1. Configure Unifrax I LLC - 1st PRODUCT:
DUCT INSULATION FOR FIRE RATED VENTILATION AIR DUCTS (VAD)
FyreWrap Elite 1.5 Duct Insulation by Unifrax I LLC, Niagara Falls, NY:
Nominal 1.5 inch (38 mm) thick foil encapsulated blanket material at 6 PCF to provide 2-hour fire resistive enclosure assembly per ISO 6944
An inorganic, flexible, non-asbestos, bio-soluble high temperature, foil encapsulated blanket material
Blanket insulation must maintain a 2012 degree F (1100 degree C) operating temperature
Blanket fiber materials must be tested per EU regulatory requirements, Directive 97/69/EC for bio-solubility, and verified by an independent laboratory
Provide Firestop sealants, tape, insulation pins, clips, banding and other components to ensure the installed system complies with the complete tested two-hour fire rated VAD assembly
PLENUM INSULATION FOR NONCOMBUSTIBLE FIRE RATED PLENUM
FyreWrap 0.5 Plenum Insulation by Unifrax I LLC, Niagara Falls, NY:
Nominal 0.5 inches (12 mm) thick foil encapsulated blanket material to provide non combustible rating
An inorganic, flexible, non-asbestos, bio-soluble high temperature, foil encapsulated blanket material
Blanket insulation must maintain a 2012 degree F (1100 degree C) operating temperature
Blanket fiber materials must be tested per EU regulatory requirements, Directive 97/69/EC for bio-solubility, and verified by an independent laboratory
DUCT INSULATION FOR ZERO CLEARANCE APPLIED FIREPROOFING FOR FIRE-RATED GREASE DUCTS
FyreWrap Elite 1.5 Duct Insulation by Unifrax I LLC, Niagara Falls, NY:
Nominal 1.5 inch (38 mm) thick foil encapsulated blanket material at 6 PCF to provide 2-hour fire resistive enclosure assembly per ASTM E 2336
Nominal 1.5 inch (38 mm) thick foil encapsulated blanket material at 6 PCF to provide 2-hour fire resistive enclosure assembly per ASTM E 2336
A lightweight, flexible, inorganic, non-asbestos, bio-soluble, high temperature, foil encapsulated blanket wrap
Flexible, fully encapsulated blanket material, two-layer system to provide 2-hour fire resistive enclosure assembly per ASTM E 2336
Blanket insulation must maintain a 2012 degree F (1100 degree C) operating temperature
Blanket fiber materials must be tested per EU regulatory requirements, Directive 97/69/EC for bio-solubility, and verified by an independent laboratory
Provide field fabricated or prefabricated fire rated access doors (for cleanout as required) to maintain 2-hour rating and required clearance
Provide Firestop sealants, tape, insulation pins, clips, banding and other components as per manufacturer's instructions to provide fully functioning zero clearance to combustibles grease duct system
ACCESS DOORS
Access Door: Field fabricated 16 gauge steel
Threaded Rods: 1/4 inch (6 mm) diameter
Gasket: 1/2 inch (13 mm) Unfaced FyreWrap or ceramic fiber blanket
Access Door: Ductmate Ultimate prefabricated 16 gauge steel
Access Door: Ductmate F2 prefabricated 16 gauge steel