1. Configure Anvil - Hangers and Supports:
Finishes:
Electro-plating galvanizing process per ASTM B633
Hot Dipped galvanizing process per ASTM A153
Epoxy paint
Zinc-rich paint
Standard primer shall meet Fed Spec TT-P-636
Manufactured Units:
Copper Tubing Hangers: Fig. Numbers.
Pipe Rings: Fig. Numbers.
Clevis: Fig. Numbers.
Steel Pipe Clamps: Fig. Numbers.
Steel Riser Clamps: Fig. Numbers.
Socket Clamps (AWWA/Ductile/Cast Iron Pipe): Fig. Numbers.
Beam Clamps: Fig. Numbers.
Structural Attachments: Fig. Numbers.
Ceiling Plates and Ceiling Flanges: Fig. Numbers.
Brackets: Fig. Numbers.
Concrete Inserts and Attachments: Fig. Numbers.
Hanger Rod and Rod Attachments: Fig. Numbers.
U-Bolts and Straps: Fig. Numbers.
Pipe Supports: Fig. Numbers.
Trapeze and Channel Support: Fig. Numbers.
Pipe Shields and Saddles: Fig. Numbers.
Pipe Rolls: Fig. Numbers.
Guides and Slides: Fig. Numbers.
Metal Framing:
Provide metal framing channel, fittings and hardware components as indicated or required for the structural
support of piping systems and equipment Metal framing shall be Anvil Strut as manufactured by Anvil International
for the structural support of piping systems and equipment.
Strut mounted pipe support, Klo-Shure insulated couplings with strut clamp, size range of 3/8 inch (9.5 mm) through 4 inch
(102 mm) copper tube with 3/8 inch (9.5 mm) through 1 inch ( 25 mm) thick insulation.
Strut mounted pipe clamps.
Strut mounted pipe rollers.
Strut mounted Cushion Clamps (steel pipe and copper tube).
Channels shall be produced from prime structural metals complying with the following specification as applicable:
Pre-Galvanized Steel - ASTM A-653
Plain Steel - ASTM A-570
Aluminum (Type 6063-T6) - ASTM B-221
Stainless Steel (Type 304 & 316) - ASTM A-240
Hanger Spacing:
Plumbing Piping: Most stringent requirements of Plumbing Code, or authority having jurisdiction
Fire Protection: Comply with applicable fire code
Gas and Fuel Oil Piping: Comply with pipe manufacturer's recommendations and applicable codes
Copper Piping: Comply with pipe manufacturer's recommendations and applicable codes
Flexible Joint Roll Groove Pipe: Not less than one hanger at joints. For size and
spacing of hangers and supports, refer to manufacturer's literature
When practical located immediately adjacent to any change of direction of pipe. Total length
of pipe between supports less than three-fourths the full hanger span
In case of concentrated loads (such as valves) the supports shall be placed as close as possible
 2. When you are finished making selections: