installed.
3)
Hanging strip.
4)
Tamper proof lock.
5)
Wall gasketing.
 
** NOTE TO SPECIFIER ** Delete Multi/Pak 95 series if not required.
 
H.
Basis of Design: Multi/Pak 95 as manufactured by Slant/Fin Corporation. Flat top, two-piece interlocking fin-tube enclosures. Factory packaged and prepainted.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model 95-10 one tier element. 9-3/4 inch (248 mm) height.
2.
Model 95-17 one tier element.16-3/4 inch (425 mm) height.
3.
Model 95-17 two tier element. 16-3/4 inch (425 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
4.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
5.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
6.
Heating Element: S-832.
a.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
7.
Heating Element: C-340.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
8.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
10.
Material:
a.
Top and Front Cover: 18 gauge galvanized steel.
b.
Wall Brackets: 11 gauge steel.
 
** NOTE TO SPECIFIER ** Nu-White baked enamel is standard. Delete finish not required.
 
11.
Finish: Baked enamel. Color: Nu-White.
12.
Finish: Baked enamel. Color as determined by the Architect.
13.
Finish: Baked enamel. Color: ______.
14.
Depth: 5-1/4 inch (57 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 ft (610 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm).
 
15.
Length (ft / mm): ______.
16.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
17.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm)vertical pitch adjustment.
 
** NOTE TO SPECIFIER ** Delete accessories not required.
 
18.
Optional Accessories:
a.
Anodized Aluminum grille.
 
** NOTE TO SPECIFIER ** Not available with aluminum grille.
 
b.
Damper.
c.
Hanging strip.
d.
Tamper proof lock.
e.
Wall gasketing.
I.
Basis of Design: HD and LC Series as manufactured by Slant/Fin Corporation. Heavy duty sloped top baseboards.
1.
Model HD-850 one tier element. 8-1/2 inch (216 mm).
2.
Model HD-1400 one tier element. 14 inch (356 mm)
3.
Model HD-1400 two tier element. 14 inch (356 mm).
4.
Model LC-850 one tier element. 8-3/4 inch (222 mm).
5.
Model LC-1400 one tier element. 14-1/4 inch (362 mm).
6.
Model LC-1400 two tier element. 14-1/4 inch (362 mm).
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
7.
Heating Element: H-1.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm), by 0.024 inch (0.61 mm) thick aluminum.
c.
Fins Density: 48 per ft (157.5 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec).
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
8.
Heating Element: H-3.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 2-3/4 by 2-1/2 inch (70 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fin Density: 55 fins per ft (180 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: H-4.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 2-1/2 inch (76 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fins Density: 48 per ft (157.5 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
13 milliinches per ft (1 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
145 milliinches per fit (12 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hour per foot / W per m): ______.
10.
Heating Element: H-5X.
a.
Tube: 1-1/4 inch (31 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 48 fins per ft (157.5 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
6 milliinches per ft (0.5 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
63 milliinches per fit (5 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 desgrees C) entering air temperature. Delete if not required.
 
f.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
g.
Hot Water Temperature (F / C): ______.
h.
Hot Water Rating (Btu per hr per ft / W per m): ______.
11.
Heating Element: H-6X
a.
Tube: 1-1/4 inch (.DN 32) schedule 40 steel pipe with threaded ends.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.028 inch (0.71 mm) thick aluminized steel.
c.
Fin Density: 48 fins per ft (157.5 fins per m).
d.
Active Finned Length: Length minus 5 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
3 milliinches per ft (0.25 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
41 milliinches per fit (34.17 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hour per foot / W per m): ______.
12.
Material:
 
**NOTE TO SPECIFIER ** HD series units have 16 gauge front covers. LC series units have 18 gauge front covers. Delete the front cover not required.
 
a.
Front Cover: 16 gauge galvanized steel.
b.
Front Cover: 18 gauge galvanized steel.
 
** NOTE TO SPECIFIER ** LC series units do not have a back panel. Delete if not required.
 
c.
Back Panel: 20 gauge steel.
 
** NOTE TO SPECIFIER ** HD series wall bracket spacing. Delete if not required.
 
d.
Wall Brackets: Spaced every 12 in (305 mm).
 
** NOTE TO SPECIFIER ** LC series wall bracket spacing. Delete if not required.
 
e.
Wall Brackets: Recommended spacing no greater than 24 in (610 mm).
 
** NOTE TO SPECIFIER ** Galvanized is standard. Delete finish not required.
 
13.
Finish: Galvanized
14.
Finish: Baked enamel. Color: As determined by the Architect.
15.
Finish: Baked enamel. Color: ______.
16.
Depth: 3-1/2 in (89 mm)
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 feet (607 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm). Other half-foot (152 mm) increments are also available.
 
17.
Length (ft / mm): ______.
18.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
 
** NOTE TO SPECIFIER ** HD series element hangers. Delete if not required.
 
19.
Element Hangers: Welded to back panel every 12 in (305 mm)
 
** NOTE TO SPECIFIER ** LC series element hangers. Delete if not required.
 
20.
Element Hangers: Recommended spacing no greater than 24 in (610 mm).
 
** NOTE TO SPECIFIER ** The damper does not apply to the LC model series and is optional for the HD series. Delete if not required.
 
21.
Damper.
 
** NOTE TO SPECIFIER ** Delete 350 series if not required.
 
J.
Basis of Design: 350 Series as manufactured by Slant/Fin Corporation. High output, sloped top baseboards. Factory packaged and prepainted.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model 351-10 one tier element. 9-7/8 inch (98 mm) height.
2.
Model 353-10 one tier element. 9-7/8 inch (98 mm) height.
3.
Model 354-10 one tier element. 9-7/8 inch (98 mm) height.
4.
Model 355-10 one tier element. 9-7/8 inch (98 mm) height.
5.
Model 356-10 one tier element. 9-7/8 inch (98 mm) height.
6.
Model 350-14 one tier element. 9-7/8 inch (98 mm) height.
7.
Model 353-14 one tier element. 9-7/8 inch (98 mm) height.
8.
Model 354-14 one tier element. 9-7/8 inch (98 mm) height.
9.
Model 355-14 one tier element. 9-7/8 inch (98 mm) height.
10.
Model 356-14 one tier element. 9-7/8 inch (98 mm) height.
11.
Model 351-14 two tier element. 13-7/8 inch (352 mm) height.
12.
Model 353-14 two tier element. 13-7/8 inch (352 mm) height.
13.
Model 354-14 two tier element. 13-7/8 inch (352 mm) height.
14.
Model 355-14 two tier element. 13-7/8 inch (352 mm) height.
15.
Model 356-14 two tier element. 13-7/8 inch (352 mm) height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
16.
Heating Element: H-1.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm), by 0.024 inch (0.61 mm) thick aluminum.
c.
Fins Density: 48 per ft (157.5 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec).
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
17.
Heating Element: H-3.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 2-3/4 by 2-1/2 inch (70 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum.
c.
Fin Density: 55 fins per ft (180 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
18.
Heating Element: H-4
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 2-1/2 inch (76 by 64 mm) by 0.011 inch (0.28 mm) thick aluminum.
c.
Fins Density: 48 per ft (157.5 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
13 milliinches per ft (1 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
145 milliinches per fit (12 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hour per foot / W per m): ______.
19.
Heating Element: H-5X
a.
Tube: 1-1/4 inch (31 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 48 fins per ft (157.5 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
6 milliinches per ft (0.5 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
63 milliinches per fit (5 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 desgrees C) entering air temperature. Delete if not required.
 
f.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
g.
Hot Water Temperature (F / C): ______.
h.
Hot Water Rating (Btu per hr per ft / W per m): ______.
20.
Heating Element: H-6X
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe with threaded ends.
b.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.028 inch (0.71 mm) thick aluminized steel. Double bent fine with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fin Density: 48 fins per ft (157.5 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
3 milliinches per ft (0.25 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
41 milliinches per fit (34.17 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hour per foot / W per m): ______.
21.
Material:
 
** NOTE TO SPECIFIER ** The 19 gauge front cover is standard. Delete the front cover not required.
 
a.
Front Cover: 19 gauge (1.062 mm) steel.
b.
Front Cover: 16 gauge (1.519 mm) steel.
c.
Front Cover: 16 gauge (1.519 mm) galvanized steel.
d.
Back cover: 24 gauge (0.607 mm) steel.
e.
Support Brackets: 17 gauge (1.367 mm) steel.
1)
Spacing between brackets not to exceed 24 in (610 mm).
 
** NOTE TO SPECIFIER ** Nu-White baked enamel is standard for the 19 gauge front cover. Galvanized is optional for 16 gauge cover. Other colors available upon request. Delete finishes not required.
 
22.
Finished: Galvanized.
23.
Finish: Baked enamel. Color: Nu-White.
24.
Finish: Baked enamel. Color as determined by the Architect.
25.
Finish: Baked enamel. Color: ______.
26.
Depth: 3-1/2 inch (89 mm)
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 ft (610 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm).
 
27.
Length (ft / mm): ______.
28.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
 
** NOTE TO SPECIFIER ** Optional. Delete if not required.
 
29.
Damper: Fully modulating.
30.
Element Support: Self-adjusting, polypropylene expansion cradles positioned over support brackets, allowing quiet expansion.
 
** NOTE TO SPECIFIER ** Delete FS series if not required.
 
K.
Basis of Design: FS Series as manufactured by Slant/Fin Corporation. Free standing pedestal mounted, fin-tube enclosures.
 
** NOTE TO SPECIFIER ** Delete models not required.
 
1.
Model FS-7 one tier element. 11 inch (279 mm) installed height
2.
Model FS-14 one tier element. 18 inch (457 mm) installed height.
3.
Model FS-14 two-tier element. 18 inch (457 mm) installed height.
4.
Model FS-21 one tier element. 21 inch (610 mm) installed height.
5.
Model FS-21 two-tier element. 21 inch (610 mm) installed height.
6.
Model FS-21 three tier element. 21 inch (610 mm) installed height.
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
7.
Heating Element: S-532.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 32 fins per ft (105 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
8.
Heating Element: S-540.
a.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe factory threaded at both ends.
b.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
9.
Heating Element: C-340
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
10.
Heating Element: C-440.
a.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum. Double bent fins with edges of each fin wedged against the next. End fins are of plated steel for extra ruggedness.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
11.
Heating Element: C-540.
a.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
c.
Fin Density: 40 fins per ft (131 fins per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
e.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per foot / W per m): ______.
 
** NOITE TO SPECIFIER** 16 gauge is standard. Delete material not required.
 
12.
Material: 16 gauge (1.519 mm) steel.
13.
Material: 14 gauge (1.897 mm) steel.
 
** NOTE TO SPECIFIER ** Galvanized finish is standard. Delete finish not required.
 
14.
Finish: Galvanized.
15.
Finish: Baked enamel. Color as determined by the Architect.
16.
Finish: Baked enamel. Color: ______.
17.
Depth: 5-1/2 in (140 mm).
 
** NOTE TO SPECIFIER ** Standard lengths are 2 to 8 feet (607 to 2438 mm) in 1 ft (305 mm) increments and 3-1/2 ft (1067 mm).
 
18.
Length (ft / mm): ______.
19.
Pedestals: Adjustable height with stainless steel escutcheon at the floor supporting the heating element and enclosure.
 
** NOTE TO SPECIFIER ** Delete Element Hangers or slip joint connectors.
 
20.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm)vertical pitch adjustment
21.
Slip joint connectors.
22.
Telescopic Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
 
** NOTE TO SPECIFIER ** Delete accessories not required.
 
23.
Optional Accessories:
a.
Anodized Aluminum grille
b.
Access door; field installed.
 
** NOTE TO SPECIFIER ** Delete Base/Line 2000 series if not required. Both covers and heating elements can be purchased separately.
 
L.
Basis of Design: Base/Line 2000 series as manufactured by Slant/Fin Corporation. High output, low profile baseboards. Preassembled at factory. Accomodates return tubing above heating element using standard fittings.
 
** NOTE TO SPECIFIER ** Delete model not required.
 
1.
Model BL-75. 7-23/64 in (187 mm) height.
a.
Heating Element: E-75E.
1)
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
2)
Fins: 2-5/8 by 2-1/8 inch (67 by 54 mm), by 0.009 inch (0.23 mm) thick aluminum. Fins are double bent. End fins are of plated steel for extra ruggedness.
3)
Fins Density: 56.35 per ft (184.87 per m).
4)
Active Finned Length: Length minus 4 inch (102 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on1 and 4 gpm (3.8 and 15.1 lpm).
 
6)
Hot Water Temperature (F / C): ______.
7)
Hot Water Rating (Btu per hr per ft / W per m): ______.
2.
Model BL-50. 7-23/64 in (187 mm) height.
a.
Heating Element: E-50.
1)
Tube: 1/2 inch (13 mm) diameter copper seamless drawn tubing with one expanded end.
2)
Fins: 2-5/8 by 2-1/8 inch (67 by 54 mm), by 0.009 inch (0.23 mm) thick aluminum. Fins are double bent. End fins are of plated steel for extra ruggedness.
3)
Fins Density: 56.35 per ft (184.87 per m).
4)
Active Finned Length: Length minus 4 inch (102 mm).
5)
Pressure Drop: Rated at 140 degrees F (60 degrees C).
a)
260 milliinches per ft (22 mm per m) based on flow rate of 1 gpm (3.78 lpm).
b)
2880 milliinches per fit (240 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on 1 and 4 gpm (3.8 and 15.1 lpm).
 
6)
Hot Water Temperature (F / C): ______.
7)
Hot Water Rating (Btu per hr per ft / W per m): ______.
3.
Material:
a.
Front Cover: 23 gauge (0.777 mm) galvanized steel.
b.
Back Panel: 26 gauge (0.551 mm) galvanized steel.
c.
Damper: Fully modulating, pivot mounted, setting retention.
d.
Support Brackets: 19 gauge (1.062 mm) steel.
1)
Spacing between brackets not to exceed 24 in (610 mm).
4.
Finish: Baked enamel. Color: Nu-White.
5.
Depth: 2-45/64 in (69 mm).
 
** NOTE TO SPECIFIER ** USA standard lengths are 2 to 10 feet (607 to 3048 mm) in 1 foot (305 mm) increments.
 
6.
Length (ft / mm): ______.
7.
Element Hangers: Built into support brackets.
8.
Element Support: Self-adjusting, polypropylene expansion cradles positioned over support brackets, allowing quiet expansion.
9.
Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
 
** NOTE TO SPECIFIER ** Delete Fine/Line 30 series if not required. Both covers and heating elements can be purchased separately.
 
M.
Basis of Design: Fine/Line 30 series as manufactured by Slant/Fin Corporation. High output, low profile baseboards. Preassembled at factory. Accomodates return tubing above heating element using standard fittings.
 
** NOTE TO SPECIFIER ** Delete model not required.
 
1.
Model 30-75. 7-7/8 in (200 mm) height.
2.
Heating Element: E-75E.
a.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
b.
Fins: 2-5/8 by 2-1/8 inch (67 by 54 mm), by 0.009 inch (0.23 mm) thick aluminum. Fins are double bent. End fins are of plated steel for extra ruggedness.
c.
Fins Density: 56.35 per ft (184.87 per m).
d.
Active Finned Length: Length minus 4 inch (102 mm).
e.
Pressure Drop: Rated at 140 degrees F (60 degrees C).
1)
47 milliinches per ft (4 mm per m) based on flow rate of 1 gpm (3.78 lpm).
2)
525 milliinches per fit (44 mm per m) based on flow rate of 4 gpm (15.14 lpm).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on 1 and 4 gpm (3.8 and 15.1 lpm).
 
f.
Hot Water Temperature (F / C): ______.
g.
Hot Water Rating (Btu per hr per ft / W per m): ______.
3.
Material:
a.
Front Cover: 20 gauge (1.006 mm) galvanized steel.
b.
Back Panel: 24 gauge (0.701 mm) galvanized steel.
c.
Damper: Fully modulating, pivot mounted, setting retention.
d.
Support Brackets: 17 gauge (1.367 mm) steel.
1)
Spacing between brackets not to exceed 24 in (610 mm).
4.
Finish: Galvanized steel with baked enamel. Color: Nu-White.
5.
Depth: 2-11/16 in (68 mm).
 
** NOTE TO SPECIFIER ** USA standard lengths are 2 to 10 feet (607 to 3048 mm) in 1 foot (305 mm) increments.
 
6.
Length (ft / mm): ______.
7.
Element Hangers: Built into support brackets.
8.
Element Support: Self-adjusting, polypropylene expansion cradles positioned over support brackets, allowing quiet expansion.
9.
Joint Accessories: End caps, filler sleeves, splice plates, valve covers, inside and outside corners.
 
** NOTE TO SPECIFIER ** This specification covers the major features, attributes and most common options for finned tube heating elements including but not limted to mounting and support brackets. For a complete list of optional features and attributes available for each model, please contact a qualified manufacturer's representative or refer to the company's website for more information. Delete heating elements article if not required.
 
2.3
FINNED TUBE HEATING ELEMENTS
 
** NOTE TO SPECIFIER ** Delete heating elements not required.
 
A.
Basis of Design: Model S-532 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 1-1/4 (DN 32) schedule 40 steel pipe factory threaded at both ends.
2.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
3.
Fin Density: 32 fins per ft (105 fins per m).
4.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 4-7/8 inch (124 mm) height.
6.
Number of Tiers: 11-7/8 inch (302 mm) height.
7.
Number of Tiers: 18-7/8 inch (479 mm).
8.
Pressure Drop: 420 millinches per ft (35 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per ft / W per m): ______.
B.
Basis of Design: Model S-540 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 1-1/4 (DN 32) schedule 40 steel pipe factory threaded at both ends.
2.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
3.
Fin Density: 40 fins per ft (131 fins per m).
4.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 4-7/8 inch (124 mm) height.
6.
Number of Tiers: 11-7/8 inch (302 mm) height.
7.
Number of Tiers: 18-7/8 inch (479 mm).
8.
Pressure Drop: 420 millinches per ft (35 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per ft / W per m): ______.
C.
Basis of Design: Model S-832 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 2 inch (DN 50) schedule 40 steel pipe factory threaded at both ends.
2.
Fin: 4-1/4 inch (108 mm) square by 0.024 (0.61 mm) thick electro-galvanized steel with interlocking tongue-and-groove locking collar.
3.
Fin Density: 32 fins per ft (105 fins per m).
4.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 4-7/8 inch (124 mm) height.
6.
Number of Tiers: 11-7/8 inch (302 mm) height.
7.
Number of Tiers: 18-7/8 inch (479 mm).
8.
Pressure Drop: 252 millinches per ft (21 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per ft / W per m): ______.
D.
Basis of Design: Model C-340 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
2.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
3.
Fin Density: 40 fins per ft (131 fins per m).
4.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 4-7/8 inch (124 mm) height.
6.
Number of Tiers: 11-7/8 inch (302 mm) height.
7.
Number of Tiers: 18-7/8 inch (479 mm).
8.
Pressure Drop: 708 millinches per ft (59 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per foot / W per m): ______.
E.
Basis of Design: Model C-440 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 1 inch (25 mm) diameter copper seamless drawn tubing with one expanded end.
2.
Fin: 4-1/4 inch (108 mm) square by 0.020 (0.51 mm) thick aluminum.
3.
Fin Density: 40 fins per ft (131 fins per m).
4.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 4-7/8 inch (124 mm) height.
6.
Number of Tiers: 11-7/8 inch (302 mm) height.
7.
Number of Tiers: 18-7/8 inch (479 mm).
8.
Pressure Drop: 504 millinches per ft (42 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per ft / W per m): ______.
F.
Basis of Design: Model C-540 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 1-1/4 inch (32 mm) diameter copper seamless drawn tubing with one expanded end.
2.
Fins: 4-1/4 inch (108 mm) square by 0.020 inch (0.51 mm) thick aluminum.
3.
Fin Density: 40 fins per ft (131 fins per m).
4.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 4-7/8 inch (124 mm) height.
6.
Number of Tiers: 11-7/8 inch (302 mm) height.
7.
Number of Tiers: 18-7/8 inch (479 mm).
8.
Pressure Drop: 396 millinches per foot (33 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec);
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per foot / W per m): ______.
G.
Basis of Design: Model H-1 as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 3/4 inch (19 mm) diameter copper seamless drawn tubing with one expanded end.
2.
Fins: 3 by 3-1/4 inch (76 by 83 mm), by 0.024 inch (0.61 mm) thick aluminum.
3.
Fins Density: 48 per ft (157.5 per m)
4.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 1.
6.
Number of Tiers: 2.
7.
Number of Tiers: 3.
8.
Pressure Drop: 708 millinches per ft (59 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
9.
Hot Water Temperature (F / C): ______.
10.
Hot Water Rating (Btu per hr per ft / W per m): ______.
H.
Basis of Design: Model H-5X as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 1-1/4 inch (31 mm) diameter copper seamless drawn tubing with one expanded end.
2.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.020 inch (0.51 mm) thick aluminum.
3.
Fin Density: 48 fins per ft (157.5 fins per m).
4.
Active Finned Length: Length minus 4 inch (102 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 1.
6.
Number of Tiers: 2.
7.
Number of Tiers: 3.
8.
Pressure Drop: 396 millinches per ft, based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 desgrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per ft / W per m): ______.
I.
Basis of Design: Model H-6X as manufactured by Slant/Fin Corporation. For single or multi-tier installations.
1.
Tube: 1-1/4 inch (DN 32) schedule 40 steel pipe with threaded ends.
2.
Fins: 3 by 3-1/4 inch (76 by 83 mm) by 0.028 inch (0.71 mm) thick aluminized steel.
3.
Fin Density: 48 fins per ft (157.5 fins per m).
4.
Active Finned Length: Length minus 5 inch (127 mm).
 
** NOTE TO SPECIFIER ** Delete number of tiers not required.
 
5.
Number of Tiers: 1.
6.
Number of Tiers: 2.
7.
Number of Tiers: 3.
8.
Pressure Drop: 420 millinches per ft (35 mm per m), based on flow rate of 3 ft per sec (0.914 m per sec).
 
** NOTE TO SPECIFIER ** See detailed product information for steam heat rating capacities. Based on 65 degrees F (18.3 degrees C) entering air temperature. Delete if not required.
 
9.
Steam Rating at 1 psi (6.9 kPa) Pressure: (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** See detailed product information for hot water rating capacities. Based on flow rate of 3 ft per sec (0.914 m per sec). Delete if not required.
 
10.
Hot Water Temperature (F / C): ______.
11.
Hot Water Rating (Btu per hr per ft / W per m): ______.
 
** NOTE TO SPECIFIER ** Standard length for S and C series are 2 to 12 ft (610 to 3658 mm) in 1 ft (305 mm) increments. C-340 is only available up to 10 ft (3048 mm). Standard lengths for H series are 2 to 10 ft (610 to 3048 mm) in 1 ft (305 mm) increments. 1/2 ft (152 mm) increments are available.
 
12.
Length (ft / mm): ______.
13.
Hangers and Accessories:
a.
Element Hangers: Channeled steel with guide rod allowing 1-5/16 inch (33 mm) lateral expansion movement and 1-1/8 inch (29 mm) vertical pitch adjustment.
b.
Optional Accessories:
1)
Adapter brackets for adding covers to heating elements.
2)
Hanging strips.
3)
Hook braces.
4)
Multi-tier brackets.
5)
Tamper proof locks.
6)
Wall gasketing.
PART 3 EXECUTION
 
3.1
EXAMINATION
A.
Do not begin installation until substrates have been properly prepared.
B.
If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
3.2
PREPARATION
A.
Clean surfaces thoroughly prior to installation.
B.
Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
3.3
INSTALLATION
A.
Install in accordance with manufacturer's instructions. Test for proper operation.
3.4
PROTECTION
A.
Protect installed products until completion of project.
B.
Touch-up, repair or replace damaged products before Substantial Completion.
END OF SECTION