 | 1. Configure Thermmax Scientific Products - SYSTEM DESCRIPTION: |
| | Control and Performance: |
| | | Temperature Range: |
| | | | Cold Room: 2 degrees C to 10 degrees C. | | Freezer Room: Minus 10 degrees C to minus 30 degrees C. |
| | | | Incubator Room: 20 degrees C to 50 degrees C. | | Stability Room: 0 degrees C to 60 degrees. |
| | | | Ultra-Low Freezer Room: 0 degrees C to minus 40 degrees C. | | Special Environmental Rooms: ___ degrees C to ___ degrees C. |
| | | Humidity Range: |
| MANUFACTURED UNITS: |
| | Doors: General: In-fitting, flush mounted, constructed similar to wall panels. |
| | | Door Swing: |
| | | Door Opening: |
| | Heated Gasket: Low voltage heater built into perimeter of jamb to prevent door from accumulating ice and freezing temperatures. |
| | Window: Multi-layer, heated thermal pane window mounted in door with the following minimum viewing area. |
| | | Window Size: |
| | Floors: Provide insulated floors with similar construction as wall and ceiling panels. |
| | | | Where scheduled, apply non-skid coating to cover floor surface. |
| | | Floor Thickness: |
| | | Floor Covering: Removable, open tread floor covering in each environmental room complying with the following: |
| | | | Thickness: 1/8 inch (3 mm). |
| | | | Material: PVC rubber matting. |
| | | | Pattern: Open diamond design for easy cleaning. |
| | | | Color: As selected. |
| | | Floor Covering: Seamless inlaid sheet vinyl in each environmental room complying with the following: |
| | | | Manufacturer: Medintech by Armstrong or equal. |
| | | | Coving: Seamless corner coving, extending into the sidewalls a minimum height of 4 inches (102 mm). Coving shall be vinyl capped. |
| | | | Color: As selected. |
| ROOM SURFACE FINISH: |
| | Standard Finishes: Where scheduled, provide panel sections with the following surface finishes. |
| | Special Aluminum Finishes: Provide panel sections with the following surface finishes. |
| | Special Stainless Steel Finishes: Provide interior and exterior wall surfaces fabricated from stainless steel with No. 2B finish. |
| LIGHTING: |
| | Low Temperature Electronic Ballasts: Provide low temperature for cold rooms operating below 10 degrees C (50 degrees F). |
| | Incandescent Lights: Vapor proof lights provide for freezers operating below 0 degrees C (32 degrees F). |
| | Light Cycle Timer: A 24 hour on/off cycle timer shall be provided on control panel for cycling interior lighting. |
 | INSTRUMENTS AND CONTROL SYSTEMS: |
| | Alarms: |
| | | Inside Panic Alarm: Red "mushroom head"-type push-button located inside room near door. |
| | Humidity Controller: When relative humidity control is specified, a completely solid state, electronic humidity controller will be supplied. |
| | Profile Programmer: Control system that includes microprocessor based set point instead of time profile programmer. |
| | Computer Interface: Digital computer communication interfaces designed to enable user to monitor and record process variables. |
| CONDITIONING PLENUMS: |
| | Steam Humidifier: Steam-generating-type humidifier designed to add water vapor into conditioning plenum and not directly into room area. |
| | | Uses demineralized, distilled or reverse osmosis water supply furnished by Owner. |
| | Chemical Drier (Sub-Freezing Dew Point Capability): Chemical dehumidifier system for ultra low humidity range. |
| FORCED AIR VENTILATION SYSTEM: |
| | Provide forced air exchange ventilation system for applications consisting of an independent exhaust blower and adjustable intake filter port. |
| | Amount of Air Exchange: |
 | REFRIGERATION SYSTEMS: |
| | Air-Cooled Condensing Unit: Provide system with air cooled condenser, low speed fans, and low noise with metal guard protection. |
| | Water-Cooled Condenser: Provide system with water-cooled condenser. Include water saving pressure regulation valve for constant compressor head pressure regulation. |
| | Redundant Refrigeration System: 100 percent backup refrigeration system with complete redundancy including all refrigeration components. |
| SHELVING: |
| | Freestanding Shelving: Chrome-plated wire rod shelving units manufactured free of burrs, sharp edges, and protrusions. |
| | Freestanding Shelving: Stainless steel wire rod shelving units manufactured free of burrs, sharp edges, and protrusions. |
| | Wall-Mounted Shelving: Chrome-plated or stainless steel, wire rod shelving units manufactured free of burrs, sharp edges, and protrusions. |
| | Protective Finish: Manufacturer's recommended MetroSeal or Eagle antimicrobial protective finish. |
| ACCESS PORTS: |
| | Provide access ports for water, drain line, air line, or gas lines in size specified: |
| SCHEDULE OF ROOMS: |
| | Equipment Designation: ER-1. |
| | | Condensing Unit: |
| | | Condensing Unit Location: |
| 2. When you are finished making selections: |
 | Generate Spec: Word WP or RTF |