1. Configure Thermmax Scientific Products - SYSTEM DESCRIPTION:
Control and Performance:
Temperature Range:
Cold Room: 2 degrees C to 10 degrees C.Freezer Room: Minus 10 degrees C to minus 30 degrees C.
Incubator Room: 20 degrees C to 50 degrees C.Stability Room: 0 degrees C to 60 degrees.
Ultra-Low Freezer Room: 0 degrees C to minus 40 degrees C.Special Environmental Rooms: ___ degrees C to ___ degrees C.
Humidity Range:
MANUFACTURED UNITS:
Doors: General: In-fitting, flush mounted, constructed similar to wall panels.
Door Swing:
Door Opening:
Heated Gasket: Low voltage heater built into perimeter of jamb to prevent door from accumulating ice and freezing temperatures.
Window: Multi-layer, heated thermal pane window mounted in door with the following minimum viewing area.
Window Size:
Floors: Provide insulated floors with similar construction as wall and ceiling panels.
Where scheduled, apply non-skid coating to cover floor surface.
Floor Thickness:
Floor Covering: Removable, open tread floor covering in each environmental room complying with the following:
Thickness: 1/8 inch (3 mm).
Material: PVC rubber matting.
Pattern: Open diamond design for easy cleaning.
Color: As selected.
Floor Covering: Seamless inlaid sheet vinyl in each environmental room complying with the following:
Manufacturer: Medintech by Armstrong or equal.
Coving: Seamless corner coving, extending into the sidewalls a minimum height of 4 inches (102 mm). Coving shall be vinyl capped.
Color: As selected.
ROOM SURFACE FINISH:
Standard Finishes: Where scheduled, provide panel sections with the following surface finishes.
Special Aluminum Finishes: Provide panel sections with the following surface finishes.
Special Stainless Steel Finishes: Provide interior and exterior wall surfaces fabricated from stainless steel with No. 2B finish.
LIGHTING:
Low Temperature Electronic Ballasts: Provide low temperature for cold rooms operating below 10 degrees C (50 degrees F).
Incandescent Lights: Vapor proof lights provide for freezers operating below 0 degrees C (32 degrees F).
Light Cycle Timer: A 24 hour on/off cycle timer shall be provided on control panel for cycling interior lighting.
INSTRUMENTS AND CONTROL SYSTEMS:
Alarms:
Inside Panic Alarm: Red "mushroom head"-type push-button located inside room near door.
Humidity Controller: When relative humidity control is specified, a completely solid state, electronic humidity controller will be supplied.
Profile Programmer: Control system that includes microprocessor based set point instead of time profile programmer.
Computer Interface: Digital computer communication interfaces designed to enable user to monitor and record process variables.
CONDITIONING PLENUMS:
Steam Humidifier: Steam-generating-type humidifier designed to add water vapor into conditioning plenum and not directly into room area.
Uses demineralized, distilled or reverse osmosis water supply furnished by Owner.
Chemical Drier (Sub-Freezing Dew Point Capability): Chemical dehumidifier system for ultra low humidity range.
FORCED AIR VENTILATION SYSTEM:
Provide forced air exchange ventilation system for applications consisting of an independent exhaust blower and adjustable intake filter port.
Amount of Air Exchange:
REFRIGERATION SYSTEMS:
Air-Cooled Condensing Unit: Provide system with air cooled condenser, low speed fans, and low noise with metal guard protection.
Water-Cooled Condenser: Provide system with water-cooled condenser. Include water saving pressure regulation valve for constant compressor
head pressure regulation.
Redundant Refrigeration System: 100 percent backup refrigeration system with complete redundancy including all refrigeration components.
SHELVING:
Freestanding Shelving: Chrome-plated wire rod shelving units manufactured free of burrs, sharp edges, and protrusions.
Freestanding Shelving: Stainless steel wire rod shelving units manufactured free of burrs, sharp edges, and protrusions.
Wall-Mounted Shelving: Chrome-plated or stainless steel, wire rod shelving units manufactured free of burrs, sharp edges, and protrusions.
Protective Finish: Manufacturer's recommended MetroSeal or Eagle antimicrobial protective finish.
ACCESS PORTS:
Provide access ports for water, drain line, air line, or gas lines in size specified:
SCHEDULE OF ROOMS:
Equipment Designation: ER-1.
Condensing Unit:
Condensing Unit Location: