MasterFormat: 12
Download this Specification for   WORD | WP | RTF | TEXT
Find over 500 more construction specifications | Arcat.com
         
 
         
SECTION 07 56 00
 
         
FLUID APPLIED ROOFING
 
         
 
         
Copyright 2014 ARCAT, Inc. - All rights reserved

          ** NOTE TO SPECIFIER ** SOPREMA, Inc.; roofing and waterproofing systems.
.
This section is based on the products of SOPREMA, Inc., which is located at:
          310 Quadral Dr.
Wadsworth, OH 44281
Toll Free Te1: (800) 356-3521
Tel: (330) 334-0066
Fax: (330)334-4289
Email: bbotdorf@soprema.us.
Web: www.soprema.us

[ Click Here ] for additional information.
          Since 1908, SOPREMA has been a world-wide leader in the roofing membrane industry. Here in the Unites States, SOPREMA has transformed into 'The Building Envelope Company' with waterproofing products for every area of the building envelope. SOPREMA offers a wide range of products including SBS modified bitumen roofing membranes, liquid applied systems, waterproofing products for the entire building envelope, a complete line of self-adhered products, green solutions such as garden roof, building integrated photovoltaic systems and much more.

See our SpecWizard: Click Here

 
          PART 1GENERAL
 
          1.1SECTION INCLUDES
          ** NOTE TO SPECIFIER ** Delete items below not required for project.
 
          A.Adhered fully reinforced cold fluid-applied (PMMA) methyl-methacrylate liquid resin roofing system including, membrane, penetration flashings, base flashings, and expansion joints.
 
          B.Adhered non-reinforced cold fluid-applied polyurethane/bitumen liquid resin waterproofing system including, membrane, penetration flashings, base flashings, and expansion joints.
 
          C.Adhered non-reinforced cold fluid-applied styrene ethylene butadiene styrene (SEBS) liquid resin waterproofing system including, membrane, penetration flashings, base flashings, and expansion joints.
 
          1.2RELATED SECTIONS
          ** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
          A.Section 06 10 00 - Rough Carpentry.
 
          B.Section 06 11 00 - Wood Framing.
 
          C.Section 07 22 16 - Roof Board Insulation.
 
          D.Section 07 60 00 - Flashing and Sheet Metal.
 
          E.Section 07 72 33 - Roof Hatches.
 
          F.Section 07 81 33 - Mineral-Fiber Fireproofing.
 
          G.Section 22 30 00 - Plumbing Equipment.
 
          1.3REFERENCES
          ** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.
 
          A.American Society of Civil Engineers Reference Document ASCE 7-05 - Minimum Design Loads for Buildings and Other Structures.
 
          B.ACI-308 - Recommended Practice for Curing Concrete.
 
          C.ASTM - D638 - Test Methods for Tensile Properties of Plastics.
 
          D.ASTM - D4258 - Standard Practice for Surface Cleaning Concrete for Coatings.
 
          E.ASTM - D4259 - Standard Practice for Abrading Concrete.
 
          F.ASTM - D4541 - Method for Pull-Off Strength of Coatings using Portable Adhesion Tester
 
          G.ASTM - E96 (A) - Test Methods of Moisture Transmission of Material.
 
          H.ASTM E-108, ANSI/UL 790 for fire resistance.
 
          I.International Concrete Repair Institute Guideline 03732 Concrete Surface Preparation.
 
          J.Steel Structures Painting Council (SSPC).
 
          K.National Roofing Contractors Association (NRCA) - Roofing and Waterproofing Manual-4th Edition.
 
          L.Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) - Architectural Sheet Metal Manual.
 
          M.Underwriters Laboratories (UL) - Roofing Materials and Systems Annual Directory.
 
          N.IBC/IRC - AC75 Evaluation Reports.
 
          1.4CODE AND TEST REQUIREMENTS
 
          A.The roof system shall have been tested in compliance with the following codes and test requirements:
          1.Underwriters Laboratories UL 790 Class A and ASTM E 108 Class A external fire resistance criteria.
          2.Factory Mutual Research Corporation windstorm classification 1-540 minimum.
          3.Metal flashings shall be in compliance with ANSI-SPRI ES-1 Wind Design Standard for Edge Systems (most recent version prevailing).
          4.Florida Building Code Section 423.25.4 for large missile impact.
          5.The roof system assembly shall be installed in compliance with all local building and safety requirements adopted by the local building code jurisdiction.
 
          1.5DEFINITIONS
 
          A.Roofing Terminology: Refer to the following publications for terms related to roofing work not otherwise defined in this section.
          1.ASTM D 1079: Definitions of Terms Relating to Roofing, Waterproofing, and Bituminous Materials.
          2.National Roofing Contractor's Association (NRCA): Roofing and Waterproofing Manual.
          3.Roof Consultants Institute Glossary of Terms.
 
          1.6SYSTEM DESCRIPTION
          ** NOTE TO SPECIFIER ** Urethane system. Delete if not required.
 
          A.Roofing system shall be a two or three coat un-reinforced cold-applied liquid polyurethane membrane system applied over approved substrates. Alsan Flashing is a single component cold-applied liquid polyurethane / bitumen resin. The system is generally not reinforced except for certain critical areas which have Alsan PolyFleece reinforcement added. The finished surfacing is achieved with ceramic granules embedded in the top layer of liquid membrane or the application of a white finish coat.
          ** NOTE TO SPECIFIER ** MMA system. Delete if not required.
 
          B.Roofing system shall be a fully reinforced, cold fluid-applied, (PMMA) methyl-methacrylate liquid resin roofing/waterproofing membrane (with optional approved broadcast mineral aggregate surfacing or approved coating) and all other ancillary waterproofing work including but not limited to, installation of drains, pipe flashings, penetration flashings, sealants and metal work as specified.
          1.All membrane materials shall have a superior coefficient of expansion, to allow for differential movement between the horizontal and vertical surface of the flashed penetration or projection.
          2.New membrane system shall provide fast-drying primers to allow substrate preparation, priming and membrane application to be completed the same day.
          3.The use of cold fluid-applied reinforced (PMMA) methyl-methacrylate membrane materials will be required for all field membrane and flashings.
          4.Any occupied and/or heated spaces shall be waterproofed using a fully reinforced system.
          ** NOTE TO SPECIFIER ** SEBS system. Soprema Alsan MBSP over metal roofing. Delete if not required.
 
          C.Roofing system shall be a two coat un-reinforced cold-applied liquid Styrene Ethylbutlyene Styrene (SEBS) membrane system applied over approved metal roof substrates with all other ancillary waterproofing work including but not limited to, waterproofing of drains, pipe flashings, penetration flashings and metal work as specified.
          ** NOTE TO SPECIFIER ** SEBS system. Soprema Alsan MBSP over single ply membrane. Delete if not required.
 
          D.Roofing system shall be a three coat un-reinforced cold-applied liquid Styrene Ethylbutlyene Styrene (SEBS) membrane system applied over approved single ply roof membranes with all other ancillary waterproofing work including but not limited to, waterproofing of drains, pipe flashings, penetration flashings and metal work as specified.
          ** NOTE TO SPECIFIER ** Revise to meet additional testing requirements.
 
          1.7SUBMITTALS
 
          A.Submit under provisions of Section 01 30 00.
 
          B.Certification of Installer's experience with specified roof system shall be included in the submittal.
 
          C.Primary evidence of compliance shall be provided with the manufacturer's letter of intent-to-warrant. A photostatic copy of the specific assembly Approval (Miami-Dade NOA or RoofNav Assembly) is required for evidence of compliance with the specified wind load resistance; Underwriters Laboratories (UL) 790 classification (UL File designation TGFU); and Approval for large missile impact resistance as required by Subsection 5.4(d)(2) of the State of Florida Public Shelter Design Criteria for Enhanced Hurricane Protection Areas (EHPAs) (also as published in 2004 and 2007 FBC Section 423.25.4.1).
          ** NOTE TO SPECIFIER ** The pressures for all roof zones shall be provided. Insert Required Uplift Resistance Data.
 
          D.Design pressure calculations for the roof area in compliance with ASCE 7-05 and local Building Code requirements. A roof system attachment analysis (Engineer's Report), certifying the system's compliance with ASCE 7-05 wind load requirements, is required before work begins. This report shall signed and sealed by a Professional Engineer (P.E.) registered in the State of the Project and who has been providing such roof system attachment analysis for not less than the five consecutive previous years.
 
          E.Membrane System Product Data: Provide current standard printed product literature indicating characteristics of membrane materials, flashing materials, components, and accessories product specification and installation.
 
          F.Product Samples: Submit product samples of membrane and flashing materials showing color, texture, thickness and surfacing representative of the proposed system for review and approval by the Owners Representative.
          1.Provide four cured samples of the membrane showing the completed thickness with granules or a colored finish layer.
 
          G.Submit sample copies of both the Manufacturer and Applicator warranties for the periods stipulated. Each specimen shall be a preprinted representative sample of the issuing company's standard warranty for the system specified.
 
          H.Submit copies of current Material Safety Data Sheets (MSDS) for all components of the work.
 
          I.Shop Drawings:
          1.Shop Drawings: Submit required number of submittal copies of shop drawings showing all a project plan, size, flashing details, and attachment for review and approval by the Owners Representative and Membrane Manufacturer before job start.
          a.Basis of Design: Approved Details by SOPREMA, Inc. of Wadsworth, Ohio only, regardless of membrane manufacturer. All detailing - including but not limited to walls, curbs, drains, penetrations, edges, and expansion and control joints - shall be installed in strict accordance with prevailing Approved Details by SOPREMA.
          b.Provide complete installation details of roofing, flashing, fastening and insulation, including notation of roof slopes and fastening patterns of insulation and base modified bitumen membrane, prior to job start.
          ** NOTE TO SPECIFIER ** Retain the following for all high wind areas.
          2.Submit fastening calculations for attachment of wood nailers in compliance with FM 1-49.
          3.Submit Roofing Manufacturer's Field Fastener Testing Report in general compliance with Metro Dade Test Protocol PA 105.
 
          J.Certificates:
          1.Manufacturer's written approval of: 1.) The roof system to be applied over the submitted insulation and deck type; 2.) Contract documents; 3.) Applicator and; 4.) Warranty conditions specified.
          2.Insulation manufacturer's certification that the product is compatible with the proposed roof system and meets specification requirements.
          3.At completion of roof application: Roof membrane field inspection reports; punchlists; as-built drawings.
          4.Certification from the membrane manufacturer at job completion confirming the installed roof assembly is in compliance with the approved submittals and warranty provisions.
 
          1.8QUALITY ASSURANCE
 
          A.Installer Qualifications:
          1.Approved by the manufacturer prior to the bidding period and throughout the installation period. Present a copy of certification upon request by the Architect or Owner.
          2.Applicator shall have installed at least five roofs of the same materials and methods specified for this project.
          3.Maintain a permanent office within 100 miles (160 km) of project site.
          4.Maintain a full-time supervisor/foreman experienced with the specified roof system on-site when roof system application is in progress.
          5.Be equipped with a trained crew and with all capital equipment required to perform work of this section.
          a.Maintain all equipment and tools in good working order.
          b.Equip all kettles and tankers with accurate, fully readable thermometers.
          c.Provide written safety plan and equipment to the work force and specify, in writing, proper clothing.
          6.Shall appoint a safety coordinator who shall be a member of the roofing installation crew. The appointment shall be conveyed to the Building Owner in writing including all qualifications for the appointment.
          7.Maintain a daily job log to be kept on site at all times starting fr4om the date of the pre-roofing conference. The job log shall include:
          a.Copies of all submittals.
          b.Safety coordinator appointment with emergency telephone numbers; fall protection plan and material safety data sheets for all products.
          c.Daily crew attendance and time records.
          d.A summary of each days work including any photographs or detail revisions.
          e.Accident reports.
          f.Material delivery records.
          g.A visitor registry.
 
          B.Membrane Manufacturer: Company specializing in manufacturing fully reinforced, cold fluid-applied liquid resin waterproofing membrane products as specified in this section with a minimum of five years of documented applications in the United States. Membrane Manufacturer shall submit the following certifications for review:
          1.Substrates and conditions are acceptable for purpose of providing specified warranty.
          2.Materials supplied shall meet the specified requirements.
          3.Shall submit a current copy of their ISO 9002 manufacturing certification for the plant materials shall be manufactured and shipped from. Additionally, the SEQUENTIAL PRODUCTION LOG and the ISO 9002 PRODUCTION CONTROL RECORD documents shall accompany the material shipment and made a permanent part of the job record and warranty file.
          4.Provide a factory-trained technician to attend site meetings and to perform final inspections of the roofing system.
          5.Provide a warranty upon satisfactory installation of the roofing system.
          ** NOTE TO SPECIFIER ** Include a mock-up if the project size and/or quality warrant taking such a precaution. The following is one example of how a mock-up on a large project might be specified. When deciding on the extent of the mock-up, consider all the major different types of work on the project.
 
          C.Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.
          1.Finish areas designated by Architect.
          2.Do not proceed with remaining work until workmanship is approved by Architect.
          3.Correct mock-up area as required to produce acceptable work.
 
          1.9PRE-INSTALLATION CONFERENCE
 
          A.Convene no less than five days prior to commencing Work at a time and location to be determined.
          1.All parties responsible for Work of this section shall be required to attend including the Architect, Owner, Contractor and any other trades affected by the roofing Work.
          2.Review installation procedures and coordination required with related work.
          3.Inspect and make notes of job conditions prior to installation:
          a.Minutes shall be taken at the conference and provided to all parties present.
          b.All outstanding issues shall be noted in writing designating the responsible party for follow-up action and the timetable for completion.
          c.Application of roofing system shall not take place until all outstanding issues are resolved to the satisfaction of the Building Owner.
 
          B.Work shall not begin until a NOTICE TO PROCEED is issued following the pre-roofing conference. This notice shall include information concerning acceptable staging areas; suitable parking and access points; placement of trash conveyances; sanitary requirements; any and all working hour restrictions (day/night, weekends, and holidays); noise restrictions and project complaint procedure between Contractor and Building Owner.
 
          1.10DELIVERY, STORAGE, AND PROTECTION
 
          A.The Contractor together with the Owner or his designated Representative shall define a storage area for all components. The area shall be cool, dry, out of direct sunlight, and in accordance with manufacturers recommendations and relevant regulatory agencies. Materials shall not be stored in quantities that will exceed design loads, damage substrate materials, hinder installation or drainage.
 
          B.Store solvent-bearing solutions, resins, additives, inhibitors or adhesives in accordance with the MSDS and/or local fire authority. After partial use of materials replace lids promptly and tightly to prevent contamination.
 
          C.Roll goods shall be stored horizontally on platforms sufficiently elevated to prevent contact with water and other contaminants. DO NOT use rolls that are wet, dirty or have damaged ends.
 
          D.Roofing/waterproofing materials shall be kept dry at all times. If stored outside, raise materials above ground or roof level on pallets and cover with a tarpaulin or other waterproof material. Plastic wrapping installed at the factory shall not be used as outside storage covers.
 
          E.Follow manufacturer's directions for protection of materials prior to and during installation. Do not use materials that have been damaged to the point that they will not perform as specified. Fleece reinforcing materials shall be clean, dry and free of all contaminants.
 
          F.Copies of all current MSDS for all components shall be kept on site. Provide any and all crew members with appropriate safety data information and training as it relates to the specific chemical compound he or she may be expected to deal with. Each crew member shall be fully aware of first-aid measures to be undertaken in case of incidents. Comply with requirements of OSHA, NIOSH or local governing authority for work place safety.
 
          1.11ENVIRONMENTAL REQUIREMENTS
 
          A.Do not apply roofing/waterproofing membrane during or with the threat of inclement weather.
 
          B.Application of cold fluid-applied reinforced (PMMA) methyl-methacrylate roofing and waterproofing membrane may proceed while air temperature is between 23 degree F (-5 degree C) and 95 degree F (35 degree C) providing the substrate is a minimum of 5 degree F above the dew point.
 
          C.When ambient temperatures are at or expected to fall below 32 degree F (0 degree C), or reach 86 degree F (30 degree C) or higher, follow Membrane System Manufacturer's recommendations for weather related application procedures.
 
          D.Ensure that substrate materials are dry and free of contaminants. DO NOT commence with the application unless substrate conditions are suitable. Contractor shall demonstrate that substrate conditions are suitable for the application of the materials.
 
          E.Where required by the Owner or his designated Representative, Contractor shall implement odor control and elimination measures prior to and during the application of the roofing/waterproofing materials. Control/elimination measures shall be field tested at off-hours and typically consists of one or a multiple of the following measures:
          1.Sealing of air intakes with activated carbon filters. Install filters in accordance with requirements and recommendations of the filter manufacturer. Seal filters at joints and against building exterior walls to prevent leakage of unfiltered air where required due to size of intake opening. Provide track system to secure filters.
          2.Erection and use of moveable enclosure(s) sized to accommodate work area(s) and stationary enclosure for resin mixing station. Enclosure shall be field constructed or pre-manufactured of fire retardant materials in compliance with local code requirements in accordance with requirements of the Owner or his designated Representative. Equipment enclosure(s) with mechanical air intake/exhaust openings and Odor Control Air Cleaners, as required to clean enclosed air volume and to prevent odor migration outside the enclosure. Exhaust opening shall be sealed with activated carbon filter.
          3.Placement of odor elimination stations inside and outside of the enclosure(s) as required by field condition, in coordination with the Owner or his designated Representative.
          4.Protection of Contractor personnel and occupants of the structure and surrounding buildings as necessary to comply with requirements of OSHA, NIOSH and/or governing local authority.
          5.When disposing of all refuse or unused materials, observe all EPA, OSHA or local disposal requirements.
 
          1.12COORDINATION AND PROTECTION
 
          A.Coordinate the work with the installation of associated metal flashings, accessories, appurtenances, etc. as the work of this section proceeds.
 
          B.Building components shall be protected adequately (with tarp or other suitable material) from soil, stains, or spills at all hoisting points and areas of application. Contractor shall be responsible for preventing damage from any operation under its Contract. Any such damage shall be repaired at Contractor's expense to Owner's satisfaction or be restored to original condition.
 
          C.Provide barricades, retaining ropes, safety elements (active/passive) and any appropriate signage required by OSHA, NIOSH, and NSC and/or the Owner or designated Representative.
 
          D.Protect finished roofing/waterproofing membrane from damage by other trades. Do not allow waste products containing petroleum, grease, acid, solvents, vegetable or mineral oil, animal oil, animal fat, etc. or direct steam venting to come into direct contact with the membrane.
 
          1.13QUALITY CONTROL
 
          A.Submit certification by the manufacturer that the system materials indicated by Specifications and Drawing Details are acceptable for the deck and surfacing to which they are to be applied.
          1.All detailing - including but not limited to walls, curbs, drains, penetrations, edges, and expansion and control joints - shall be installed in strict accordance with prevailing Approved Details by SOPREMA, Inc. of Wadsworth, Ohio as the Basis of Design regardless of membrane manufacturer.
 
          B.Inspection: At a minimum, inspections shall be required at start-up and at intervals of approximately 30%, 60% and 90% completion. A final inspection shall be required.
          1.Warranty shall be issued upon approval of the installation.
          2.Inspections shall be performed by a Technical Representative employed full-time by the Manufacturer and whose primary job description is to assist, inspect and approve membrane installations for the Manufacturer only.
          3.A final inspection report from the Technical Representative, certifying that the roofing system has been satisfactorily installed according to the project specifications, Approved Details and good general roofing practice, shall be provided.
          4.Any failure by the Owner's or Manufacturers' Representative to detect, pinpoint, or object to any defect or noncompliance of these specifications of work in progress or completed work shall not relieve the contractor, or reduce, or in any way limit, his responsibility of full performance of work required of him under these specifications.
 
          C.Evaluate moisture content of substrate materials. Constructor shall determine substrate moisture content throughout the work and record with Daily Inspection Reports or other form of reporting acceptable to the Owner or designated Representative, and Membrane Manufacturer.
 
          D.Random tests to determine tensile bond strength of membrane to substrate shall be conducted by the Contractor at the job site by the performance of a manual pull test. Contractor shall perform tests at the beginning of the Work, and at intervals as required to assure specified adhesion with a minimum of three tests per 5000 square feet (465 square meters). Smaller areas shall receive a minimum of three tests. Test results shall be submitted to the Owner or his designated Representative and the Membrane Manufacturer. Contractor shall immediately notify the Owner or his designated Representative and Membrane Manufacturer in the event bond test results are below specified values.
          1.Adequate surface preparation will be indicated by tensile bond strength of membrane to substrate greater than or equal to 219 psi (1.5 N/mm2) for pedestrian traffic and 300 psi (2.0 N/mm2) for vehicular (low speed) traffic and water flow/containment, as determined by use of an adhesion tester.
          2.Adequate surface preparation will be indicated by 135 degree peel bond strength of membrane to substrate such that cohesive failure of substrate occurs before adhesive failure of membrane/substrate interface.
          3.In the event the bond strengths are less than the minimum specified, additional substrate preparation is required. Repeat testing to verify suitability of substrate preparation.
 
          E.Monitor quantities of installed materials. Monitor application of resin mixture, reinforcing fleece and flashing. Perform Work in accordance with manufacturer's instructions.
 
          F.Submit certification that the materials to be used meet these specifications and are acceptable for use with the field membrane system and for the surfaces that they are to be applied.
 
          G.Installation:
          1.Unless otherwise indicated, the materials to be used in this specification are those specified and denote the type, quality, performance, etc. required. All proposals shall be based upon the use of the specified material.
          2.Install materials in accordance with the manufacturer's current published application procedures and the general recommendations of the National Roofing Contractor's Association.
          3.It will be the contractor's responsibility to obtain and/or verify any necessary dimensions by visiting the job site, and the contractor shall be responsible for the correctness of same. Any drawings supplied are for reference only.
          4.Contractor shall plan and conduct the operations of the work so that each section started on one day is complete, details installed and thoroughly protected and in watertight condition before the close of work for that day.
          5.Materials will be securely fastened in place in a watertight, neat and workmanlike manner. All workmen shall be thoroughly experienced in the particular class of work upon which employed. Work shall be performed in accordance with these specifications and shall meet the approval in the field of the Architect.
          6.All waste materials, rubbish, etc., shall be removed from the Owner's premises as accumulated. Rubbish shall be carefully handled to reduce the spread of dust, and shall be deposited at an approved disposal site.
 
          1.14LABORATORY TESTING
 
          A.Upon request from the Owner or Architect the elastomeric membrane manufacturers shall supply, at their expense, the results of mechanical and chemical testing performed on the materials supplied.
 
          B.The tests shall be performed to certify compliance with the standards referenced under this section.
 
          1.15SITE PROTECTION
 
          A.During roofing work, exposed surfaces of finished walls shall be protected with tarps to prevent damage. Contractor shall assume full responsibility for any damage.
 
          1.16PROJECT CONDITIONS
 
          A.Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.
 
          1.17WARRANTY
          ** NOTE TO SPECIFIER ** PMMA system. Delete if not required.
 
          A.Manufacturer's Standard Warranty: Provide twenty year standard manufacturer's warranty under provisions of this section.
          ** NOTE TO SPECIFIER ** Urethane and SEBS system. Delete if not required.
 
          B.Manufacturer's Standard Warranty: Provide ten year standard manufacturer's warranty under provisions of this section.
 
          C.Waterproofing Contractor's Warranty: Provide 2 year "Applicator Maintenance Warranty" covering workmanship for all work of this section including installation of membrane, flashings, metal work, and roofing/waterproofing accessories.
 
          D.Submit two executed copies of both the manufacturer and applicator warranties for the periods stipulated, starting from the date of substantial completion. Each warranty shall be signed by an authorized representative of the issuing company.
 
          PART 2PRODUCTS
 
          2.1MANUFACTURERS
 
          A.Acceptable Manufacturer: SOPREMA, Inc., which is located at: 310 Quadral Dr. ; Wadsworth, OH 44281; Toll Free Tel: 800-356-3521; Tel: 330-334-0066; Fax: 330-334-4289; Email: request info; Web: www.soprema.us
          ** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
          B.Substitutions: Not permitted.
 
          C.Requests for substitutions will be considered in accordance with provisions of Section 01 60 00.
 
          2.2FIELD MEMBRANE
          ** NOTE TO SPECIFIER ** PMMA System. Delete if not required.
 
          A.Field Membrane: Two-component, with catalyst, cold fluid-applied (PMMA) methyl-methacrylate waterproofing membrane reinforced with Alsan RS Fleece, for a finished nominal dry film membrane thickness of .080 inch per ply.
          1.Waterproofing Membrane: Soprema Alsan RS 230 Field resin for use in a fully adhered waterproofing membrane system.
          2.Color: Pebble Gray.
          ** NOTE TO SPECIFIER ** Urethane system. Delete if not required.
 
          B.Field Membrane: Ready to use single component bitumen modified polyurethane resin.
          1.Product: Alsan Flashing 1 by SOPREMA.
          2.Physical State: Thixotropic Paste.
          3.Color: Brown.
          ** NOTE TO SPECIFIER ** SEBS system. Delete if not required.
 
          C.Field Membrane: Cold-applied liquid Styrene Ethylbutlyene Styrene (SEBS) membrane.
          1.Product: Alsan MBSP Grey (undercoat).
          2.Product: Alsan MBSP White (topcoat).
          ** NOTE TO SPECIFIER ** Primers not required for SEBS System. Delete if not required.
 
          2.3PRIMERS
          ** NOTE TO SPECIFIER ** PMMA System. Delete if not required.
 
          A.Epoxy Primer: Supplied by membrane manufacturer; two-component, high solids, and low-odor translucent epoxy primer for use in improving adhesion of membrane to substrate surfaces. Monitor application rate and adjust depending on substrate absorbency.
          1.Product: Soprema Alsan EPR Primer for use on highly absorbent substrates.
          ** NOTE TO SPECIFIER ** PMMA System. Delete if not required.
 
          B.Methyl-Methacrylate Primer: Supplied by membrane manufacturer; two-component, high solids (PMMA) methyl-methacrylate resin for use in improving adhesion of membrane to various substrate surfaces. Monitor application rate and adjust depending on substrate absorbency.
          ** NOTE TO SPECIFIER ** Delete if not required.
          1.Product: Soprema Alsan RS 222 Primer for use over bituminous surfaces in fully adhered waterproofing membrane system.
          ** NOTE TO SPECIFIER ** Delete if not required.
          2.Product: Soprema Alsan RS 276 Primer for use over concrete and wood surfaces in fully adhered waterproofing membrane system.
          ** NOTE TO SPECIFIER ** Urethane System. Delete if not required.
 
          C.Primer:
          1.Product: Alsan Trafik HP 510 Zero single component polyurethane primer.
          2.Product: Alsan 2K Primer two component low odor polyurethane primer.
 
          2.4FLASHING MEMBRANE
          ** NOTE TO SPECIFIER ** Urethane and PMMA System. Delete if not required.
 
          A.Flashing Membrane: A vertical grade two-component, with catalyst, cold fluid-applied (PMMA) methyl-methacrylate waterproofing membrane reinforced with Alsan RS Fleece, for a finished nominal dry film membrane thickness of .080 inch (2 mm) per ply with optional finished colored aggregate topcoat surfacing or approved coating.
          1.Product: Soprema Alsan RS 230 Flash resin for use in a fully adhered waterproofing membrane system.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          B.Flashing Membrane: A vertical grade single component polyurethane/bitumen resin, cold fluid-applied waterproofing membrane reinforced at transition changes with Alsan POLYFLEECE for a finished nominal dry film thickness of 0.080 inch (2 mm) per ply with optional finished colored ceramic granule topcoat surfacing.
          1.Product: Soprema Alsan Flashing resin for use in a fully adhered waterproofing membrane system.
 
          2.5OTHER RESINS
 
          A.Wearing/Surfacing Resin: Three-component, with catalyst, cold fluid-applied (PMMA) methyl-methacrylate self-leveling mortar.
          1.Product: Soprema Alsan RS 233 Self-Leveling Mortar (Alsan RS 210 resin mixed with Alsan RS 223 Powder) for use in trafficable waterproofing membrane systems.
 
          B.Patching, Filling and Smoothing Resin: Two-component, with catalyst, cold fluid-applied (PM MA) methyl-methacrylate paste.
          1.Product: Soprema Alsan RS Paste for use in filling small cracks, voids and depressions and for smoothing membrane laps prior to application of Alsan RS resins.
          2.Product: Soprema Alsan RS Detailer (micro-fiber enhanced PMMA) for use in flashing small and difficult penetrations and for filling small cracks, voids and depressions where use of Alsan RS reinforced membrane is not possible. Use of material shall be approved by manufacturer in writing.
 
          C.Textured Surfacing: Two-component, with catalyst, cold fluid-applied (PMMA) methyl methacrylate resin, with pre-mixed grain, trafficable surface finish.
          1.Product: Soprema Alsan RS Textured Coating for use as a heavy duty vehicular trafficable surface finish in reinforced and non-reinforced systems.
          2.Product: Soprema Alsan RS 290 Textured Finish for use as a pedestrian or vehicular trafficable surface finish in reinforced and non-reinforced systems.
 
          D.Finish Resin: Two-component, with catalyst, cold fluid-applied (PMMA) methyl-methacrylate aesthetic finish layer.
          1.Product: Soprema Alsan RS 288 Finish for use as a colored finish layer, colored finish layer with Alsan RS Deco Chips broadcasted and as a sealing layer when natural Alsan RS Surfacing Aggregate is used.
          2.Product: Soprema Alsan RS 281 Finish for use as a translucent (clear) finish layer over colored Alsan RS Surfacing Aggregate, vinyl chips or other approved aesthetic materials.
 
          2.6REINFORCEMENT
          ** NOTE TO SPECIFIER ** PMMA System. Delete if not required.
 
          A.Reinforcing Fleece: Non-woven, needle-punched polyester fabric reinforcement used in the Alsan RS system.
          1.Soprema Alsan RS Fleece used to improve tear strength, puncture resistance, flexural fatigue and crack bridging capabilities while maintaining membrane uniformity.
          a.Color: White.
          b.Nominal thickness: 40 mils (1 mm).
          c.Weight: 110 g/sq. m 0.022 pd/sf).
          d.Tensile Strength @ break (N/50mm): ~ 130 MD / 150 CMD.
          e.Elongation (%): ~50 MD/70 CMD.
          f.Tear Resistance: >20 daN.
          g.Puncture Resistance: >24 daN.
          h.Water absorption (%): <1%.
          ** NOTE TO SPECIFIER ** Urethane and SEBS System. Delete if not required.
 
          B.Reinforcing Fleece:
          1.Alsan PolyFleece is a spun-laced high performance polyester reinforcement used at change of plane junctures, penetrations, curbs, projections, repairs and seams.
 
          2.7ACCESSORIES
 
          A.Tools, Accessories, and Cleaners: Supplied and/or approved by membrane manufacturer for product installation.
 
          B.Aggregate:
          1.Product: Alsan RS Surfacing.
          2.Topcoat Slip-Resistant Surfacing Aggregate: Silica sand, ceramic-coated quartz, or specialty aggregate shall be washed, kiln-dried, and dust-free with the following size specification:
          a.Aesthetic: .016 to .031 inch (0.4 to 0.8 mm).
          b.Bond/Wearing Coat: .04 to .06 inch (1.0 to 1.6 mm).
          c.Light Pedestrian Traffic: .016 to .031 inch (0.4 to 0.8 mm).
          d.Soprema Alsan RS Deco Chips: 1/16 inch + (1.6 mm +).
          3.Leveling and Patching Aggregate: silica sand shall be washed, kiln-dried, and dust-free, suitable for troweling or pourable self-leveling, round grain or angular with the following size specification:
          a.For voids less than 1/4 inch in depth: .016 to .031 inch (0.4 to 0.8 mm).
          b.For voids 1/4 inch to 2 inches in depth: .03 to .047 inch (0.7 to 1.2 mm).
          c.Mixing Proportions shall be a ratio of primer to sand at 1:3 by volume or as approved by membrane manufacturer.
 
          C.Backer Rod: Expanded, closed-cell polyethylene foam designed for use with cold-applied joint sealant.
 
          D.Caulking: Single component, non-sag elastomeric polyurethane sealant, as recommended and supplied by membrane manufacturer for use in making airtight and watertight seals where required.
 
          E.Wood Nailers and Cant Strips: New wood nailers and cant strips shall be pressure treated for rot resistance (e.g., "Wolmanized" or "Osmose K-33"), #2 or better lumber. Asphaltic or creosote treated lumber is not acceptable.
 
          F.Miscellaneous Fasteners: Appropriate for purpose intended and approved by fastener manufacturer; length required for thickness of material [with metal washers]; as supplied and approved by membrane manufacturer.
 
          G.Drains: Spun/cast aluminum or cast iron roof drain with strainer/grate, as supplied or approved by membrane manufacturer.
 
          H.Temporary and Night Sealant: As recommended or required by membrane manufacturer.
 
          I.Alsan RS Catalyst Powder: White granular powder, based on dibenzoylperoxide, used as a reactive agent to induce curing of all Alsan RS resins.
 
          J.Alsan RS Liquid Thixo: Thixotropic liquid additive used to increase viscosity of Alsan RS resins.
 
          K.Pavers: Standard concrete pavers with compressive strength greater than or equal to 7000 psi, water absorption not greater than 5% and meeting ASTM C-67 for freeze/thaw cycles as recommended by manufacturer.
 
          L.Supportive Pedestals: Pedestals to support and space pavers with leveling shims or similar method to adjust paver height as recommended by manufacturer.
 
          M.Insulation Adhesive: Two component elastomeric high velocity urethane insulation adhesive.
          1.Product: Soprema High Velocity Insulation Adhesive III.
 
          2.8INSULATION COVER BOARD
 
          A.Cover Board (Sopraboard by SOPREMA): High compressive strength, multi-ply, semi-rigid asphaltic roofing substrate underlayment board composed of a mineral fortified asphaltic core formed between two asphaltic saturated fiberglass liners.
 
          B.Cover Board (Durock by United States Gypsum): High compressive strength underlayment board consisting of aggregated Portland cement slurry with polymer-coated glass-fiber mesh.
 
          C.Cover Board (Plywood): APA-rated C-C Plugged exterior-grade plywood board, installed plugged side up.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          2.9INSULATION
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          A.Insulation: Soprema's polyisocyanurate insulation board having non-asphaltic facers meeting or exceeding the requirements for Fed. Spec. HH-I-1972/Gen. with minimum compressive resistance of 18 psi (0.12 MPa), 1.0 inch (25 mm) minimum thickness.
          1.Board Density 2.0 lb/cu ft (32 kg/cu. m).
 
          B.Insulation: Extruded polystyrene insulation board as approved by manufacturer.
          1.Insulation to meet ASTM C-578, Types VI or VII.
          2.Insulation shall be free of CFC's.
 
          2.10TAPERED INSULATION
 
          A.Insulation: Tapered polyisocyanurate insulation board having non-asphaltic facers meeting or exceeding the requirements for Fed. Spec. HH-I-1972/Gen. with minimum compressive resistance of 18 psi (0.12 MPa), 1.0 inch (25 mm) minimum thickness.
 
          2.11MODIFIED BITUMEN BASE SHEET
 
          A.Product: Colvent by Soprema. Torch or self-adhered modified bitumen vented base sheets.
 
          B.Product: Elastophene by Soprema. Torch or self-adhered modified bitumen base sheets.
 
          C.Product: Sopralene by Soprema. Torch or self-adhered modified bitumen base sheets.
 
          2.12MODIFIED BITUMEN PRIMER
 
          A.Elastocol 500 asphaltic primer.
 
          B.Elastocol 600c asphaltic primer.
 
          2.13BASE/CAP SHEET AND INSULATION SECUREMENT
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          A.Mechanical Fasteners: FM-approved corrosion resistant insulation/base sheet fasteners of appropriate length with plates. Securement pattern shall be in accordance with specified wind uplift rating for system application. Roofing fasteners shall be a type approved and supplied by membrane manufacturer.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          B.Polyurethane Adhesive: FM-approved High Velocity, moisture-cured polyurethane adhesive. Adhesive application rate shall be in accordance with specified wind uplift rating for system application. Roofing adhesive shall be a type approved and supplied by membrane manufacturer. Note: prior written approval by the adhesive, insulation and membrane type for use of polyurethane roofing adhesive shall be obtained from membrane manufacturer.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          C.Asphalt Adhesive: FM-approved steep roofing asphalt conforming to ASTM D -312, Type III. Provide label on each container indicating flash point, finished blowing temperature, softening point, and equiviscous temperature. Asphalt primer, cutback solvent type, conforming to ASTM D-41, required for concrete, masonry, and metal surfaces.
 
          2.14WEARING AND SURFACING
 
          A.Aesthetic Color Finish Coating: Two-component rapid curing (PMMA) methyl-methacrylate based coating suitable for use as a colored coating for exposed and submerged applications, as provided by the following Manufacturer:
          ** NOTE TO SPECIFIER ** Delete product not required.
          1.Product: Soprema Alsan RS 288 Finish color resin.
          2.Product: Soprema Alsan RS Deco Chips.
 
          B.Aggregate Walkway Slip-Resistant Finish Surfacing: Two-component rapid curing (PMMA) methyl-methacrylate based resin suitable for use to both bond and seal aggregate, as provided by the following Manufacturer:
          ** NOTE TO SPECIFIER ** Delete product not required.
          1.Product: Soprema kiln-dried silica quartz aggregate.
          2.Product: Soprema ceramic colored quartz aggregate.
          3.Product: Soprema Alsan RS 288 Finish color resin.
          4.Product: Soprema Alsan RS 281 Finish translucent resin.
          5.Product: Soprema Alsan RS Deco Chips.
          6.Product: Soprema Alsan RS 290 Textured Finish.
 
          PART 3EXECUTION
 
          3.1EXAMINATION
 
          A.Do not begin installation until substrates have been properly prepared.
 
          B.If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
          ** NOTE TO SPECIFIER ** The acceptance of the structural roof deck condition by SOPREMA refers solely to condition of roof deck surface. The responsibility for the structural integrity of the roof deck system and for the proper design relationship among other building components-combined with the existing or potential interior and exterior environmental considerations-and the structural roof deck system rests solely with the design professional whether they are an architect, roof consultant, engineer or building owner or authorized building owner representative. SOPREMA reserves the right to accept or reject existing deck conditions based on their suitability for specific SOPREMA assemblies and their corresponding methods of application.
 
          3.2SURFACE INSPECTION AND PREPARATION
 
          A.Before commencing work, all surfaces shall be smooth, clean, dry and free of any debris that would adversely effect the installation of the membrane.
 
          B.Before commencing work, the Owner's representative, together with the roofing subcontractor, shall inspect and approve the deck condition as suitable for installation of roofing. Review shall include slopes and nailing supports if applicable as well as verticals on parapet walls, roof drains, stack vents, vent outlets and others, building joints, and similar items.
          1.If defective conditions exist work shall not begin until corrected, or a non-compliance notice shall be submitted to the Contractor so that adjustments can be made prior to installation.
          2.Commencement of work shall mean acceptance of surfaces and conditions by the Owner or their designated representative.
 
          C.Verify that the work of other trades has been properly completed.
 
          D.Do not install materials in inclement weather.
 
          3.3PREPARATION OF SUBSTRATE
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          A.General: All existing roofing and waterproofing materials are to be removed down to the structural deck unless noted otherwise.
 
          B.Surfaces shall be structurally sound, dry and clean; free from moisture, dirt, grease, oil, paint or any other loose or existing waterproof coatings. Remove all previous coatings, laitance or any other contamination which may affect the bond of the field and flashing components. Gravel or debris between the substrate and plies is not acceptable.
 
          C.Surfaces to be prepared as a substrate for the new waterproofing system as follows:
          1.The contractor shall determine the condition of the existing structural deck/substrate. All defects in the deck or substrate shall be corrected before new waterproofing work commences. Areas of deteriorated deck/substrate, porous or other affected materials shall be removed and replaced with new to match existing.
          2.Prepare flashing substrates as required for application of new waterproofing membrane flashings.
          3.Inspect substrates, and correct defects before application of new waterproofing. Fill all surface voids greater than 1/8 inch (3 mm) wide with an acceptable fill material.
          4.Remove all ponded water, snow, frost and/or ice from the work substrate prior to installing new waterproofing materials.
          5.The final substrate for waterproofing shall be clean, dry, free of loose, spalled or weak material including coatings, mineral aggregate, and flood coat/gravel surfacing, oil, grease, contaminants, abrupt changes in level, waterproofing agents, curing compounds, and free of projections which could damage membrane materials.
          ** NOTE TO SPECIFIER ** As an option to applying the Alsan RS system directly to concrete, adhere a Soprema modified bitumen base sheet to the properly primed substrate.
 
          D.Concrete:
          1.New concrete shall have cured a minimum of 28 days in accordance with ACI-308, or as approved by Waterproofing Manufacturer's Technical Department.
          2.New or existing concrete shall be free of oil, grease, curing compounds, loose particles, moss, algae growth, laitance, friable matter, dirt, bituminous products and previous waterproofing materials.
          3.New or existing concrete shall be dry with a maximum moisture content of six percent and ninety-six percent relative humidity. Determinations of moisture content shall be performed by the Contractor. Contractor shall be responsible to perform periodic evaluations of moisture content during the work. Moisture evaluation results shall be submitted in writing to the Owner or his designated Representative and Waterproofing manufacturer for acceptance.
          4.Where required, concrete shall be abrasively cleaned in accordance with ASTM D4259 to provide a sound substrate free from laitance. Achieve an open concrete surface in accordance with ICRI surface profiles CSP 2 to 5. When using mechanical methods to remove existing waterproofing products or surface deterioration, the surface profile is not to exceed 1/4 inch (6 mm) (peak to valley).
          5.The substrate shall be sound and all spalls, voids and blow holes on vertical or horizontal surfaces shall be repaired prior to placement of the primer coat. Ensure all uneven areas are leveled using cementitious or other suitable materials. Repairs are to be done in accordance with the requirements of the Owner or his designated Representative and approved by the Membrane manufacturer.
          6.Areas of minor surface deterioration of 1/4 inch (6 mm) or greater in depth shall be repaired to prevent possible ponding of the system, leading to excessive usage of primer and resin.
          7.Extent and location of thin surface patching shall require approval of the Owner or his designated Representative and Waterproofing Manufacturer prior to the application of any system component.
          8.For concrete materials with a compressive strength of less than 3,500 psi (24 MPa) contact Waterproofing Manufacturer's Technical Department for substrate preparation requirements.
 
          E.Masonry:
          1.Walls shall be built with hard kiln dried brick or waterproof concrete block construction.
          2.Areas of soft or scaling brick or concrete, faulty mortar joints, or walls with broken, damaged or leaking coping shall be repaired in accordance with the requirements of the Owner or his designated Representative and Flashing Membrane Manufacturer.
 
          F.Steel/Metal:
          1.Clean and prepare metal surfaces to near white metal in accordance with SSPC - SP3 (power tool clean) or as required by membrane manufacturer. Extend preparation a minimum of three inches (76 mm) beyond the termination of the membrane flashing materials. Notch steel surfaces to provide a rust-stop.
          2.In addition to cleaning, all metal surfaces shall be abraded to provide a rough open surface. A wire brush finish is not acceptable.
 
          G.Wood/Plywood:
          1.Plywood shall be identified with American Plywood Association (APA) grade trade marks and shall meet the requirements of product standard PS1. Strip plywood joints with four inch (102 mm) wide strip of flashing membrane. Cover knot holes or cracks with strips of flashing Membrane.
 
          H.Other Flashing Surfaces:
          1.Remove all contaminants as required by membrane manufacturer. Surface preparation shall be performed by means approved by Owner or his designated Representative.
          2.All rust and contaminants need to be removed from metal to be flashed. Clean all metal to bright. Mechanical abrasion (SSPC SP-3 or SSPC SP-10) may be necessary to remove contaminants. Perform an adhesion test if there are any doubts. For application to Kynar or metals with similar finishes contact the Soprema Technical Department.
          3.For PVC piping use sandpaper or similar to rough up the surface before flashing. Priming may be necessary.
 
          I.Finish Leveling, Patching and Crack Preparation:
          1.General: Resin/sand mix is the preferred material for all substrate finish leveling, crack and wall/deck preparation and patching. Resin/sand patching mix provides a fast-set time of approximately 45 minutes and does not require surface grinding.
          2.Primer/sand mix is an alternative substrate leveling and patching material over horizontal surfaces. Primer/sand patching mix provides a set time of approximately 1 hour, and does not require surface grinding. Primer/sand mix is typically applied in conjunction with general surface priming.
          3.Substrate Leveling and Patching: Substrate conditions are to be evaluated by the Contractor, the Owner, or his designated Representative, and Membrane manufacturer. Perform leveling and patching operations as follows:
          a.Level uneven horizontal and low-slope surfaces with a leveling mixture of (PMMA) methyl-methacrylate Alsan RS 233 Self-Leveling Mortar (depth < 1/2 inch, (13 mm)) resin. Depths < 1/2 inch (13 mm) shall be build up in separate layers. Spread and plane this resin with a squeegee, trowel and/or roller to achieve a flat surface. Spike roller may be used to smooth out the surfaces.
          b.Fill cavities on horizontal and low-slope surfaces with a patching mixture of (PM MA) methyl-methacrylate primer and approved kiln-dried sand in a 1:3 primer to sand ratio by volume or with (PM MA) methyl-methacrylate Alsan RS Paste using trowels to apply the resin mortar in place and achieve flat surface.
          c.Fill cavities on sloped and vertical surfaces with (PMMA) methyl-methacrylate Alsan RS Paste using trowels to apply the resin mortar in place and achieve flat surface.
          d.Silica sand shall be kept absolutely dry during storage and handling.
          e.Any surface to be leveled or filled shall first be primed with an appropriate (PMMA) methyl-methacrylate primer and all Alsan RS resin mortars shall be placed in lifts no greater than the maximum thickness indicated by the manufacturer.
          ** NOTE TO SPECIFIER ** Joints, cracks, and fractures may telegraph through the waterproofing membrane.
          4.Joint and Crack Preparation: Joints, cracks and fractures in the structural deck/substrate shall be prepared prior to installation of the waterproofing membrane.
          a.Moving Cracks: Determine that crack is moving. Clean out crack by brushing and oil-free compressed air. Fill crack with (PMMA) methyl-methacrylate Alsan RS Paste. Allow for a minimum of one hour cure or as required by product manufacturer. Apply resin and 4 inches (102 mm) wide strip of membrane (resin and fleece) in strict accordance with Membrane manufacturer's written instructions.
          b.Non-Moving Cracks: Determine that crack is non-moving. Clean out crack by brushing and oil-free compressed air. Fill crack with (PM MA) methyl-methacrylate Alsan RS Paste. Allow for a minimum of one hour cure or as required by product manufacturer.
          ** NOTE TO SPECIFIER ** SEBS and Urethane System. Delete if not required.
 
          J.Surface Preparation for Recoating:
          ** NOTE TO SPECIFIER ** Delete if not required.
          1.Single Ply Membrane: Any deteriorated roofing membrane being coated shall first be repaired using like membrane to the existing roof system. Any roof system with excess moisture in the insulation shall have the wet areas removed and replaced. Consult Manufacturer regarding any moisture issue.
          ** NOTE TO SPECIFIER ** Delete if not required.
          2.Metal Roofing: Power wash with minimum 2500 psi (17,000 kPa) spray rig. Replace any material that is rusted through. Tighten or replace fasteners as needed.
          3.Before application of the roofing membrane do all repairs using Alsan Flashing and Alsan Polyfleece. Make sure that area to be repaired is clean, dry and free of debris and is built up to the same level as the surrounding roof surface. As necessary prime area with Alsan H80 and apply an even fleece coat of Alsan Flashing. Place Alsan PolyFleece in wet liquid and immediately apply a top fleece coat of Alsan Flashing wet-on-wet to ensure complete saturation of the fleece. Remove all voids, wrinkles, fishmouths, trapped air, etc. Base and top fleece coats shall extend a minimum of 2 inches (51 mm) past the perimeter of the repaired area. If the repair is to a crack, split or similar a minimum reinforcement shall be 4 inches (102 m) wide.
          a.Base Fleece Coat: Minimum consumption of 32 wet mils (0.8 mm) depending on surface texture
          b.Top Fleece Coat: Minimum consumption of 32 wet mils (0.8 mm) depending on surface texture.
 
          3.4WOOD NAILER LOCATION AND INSTALLATION
 
          A.Install pressure-treated wood nailers as specified, or as required by the Membrane manufacturer.
 
          B.Secure Wood Nailer: Wood nailers shall be firmly fastened to the deck. The wood nailer attachment shall be able to resist a minimum force of 200 lbs. per lineal foot (300 kg/meter), in any direction. Mechanically fasten wood nailers as required to resist a force of 200 lbs. per lineal foot (300 kg/meter), but with no less than 5 fasteners per 8 feet (2438 mm) or 6 fasteners per 10 feet (3048 mm) length of nailer. Refer to current FM Loss Prevention Bulletin 1-49 for additional attachment recommendations.
          ** NOTE TO SPECIFIER ** Option. Delete if not required.
 
          3.5MODIFIED BASE SHEET APPLICATION
 
          A.Adhere a modified bitumen base sheet to the substrate before application of the liquid system. Use of a modified base sheet shall be approved by manufacturer in writing. Prime surfaces to receive the base sheet with Elastocol 500 or 600c @ 100-125 sf/gal (2.4 to 3 sq. m/l) and allow to cure.
 
          B.Torch or self-adhere the specified modified bitumen base sheet to the primed deck. Side laps to be a minimum of 3 inches (76 mm) and end laps a minimum of 6 inches (152 mm). If a venting base sheet is used, ensure that rolls are properly aligned and installed to allow moisture movement. Consult manufacturer for all requirements and proper installation techniques.
 
          3.6INSULATION/COVER BOARD INSTALLATION
 
          A.Insulation and cover board shall be installed in accordance with the insulation/cover board manufacturer's current published specifications and recommendations for use with adhered roofing.
          ** NOTE TO SPECIFIER ** An increased amount of roofing adhesive and/or fasteners may be required at the perimeter band of the roof, depending upon parapet and building height. Refer to the Roof Membrane Manufacturer Application Rate Chart for recommended application rates.
 
          B.Install only as much insulation and cover board as can be primed, sealed, and protected before the end of the day's work or before the onset of inclement weather.
 
          C.Neatly fit insulation/cover board to all penetrations, projections, and nailers. Insulation shall be loosely butted, with gaps not greater than 1/4 inch (6 mm). All gaps greater than 1/4 inch (6 mm) shall be filled with acceptable insulation. Cover board shall be loosely butted, with gaps not greater than 1/4 inch (6 mm). All gaps lesser than 1/8 inch (3 mm) shall be filled with primer; all gaps greater than 1/4 inch (6 mm) shall be filled with (PM MA) methyl-methacrylate Alsan RS Paste.
 
          D.Strip all cover board joints with four inch (102 mm) wide strip of flashing membrane. Under no circumstances shall the membrane be left unsupported over a space greater than 1/4 inch (6 mm).
 
          E.When installing multiple layers of insulation, all joints between succeeding layers shall be staggered a minimum of 6 inches (152 mm) in each direction.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          F.Steel Deck Substrates: Place boards perpendicular to steel deck flutes with edges over flute surface for bearing support. Edges shall be checked so that no edges are left substantially unsupported along the flutes.
 
          G.Insulation shall be feathered or tapered to provide a sump area a minimum of 36 inches by 36 inches (914 mm by 914 mm) where possible at all drains. Taper insulation around roof drains so as to provide proper slope for drainage. In areas where feathered or tapered insulation leaves insulation core exposed, cover with an appropriate cover board or base sheet/cap sheet assembly to provide a sound and smooth substrate surface.
 
          H.Place the constant thickness first layer and the tapered thickness insulation to the required slope pattern in accordance with insulation manufacturer's instructions.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          I.Mechanical Attachment: Follow insulation/cover board and fastener manufacturers' recommendations for the appropriate fastener and plate type, size and length. Reference FM approvals for fastening patterns that satisfy FM wind uplift requirements. Typical application is one fastener and plate per 2 square feet (0.2 sq. meters) of insulation/cover board to be attached. Note: additional fasteners are required in the corner and perimeter regions of the roof. Secure insulation/cover board in accordance with approval requirements.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          J.Polyurethane Adhesive Attachment: Follow manufacturers' recommendations for the appropriate adhesive application rate and procedures. Under normal application rate, dispense the first bead 3 inches (76 mm) inside the outside edges of the insulation/cover board to be attached, with sequential beads equidistant. Place the boards onto the roofing adhesive beads. Walk on the boards to spread the roofing adhesive for maximum contact. Periodically walk on the boards until firmly attached. Reference FM approvals for adhesive application patterns that satisfy FM wind uplift requirements. Typical application is a 3/4 inch (19 mm) bead of roofing adhesive at a rate of one lineal foot per square foot of insulation/cover board to be attached.
          ** NOTE TO SPECIFIER ** Note: additional adhesive is required in the corner and perimeter regions of the roof. Secure insulation/cover board in accordance with approval requirements.
 
          K.Asphalt Adhesive Attachment: Follow insulation manufacturer's recommendations for the appropriate asphalt application rate and application procedure. Set each insulation panel layer in a full mopping of hot steep asphalt (Type III) at the recommended EVT range. Walk on the boards to spread the roofing adhesive for maximum contact. Periodically walk on the insulation boards until firmly attached. Reference FM approvals for asphalt application rates that satisfy FM wind uplift requirements. Typical application is 25 lb per 100 square feet (1.2 kg/sq. m) of insulation board to be attached. Secure insulation in accordance with approval requirements.
          ** NOTE TO SPECIFIER ** PMMA System Primer. Delete if not required.
 
          3.7PRIMER APPLICATION
 
          A.General:
          1.Mix and apply two-component (PMMA) methyl-methacrylate primer and epoxy primer in strict accordance with written instructions of Membrane Manufacturer. Use only proprietary materials, as supplied by the membrane manufacturer.
          2.The substrate surface shall be dry, with any remaining dust or loose particles removed using clean, dry, oil-free compressed air, industrial vacuum, cloth wipe or a combination of methods.
          3.Do not install primer on any substrate containing newly applied and/or active asphalt, coal-tar pitch, creosote or penta-based materials unless approved in writing by Membrane Manufacturer. Some substrates may require additional preparation before applying primer.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          B.Mixing of Standard Two-Component (PMMA) Methyl-Methacrylate Primers:
          1.Premix primer thoroughly with a spiral agitator or stir stick. Add pre- measured catalyst amount into mixed primer container and mix the components for approximately 2 minutes with a clean spiral agitator on slow speed or stir stick without creating any bubbles or streaks. DO NOT AERATE. The primer solution shall be a uniform color, with no light or dark streaks present.
          2.Do not thin primer. Determine required primer coverage for each substrate material/condition and apply in strict accordance with written instructions of Membrane Manufacturer.
          3.Mix only that amount of primer that can be used within 15 minutes.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          C.Mixing of Standard Two-Component Epoxy Primer:
          1.Mix A and B components together with a spiral agitator or stir stick. Use slow speed. DO NOT AERATE. The primer solution shall be a uniform color, with no light or dark streaks present.
          2.Do not thin primer. Determine required primer coverage for each substrate material/condition and apply in strict accordance with written instructions of Membrane Manufacturer.
          3.Mix only that amount of primer that can be used within 15 minutes.
 
          D.Application of Primers:
          1.Roll or brush the primer evenly onto the surface to fully saturate the substrate in one application. Do not allow primer to pond or collect in low areas.
          2.Apply primer only up to the edge of the membrane flashing terminations. Primer application past the membrane terminations requires surfacing with an approved material.
          ** NOTE TO SPECIFIER ** Delete if not required.
          3.Apply PMMA primer at the minimum rate of approximately 0.037 kg/sf (0.4 kg/sq. m).
          a.For (PMMA) methyl-methacrylate primer applications over cementitious substrates where protection from substrate wetness is required, apply primer coat at a heavier application rate until pore saturation is achieved.
          b.Allow standard (PM MA) methyl-methacrylate primers to cure for a minimum of thirty minutes before membrane application.
          ** NOTE TO SPECIFIER ** Delete if not required.
          4.Apply epoxy primer at the minimum rate of approximately 0.028 kg/sf (0.3 kg/sq. m):
          a.For all Alsan EPR primer applications, apply kiln-dried sand into the final coat of Alsan EPR primer while still wet at the rate of 30 lb per 100 square feet (1.5 kg/sq. meter). Use quartz size # 0 (0.4 to 0.8 mm).
          b.Allow epoxy-based quick-dry primers to cure for a minimum of one hour before membrane application. Membrane shall be applied to primer only when completely dry and without tack.
          5.Premature exposure to moisture may require removal and application of new primer. DO NOT apply new primer over exposed primer older than six months, primer prematurely exposed to moisture, or primer used as temporary waterproofing, unless approved in writing by the Membrane Manufacturer.
 
          E.Disposal of Resin:
          1.Cured resin may be disposed of in standard landfills. This is accomplished by thoroughly mixing resins with Catalyst Powder.
          2.Uncured resin is considered a hazardous material and shall be handled as such, in accordance with local, state and federal regulation. Do not throw uncured resin away.
          ** NOTE TO SPECIFIER ** PMMA System. Delete if not required.
 
          3.8FLASHING APPLICATION
 
          A.General:
          1.Install cold fluid-applied reinforced (PM MA) methyl-methacrylate waterproofing flashing system in accordance with the requirements/recommendations of the membrane manufacturer and as depicted on standard drawings and details. Provide system with base flashing, edge flashing, penetration flashing, counter flashing, and all other flashings required for a complete watertight system.
          2.Wherever possible, install the flashings before installing the field membrane to minimize foot traffic over newly installed field membrane.
          3.All membrane flashings shall be installed concurrently with the waterproofing membrane as the job progresses. Temporary flashings are not allowed without prior written approval from the membrane manufacturer. Shall any water penetrate the new waterproofing membrane because of incomplete flashings; the affected area shall be removed and replaced at the installer's expense.
          4.Provide a minimum vertical height of 8 inches (203 mm) for all flashing terminations. Flashing height shall be at least as high as the potential water level that could be reached as a result of a deluging rain and/or poor slope. Do not flash over existing through-wall flashings, weep holes and overflow scuppers.
          5.All flashings shall be terminated as required by the membrane manufacturer.
          6.Alsan RS 230 Flash resin is alkalinity resistant. Additional bond/wearing layer consisting of one application of Alsan RS 230 Flash on vertical surfaces and one application of approved broadcast mineral aggregate surfacing shall be applied wherever stone, concrete, or masonry elements will be placed directly over the flashing.
 
          B.Application of Resin/Fleece:
          1.Apply mixed resin to the prepared surface at the approximate rate of 0.19 kg/sf (2.0 kg/sq. m). The resin shall be rolled or brushed liberally and evenly onto the surface using a broad, even stroke. Cover one working area at a time, between 2 to 5 sf (0.19 to 0.46 sq. m).
          2.Roll out dry polyester fleece onto the liquid resin mix, making sure the SMOOTH SIDE IS FACING UP (natural unrolling procedure), avoiding any folds and wrinkles. The fleece will begin to rapidly saturate with the liquid resin mix. Use a medium nap roller or brush to work the resin into the fleece, saturating from the bottom up, ensuring that all angle changes points are tight and not bridged and eliminating air bubbles, wrinkles, etc. The appearance of the saturated fleece shall be light opaque amber with no white spots. White spots are indications of unsaturated fleece or lack of adhesion. It is important to correct these faults before the resin cures.
          3.Apply additional liquid resin mix on top of fleece at the approximate rate of 0.12 kg/sf (1.3 kg/sq. m) to finish the saturation of the fleece. Roll this final coating into the fleece, which will result in a glossy appearance. The fleece can only hold so much resin and all excess shall be rolled forward to the unsaturated fleece, eliminating ponding or excessive build-up of the resin. Any excess resin left on the top of the fleece will weather and peel off. The correct amount of resin will leave no whiteness in fleece and there will be a slightly fibrous surface texture. The final resin coating shall be smooth and uniform.
          4.Prevent contact between mixed/unmixed resin and new/existing membrane. If any unmixed resin contacts membrane surface remove immediately and clean thoroughly with a cloth rag.
          5.At all fleece seams, allow a 2 inches (51 mm) overlap for all side joints and a 4 inches (102 mm) overlap for all inside and outside corner overlaps.
          6.At membrane tie-offs, clean in-place membrane with Alsan RS Cleaner once resin has cured. Allow cleaner to fully evaporate before application of new resin.
 
          C.Metal Flashing:
          1.Metal flashings shall be fabricated in accordance with the current recommendations of SMACNA and in accordance with standard drawings and project details.
          2.Metal flashing flanges to which membrane is to be bonded shall be a minimum of four (4) inches in width, and secured to the substrate six inches (152 mm) on center staggered with fasteners appropriate to the substrate type. The flanges shall be provided with a roughened surface that has been cleaned of all oil and other residue.
          3.Metal edges that will be overlaid with membrane shall be provided with a 1/4 inch (6 mm) minimum hemmed edge.
          4.Apply primer, resin and fleece to metal flange, extending membrane to outside face of metal edging, and to vertical face of metal base/curb flashing.
 
          D.Membrane Flashing:
          1.Membrane flashings shall be fabricated with primer appropriate for the substrate surface, resin of the same base chemical type as the field membrane, and fleece of the same weight as the field membrane unless specified otherwise.
          2.Primer, resin, and fleece mixing and application methods as specified for field membranes are also suitable for membrane flashing.
          3.Fleece shall overlap 2 inches (51 mm) minimum for all joints. Fleece shall be cut neatly to fit all flashing conditions without a buildup of multiple fleece layers. Work wet membrane with a brush or roller to eliminate blisters, openings, or lifting at corners, junctions, and transitions.
 
          E.Pipes, Conduits, and Unusually Shaped Penetrations:
          1.Flash all penetrations using cold fluid-applied reinforced (PMMA) methyl-methacrylate waterproofing membrane. Flashing material shall be the same resin used in the field membrane with fleece reinforcement.
          2.Flashing is typically constructed as a two part assembly consisting of a vertical wrap and a horizontal target patch. There shall be a minimum of a two inches (51 mm) overlap between vertical and horizontal flashing components.
 
          F.Drains and Scuppers:
          1.Acceptable drain and scupper materials are cast iron, cast aluminum, and copper.
          2.Connect new drains and scuppers to existing storm sewer system.
          3.Alternatively, replace all broken or damaged parts of existing drains and scuppers, or provide and install an acceptable insert.
          4.Flash drains and scuppers using cold fluid-applied reinforced (PMMA) methyl-methacrylate waterproofing membrane. Flashing material shall be the same resin used in the field membrane with fleece reinforcement.
          5.Flashing material shall extend four inches (102 mm) minimum onto drain, scupper, or insert flange.
          6.Install clamping ring if provided as part of the drain or scupper design. Install a strainer basket to prevent debris from clogging the drainage line.
 
          G.Hot Stacks:
          1.Protect the membrane components from direct contact with steam or heat sources when the in-service temperature exceeds 150 degrees F (66 degrees C). In all such cases flash to an intermediate "cool" sleeve.
          2.Fabricate "cool" sleeve in the form of a metal cone using galvanized metal in accordance with Membrane manufacturer's details.
          3.Flash all penetrations using cold fluid-applied reinforced (PMMA) methyl-methacrylate waterproofing membrane. Flashing material shall be the same resin used in the field membrane with fleece reinforcement.
          4.Flashing is typically constructed as a two part assembly consisting of a vertical wrap and a horizontal target patch. There shall be a minimum of a two inches (51 mm) overlap between vertical and horizontal flashing components.
 
          H.Flexible Penetrations:
          1.Provide a weather tight gooseneck of round cross-section for each penetration or group of penetrations. Set in water cut-off mastic and secure to the structural substrate.
          2.Acceptable gooseneck material is copper, of a sheet weight appropriate for the application.
          3.Flash all penetrations using cold fluid-applied reinforced (PMMA) methyl-methacrylate waterproofing membrane. Flashing material shall be the same resin used in the field membrane with fleece reinforcement.
          4.Flashing is typically constructed as a two part assembly consisting of a vertical wrap and a horizontal target patch. There shall be a minimum of a two inches (51 mm) overlap between vertical and horizontal flashing components.
 
          I.Walls, Curbs and Base Flashings:
          1.Wall, curb and base flashings shall be installed to solid substrate surfaces only. Adhering to gypsum-based panels, cementitious stucco, synthetic stucco, wood or metal siding, and other similar materials is not acceptable.
          2.Flash all walls, curbs and base flashings using cold fluid-applied reinforced (PMMA) methyl-methacrylate waterproofing membrane. Flashing material shall be the same resin used in the field membrane with fleece reinforcement.
          3.Reinforce all transition locations and other potential wear areas with a four inches (102 mm) wide polyester fleece bottom layer evenly positioned over the transition prior to installing the exposed flashing layer.
          4.Reinforce all inside and outside corners with a four inches (102 mm) diameter conical piece of fleece prior to installing the exposed flashing layer.
          5.All pins, dowels and other fixation elements shall be flashed separately with a vertical flashing component prior to installing the exposed flashing layer.
          6.Extend flashing a minimum of four inches (102 mm) onto the field substrate surface.
 
          J.Drip Edges and Gravel Stops:
          1.Metal drip edges and gravel stops shall be installed to solid substrate surfaces only. Securement to gypsum-based panels, cementitious stucco, synthetic stucco, wood or metal siding or coping, and other similar materials are not acceptable.
          2.Flash all drip edges and gravel stops by extending the field membrane all the way to the edge of the exposed face prior to installing the metal edging. Strip in the metal flange with a separate 8 inches (203 mm) wide strip of membrane adhered to both the securement flange and to the field membrane.
          3.For conditions where water infiltration behind the exposed drip edge or gravel stop face is possible, install a separate polyester fleece bottom layer positioned behind the face area and extending a minimum of four inches (102 mm) past the securement flange onto the field substrate prior to installing the drip edge or gravel stop.
 
          K.Field Fabricated Control or Expansion Joint Flashing:
          1.Control or expansion joints in excess of two inches (51 mm) in width require the use of a separate engineered joint system.
          2.Control or expansion joints two inches (51 mm) or less in width may be flashed with two layers of cold fluid-applied (PM MA) methyl- methacrylate waterproofing membrane and a compressible foam or rubber insert. Use polyester reinforcing fleece bottom and top layer.
          3.Grind or otherwise bevel the inside edges of the joint opening to provide a smooth transition edge for the fleece.
          4.Flashing typically consists of polyester reinforcing fleece bottom layer looped into the joint as a cradle, a compressible foam or rubber insert at 25% compression fitted into the joint, and a polyester fleece top layer applied over the joint. Extend both fleece layers four inches (102 mm) minimum onto the field substrate on both sides of the joint.
          5.Apply the field membrane over the entire joint area.
 
          L.Electrical Conduit, Gas Lines and Lightning Protection:
          1.Supports for electrical conduit and gas lines greater than one inch (25 mm) in diameter require the use of a separate engineered support system.
          2.Supports for electrical conduit and gas lines one inch (25 mm) or less in diameter, and bases for lightning protection rods and cable, can be adhered directly to the membrane surface with two-component Alsan RS Paste or a single-component, high quality polyurethane sealant supplied by membrane manufacturer.
          ** NOTE TO SPECIFIER ** PMMA System. Delete if not required.
 
          3.9LIQUID MEMBRANE APPLICATION
 
          A.General:
          1.Mix and apply cold fluid-applied reinforced (PMMA) methyl-methacrylate waterproofing membrane in strict accordance with written instructions of Membrane Manufacturer. Use only proprietary membrane resins and materials, as supplied by the membrane manufacturer.
          2.The primed substrate surface shall be dry, with any remaining dust or loose particles removed using clean, dry, oil-free compressed air, industrial vacuum, cloth-wipe or a combination.
          3.Two-part (PMMA) methyl-methacrylate resins cure most quickly and completely when exposed to UV light. For concealed and/or interior applications where exposure to natural UV light cannot be obtained, exposure to a UV light source or a supplemental source of hot air blown over the membrane surface will improve membrane cure.
          4.Protect all areas where membrane has been installed. Do not work off installed membrane during application of remaining work before three hours of curing. Movement of materials and equipment across installed membrane is not acceptable. If movement is necessary, provide complete protection of affected areas.
          5.Closely follow the Membrane Manufacturer's recommendation for hot and cold weather application. Monitor surface and ambient temperatures, including the effects of wind chill.
 
          B.Mixing of Resin:
          1.Mix resin with a spiral agitator for a minimum of 2 minutes until the liquid has a uniform color.
          2.Add the pre-measured Catalyst Powder to resin and mix with the same agitator for 2 minutes or until the powder is completely mixed. The catalyst is completely dissolved when there are no white specs remaining.
 
          C.Application of Resin/Fleece:
          1.Apply mixed resin to the prepared surface at the approximate rate of 0.19 kg/sf (2.0 kg/sq. m). The resin shall be rolled or brushed liberally and evenly onto the surface using a broad, even stroke. Cover one working area at a time, between 15 to 20 sf (1.4 to 1.9 sq. m).
          2.Roll out dry polyester fleece onto the liquid resin mix, making sure the SMOOTH SIDE IS FACING UP (natural unrolling procedure), avoiding any folds and wrinkles. The fleece will begin to rapidly saturate with the liquid resin mix. Use a medium nap roller or brush to work the resin into the fleece, saturating from the bottom up, and eliminating air bubbles, wrinkles, etc. The appearance of the saturated fleece shall be light opaque amber with no white spots. White spots are indications of unsaturated fleece or lack of adhesion. It is important to correct these faults before the resin cures.
          3.Apply additional liquid resin mix on top of fleece at the approximate rate of 0.12 kg/sf (1.3 kg/sq. m) to finish the saturation of the fleece. Roll this final coating into the fleece, which will result in a glossy appearance. The fleece can only hold so much resin and all excess shall be rolled forward to the unsaturated fleece, eliminating ponding or excessive build-up of the resin. Any excess resin left on the top of the fleece will weather and peel off. The correct amount of resin will leave no whiteness in fleece and there will be a slightly fibrous surface texture. The final resin coating shall be smooth and uniform.
          4.Prevent contact between mixed/unmixed resin and new/existing membrane. If any unmixed resin contacts membrane surface remove immediately and clean thoroughly with a cloth rag.
          5.At all fleece seams, allow a 2 inches (51 mm) overlap for all side joints and a 4 inches (102 mm) overlap for all end joints.
          6.At membrane tie-offs, clean in-place membrane with Alsan RS Cleaner once resin has cured. Allow cleaner to fully evaporate before application of new resin.
          7.Alsan RS 230 Field resin is alkalinity resistant. Additional bond/wearing layer consisting of one application of Alsan RS 230 Field on horizontal surfaces and one application of approved broadcast mineral aggregate surfacing shall be applied wherever stone, concrete, or masonry elements will be placed directly over the flashing.
          ** NOTE TO SPECIFIER ** Urethane System. Delete if not required.
 
          3.10PRIMER APPLICATION
 
          A.Priming is not normally required on clean SBS modified bitumen, smooth BUR and most metals.
          1.Apply Alsan H80 prime at 5 to 6 wet mils (0.13 to 0.16 mm). Amount of primer needed is affected by surface roughness and porosity. The primer when applied shall have a glossy appearance. Use of H80 will promote better adhesion and can help reduce the amount of base coat needed.
          2.Any aged roof, after substrate preparation, will require priming particularly where ponded water or residual dirt has been present.
          3.Primers shall be allowed to dry for 6 to 12 hours depending on environmental conditions prior to the Alsan Flashing Application. Primed substrates may only be exposed for a period of 24 hours prior to the application of Alsan Flashing or they shall be re primed.
          ** NOTE TO SPECIFIER ** Urethane System. Delete if not required.
 
          3.11FLASHING APPLICATION
 
          A.For all flashings, penetrations, drains, metal edges, etc. apply an even base fleece coat of Alsan Flashing resin with a brush or roller. Embed Alsan PolyFleece in this layer and immediately apply a top fleece coat of Alsan Flashing wet-on-wet. Cut Alsan PolyFleece 4 inches (102 mm) wider than the split, seam or transition in each direction. Ensure that polyester reinforcement is fully saturated and does not have voids, fish mouths, trapped air, or wrinkles. To the cured base coat apply an Alsan Flashing finish coat. Broadcast to excess ceramic granules into the finish coat. As an option in place of the granules, allow the finish coat of Alsan Flashing to cure 9-12 hours and then apply a coat of colored Alsan 310.
          1.Base Fleece Coat: Minimum consumption of 32 wet mils (0.81 mm) depending on surface texture.
          2.Top Fleece Coat: Minimum consumption of 32 wet mils (0.81 mm) depending on surface Texture
          3.Finish Coat: Minimum consumption of 32 wet mils (0.81 mm) depending on surface texture.
          ** NOTE TO SPECIFIER ** Delete if not required.
          4.Granules: Prior to the topcoat beginning to cure, broadcast to rejection Soprema Ceramic Granules. Color is to be selected by the Owner from the standard palate of colors.
          ** NOTE TO SPECIFIER ** Urethane System. Delete if not required.
 
          3.12FIELD APPLICATION
 
          A.Apply an even base coat of Alsan Flashing resin with a squeegee or roller over the entire roof surface. Allow this coat to cure 9 to12 hours and then apply a finish coat of Alsan Flashing. Broadcast to excess ceramic granules into the finish coat. As an option in place of the granules, allow the finish coat to cure 9 to12 hours and then apply a coat of colored Alsan 310. Allow Alsan 310 to cure 24 hours before trafficking.
          1.Base Coat: Minimum consumption of 2.0 to2.5 gal/sq (32 wet mils) (0.8 mm) depending on surface texture.
          2.Finish Coat: Minimum consumption of 2.0 to2.5 gal/sq (32 wet mils) (0.8 mm) depending on surface texture.
          3.Granules: Prior to the topcoat beginning to cure, broadcast to rejection Soprema Ceramic Granules, color to be selected by the owner, from a standard palate of colors.
          4.Optional Alsan 310 Coat: Minimum consumption 1.5 gal/sq (24 wet mils) (0.6 mm). Color is to be selected by the owner from the standard palate of colors.
 
          B.If the Alsan Membrane Base Coat is left exposed to the elements for more than seven days prior to the next application of Alsan Flashing Membrane it shall be primed at a rate of 200 to 250 sf/gal. (2 to 3 wet mils) (.05 to .08 mm).
 
          C.Membrane Application: Install roofing in accordance with roofing system manufacturer's current published instructions and the following requirements.
 
          D.Aesthetic Considerations: The overall aesthetically pleasing appearance of the finished roof is a standard requirement for this Project. Make necessary preparations, utilize recommended application techniques, apply the specified materials and exercise care in ensuring that the finished application is acceptable to the Owner.
 
          E.General Installation:
          1.Contractor shall prevent overspray, and be responsible for parking lot areas and/or adjoining areas not part of this contract.
          2.Contractor shall be responsible for sealing, as required, all openings that may allow coating migration or dripping, i.e. pitch dams, envelopes, and filler strips.
          3.Correct all errors in application the same work day they occur, including bare spots, improper application, physical damage and all work not meeting specifications.
          4.Protect adjacent areas and materials from damage by coating operations with tarpaulin or other durable materials.
          5.Apply materials in straight, smooth lines without smears, overlaps, or splatter on adjoining materials. Complete roofing operations promptly.
          ** NOTE TO SPECIFIER ** SEBS System. Delete if not required.
 
          3.13COATING INSTALLATION
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          A.Metal Roof Application:
          1.Apply ALSAN MBSP MASTIC to all reseated fastener heads and with reinforcement at questionable seams.
          2.Apply an even layer of ALSAN MBSP GREY (1.5 gal/100 sf minimum) with a spray rig or lambswool roller. Can be walked upon/next coat applied after approximately 1 hour.
          3.Apply ALSAN MBSP WHITE (1.5 gal/100 sf minimum) with a spray rig or lambswool roller.
          4.For areas with translucent or transparent panels or glass, mask these areas during ALSAN MBSP GREY AND ALSAN MBSP WHITE applications. Apply two applications of ALSAN MBSP CLEAR (1.5 GAL/100 sf minimum) with a spray rig or roller. Overlap previously applied ALSAN MBSP WHITE by at least two inches (51 mm) to ensure proper tie-in. Can be walked upon after approximately 1 hour.
          ** NOTE TO SPECIFIER ** Delete if not required.
 
          B.Single Ply Roofing Application:
          1.Apply an initial "tack" layer of ALSAN MBSP GREY (0.5 gal/100 sf minimum) with a spray rig or lambs wool roller. Spraying is the preferred method of application. If rolling, do not pour liquid and spread; dip roller into pail and roll out. Can be walked upon/next coat applied after approximately 1 hour.
          2.Apply an even layer of ALSAN MBSP GREY (1.25 gal/100 ft2 min.) with a spray rig or lambs wool roller. Can be walked upon/next coat applied after approximately 1 hour.
          3.Apply ALSAN MBSP WHITE (1.25 gal/100 ft2 min.) with a spray rig or lambs wool roller. Can be walked upon after approximately 1 hour.
 
          3.14WEARING AND SURFACING
 
          A.Aesthetic Color Finish Coating
          1.Where specified, provide and install Membrane Manufacturer's approved two-component (PM MA) methyl-methacrylate based color finish surfacing coating applied over clean, fully cured membrane.
          2.Premix Alsan RS 288 Finish resin thoroughly for approximately 2 minutes with a clean spiral agitator on slow speed or stir stick without creating any bubbles or streaks until material is consistent in color.
          3.Add the pre-measured Catalyst Powder to resin and mix with the same agitator for 2 minutes or until the powder is completely mixed. The catalyst is completely dissolved when there are no white specs remaining.
          4.Apply Alsan RS 288 Finish coating at a rate of approximately 0.028 kg/sf (0.3 kg/m2). Product shall be applied with a lambswool roller to achieve a smooth and level surface. Avoid any traffic for a minimum of one (1) hour to allow for surfacing to cure.
          ** NOTE TO SPECIFIER ** Optional. Delete if not required.
          5.Alsan RS Deco Chips: Apply Alsan RS 288 Finish coating at a rate of approximately 0.056 kg/sf (0.6 kg/sq. m). Product shall be applied with a lambs wool roller to achieve a smooth and level surface. Broadcast the specified Alsan RS Deco Chips into the wet color finish by hand or hopper spray gun at a minimum rate of 0.019 kg/sf (0.2 kg/sq. m). Allow to cure and sweep away excess chips. Avoid any traffic for a minimum of one hour to allow for surfacing to cure.
 
          B.Aggregate Walkway Slip-Resistant Finish Surfacing:
          1.Where specified, provide and install Membrane Manufacturer's approved two-component (PMMA) methyl-methacrylate based finish surfacing coating with slip-resistant aggregate additive applied over clean, fully cured membrane. As necessary tape areas to receive surfacing.
          2.Premix all Alsan RS resins thoroughly for approximately 2 minutes with a clean spiral agitator on slow speed or stir stick without creating any bubbles or streaks until material is consistent in color.
          3.Add the pre-measured Catalyst Powder to resin and mix with the same agitator for 2 minutes or until the powder is completely mixed. The catalyst is completely dissolved when there are no white specs remaining.
          4.Apply Alsan RS 288 Finish resin at a minimum rate of approximately 0.065 kg/sf (0.7 kg/sq. m). Product shall be applied with a lambswool roller to achieve a smooth and level surface. Broadcast optional kiln-dried sand or colored quartz aggregate surfacing at approximate rate of 0.46 kg/sf; 1.0 lb/sf; (5.0 kg/sq. m) or as recommended by manufacturer into wet surface of coating to provide slip-resistant protective surfacing. Avoid any traffic for a minimum of two hours to allow for surfacing to cure. Remove all excess and loose quartz surfacing with broom, vacuum and/or oil-free blower. Seal natural quartz silica aggregate surfacing with an additional Alsan RS 288 Finish pigmented coating application at a rate of approximately 0.065 kg/sf (0.7 kg/sq. m). Seal colored quartz silica aggregate surfacing with an additional Alsan RS 281 Finish translucent coating application at a rate of approximately 0.065 kg/sf (0.7 kg/sq. m). Product shall be applied with a rubber flat blade squeegee and lambswool roller to achieve a uniform surface. Avoid any traffic for a minimum of one (1) hour to allow for coating to cure.
          ** NOTE TO SPECIFIER ** Optional. Delete if not required.
          5.Textured Surfacing: Apply Alsan RS 290 Textured Finish at a minimum rate of approximately 0.19 kg/sf (2.0 kg/sq. m). Product shall be applied with a smoothing trowel and/or a lambs wool roller to achieve a uniform surface. Avoid any traffic for a minimum of one hour to allow for coating to cure.
          ** NOTE TO SPECIFIER ** Optional. Delete if not required.
          6.Alsan RS Deco Chips: Apply Alsan RS 288 Finish coating at a rate of approximately 0.056 kg/sf (0.6 kg/sq. m). Product shall be applied with a lambs wool roller to achieve a smooth and level surface. Broadcast the specified Alsan RS Deco Chips into the wet color finish by hand or hopper spray gun at a minimum rate of 0.019 kg/sf (0.2 kg/sq. m). Allow to cure and sweep away excess chips. Avoid any traffic for a minimum of one hour to allow for surfacing to cure.
          ** NOTE TO SPECIFIER ** Optional. Delete if not required.
 
          C.Pavers:
          1.As an option to applying Alsan RS aggregate surfacing for walkable areas, install concrete or specified pavers and pedestals (as required). Install a piece of modified membrane or similar material under pavers or pedestals to protect the Alsan RS membrane. Pavers shall be spaced to allow for the passage of water. Consult specifier or manufacturer for requirements and layout.
 
          3.15TEMPORARY CLOSURES & WATERSTOPS
 
          A.Contractor shall be responsible to ensure that moisture does not damage any completed section of the new waterproofing system. Completion of flashings, terminations, and temporary closures shall be completed as required to provide a watertight condition. All temporary closures shall be made as recommended or required by the membrane manufacturer.
 
          3.16PROTECTION
 
          A.A. Upon completion of waterproofing and flashings (including all associated work), institute appropriate procedures for surveillance and protection of waterproofing during remainder of construction period. Protect all areas where membrane has been installed.
 
          3.17CLOSEOUT
 
          A.Correction of Work:
          1.Work that does not conform to specified requirements including tolerances, slopes, and finishes shall be corrected and/or replaced. Any deficiencies of membrane application, termination and/or protection as noted during the Membrane Manufacturer's inspections shall be corrected and/or replaced at Contractor's expense.
 
          B.Clean-Up:
          1.Site clean-up, including both interior and exterior building areas that have been affected by construction, shall be restored to preconstruction condition.
 
         
END OF SECTION