MasterFormat: 2020
Download this Security Communications System - ICX500 Specification for   WORD | WORD-Canadian | WP | RTF | TEXT
Find over 500 more construction specifications | Arcat.com
         
Zenitel Security Communications System - ICX500
 
         
SECTION 28 15 23.50
 
         
SECURITY COMMUNICATIONS SYSTEM - ICX500
 
         
 
         
Copyright 2019 - 2022 ARCAT, Inc. - All rights reserved

          ** NOTE TO SPECIFIER ** Zenitel; voice communication system.
This section is based on the products of Zenitel, which is located at:

,
Email: request info
Web: https://www.zenitel.com
[ Click Here ] for additional information.
As a leading provider in Intelligent Communications over IP, Zenitel is the proven and preferred audio and data communication choice for environments that require the protection of human life, property, assets and/or the management of critical activities. Our primary system offering is within Public Address, Intercom and Radio. Our key markets include Building Security, Public Safety, Transportation, Industrial Manufacturing, Energy and Maritime.
Zenitel systems provide high availability, scalability, reliability, maintainability, and cyber-defensibility. By reducing hardware to a minimum, and keeping the benefits of centralized server management, organizations have more flexibility in scale and performance.
 
          PART 1GENERAL
 
          1.1SECTION INCLUDES
          ** NOTE TO SPECIFIER ** Delete items below not required for project.
 
          A.Components:
          1.Communication gateway.
          2.Master stations.
          3.Substations.
          4.Other components.
          5.Accessories.
          6.Software.
 
          B.Security Communication System - ICX500 Protocol Series with the following
          1.Microprocessor controlled, "duplex" voice communication system. IP based central audio servers and necessary boards, power supplies, master control stations, substations, receptacles, special mounting boxes, loudspeakers, terminal boards, cable, connectors, and accessories for a complete operational communication system.
          2.Scope of Work: On-site Security Communication Systems including intercoms, access to audio paging, telephone system, CCTV video switchers, alarm systems and access control security systems.
 
          1.2RELATED SECTIONS
          ** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.
 
          A.Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables.
 
          B.Section 25 15 16 - Integrated Automation Software for Control and Monitoring Networks.
 
          C.Section 33 82 00 - Communications Distribution.
 
          D.Section - .
 
          E.(Note to specifier: Indicate exact scope of work)
 
          1.3SUBMITTALS
 
          A.Shall include an equipment list, and data sheets, system description and block diagrams on equipment to be furnished.
 
          B.Shall include all data necessary to evaluate design, function, quality, and configuration of proposed equipment and systems.
 
          1.4QUALITY ASSURANCE
 
          A.Installation shall comply with all applicable codes.
 
          B.All equipment shall be new, in current production, and the standard products of a manufacturer of intercom equipment. Manufacturer shall be certified as complying with the standards of ISO-9001 for quality control. The central audio server shall meet standards and be certified with a CE label as conforming to rigid EMC requirements for electromagnetic emissions, immunity, and harmonics.
 
          C.Manufacturer shall guarantee availability of parts, for a minimum of (7) years from date of shipment.
 
          D.If required, manufacturer shall be able to demonstrate features, functions, operating characteristics, and clarity of sound to owner.
 
          E.System shall be installed by a factory authorized communications contractor with technicians specifically trained on this system.
 
          F.On-site maintenance and repair service shall be available locally and within ( ) hours of notification for emergency conditions.
 
          G.System shall allow remote programming. Manufacturer shall have the ability to access and make changes to the system via IP connectivity.
 
          1.5CONTRACT DOCUMENTS
 
          A.All equipment and work specified in this section shall comply with all the General Conditions of the specifications, contract documents, and drawings as indicated.
 
          1.6RELATED WORK
 
          A.Systems shall be installed by a qualified Security Communications Contractor, who shall coordinate all work with other contractors and trades.
 
          B.All necessary conduit, raceways, pull boxes, standard boxes, (and special boxes provided by intercom manufacturer), shall be installed by the contractor.
 
          C.Installation of the communication systems shall be coordinated with the installation of other related systems such as: C.C.T.V video switching, audio paging, access control, two-way radio, alarm, and telephone systems.
 
          1.7DELIVERY, STORAGE, AND HANDLING
 
          A.Store and handle in strict compliance with manufacturer's written instructions and recommendations.
 
          B.Protect from damage due to weather, excessive temperature, and construction operations.
 
          1.8PROJECT CONDITIONS
 
          A.Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.
 
          1.9WARRANTY
 
          A.System shall include a factory warranty that equipment is free from defects in design, material, manufacturing, and operation.
 
          B.Factory warranty period shall be for 36 months from date of shipment.
 
          C.Installing communications contractor shall guarantee the equipment, wire, cable, and installation for 12 months from date of acceptance.
 
          1.10ON-SITE SPARES
 
          A.The following items shall be included in the system package and turned over to owner within 30 days of system acceptance.
          1.One Intelligent Communication Gateway with HD Audio.
          2.One IP Master Station.
          3.One IP Substation.
          4.One IP Flush Wall IP Master Station.
 
          PART 2PRODUCTS
 
          2.1MANUFACTURERS
 
          A.Acceptable Manufacturer: Zenitel, which is located at: ; , ; Email: request info; Web: https://www.zenitel.com
          ** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.
 
          B.Substitutions: Not permitted.
 
          C.Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.
 
          D.Basis of Design: Zenitel ICX-500 Intelligent Communication Gateway with HD Audio Server manufactured by Zenitel Group.
 
          E.Substitutions must meet requirements of Prior Approval, as outlined in the contract documents. Substitutions that meet Prior Approval requirements must be listed as alternates by addendum and shall be shown separately on the bid forms. Consideration will be based on ability to comply with all aspects of the specifications, the desired functional operation, quality, reliability, design, size, and appearance of the equipment and the support capabilities of the manufacturer.
 
          2.2SYSTEM DESCRIPTION
 
          A.Security Communication System: Fast "duplex," (hands-free at both ends) voice communication as required to provide instant intercommunications for employees and visitors, emergency paging and signaling, alarm distribution, audio program distribution and active noise cancellation for high noise environments.
          1.Assist with personnel safety, facility security, security systems integration, operational efficiency, and maintenance functions.
 
          B.Microprocessor-controlled system running embedded real time Linux version 4.14 which is a long-term support version with cybersecurity patches, fully "digital", PC programmable, intelligent communication gateway with HD audio server.
          1.Capable of automatic "duplex," hands-free operation, without the use of handsets, at both the initiating and receiving station.
          2.Audio Server:
          a.2 Ethernet IP ports supporting protocols IP v4, TCP, UDP, SSH, NTP, HTTP 1.1, Syslog, SNMP v2c, SIP, RTP, RTCP, and VoIP AlphaNet for direct transfer of call processing functions to and from other ICX-500's as well as to external microprocessor controlled equipment such as access control, CCTV switchers, remote control boards and audio amplifiers.
          b.Support the mix of IP stations with integrated active noise cancellation as desired.
          c.Support SIP protocol to allow for interfacing to VoIP telephones and or systems and equipment.
          d.Special Features:
          1)Capability of redundancy via IP
          2)Wideband audio (7kHz),
          3)Built in firewall
          4)Integrated web and SIP server as well as low latency switching.
          e.Allow for remote programming, logging and maintenance via IP using AlphaPro as well as additional maintenance and statistical information via IP using web browser to interface to ICX Web.
          f.Capability (thru software licensing) for unlimited customer specific messages that can be used for evacuation or emergency events.
          g.Hardware recovery via SD card capability.
          h.Software Integrity Check: Via SHA256 and hardware root of trust for IP security. 1048 MB SDRAM, 1048 MB NAND Flash and 128 MB NOR Flash. System capable of 60,000 BHCA.
 
          C.System Capacity: Include ICX-500 Intelligent Communication Gateway with HD Audio Servers for IP active noise cancellation stations with 125 speech channels per ICX-500 audio server.
          1.Expandable by adding IP active noise cancellation stations and software licenses and modules to approximately 140,208 stations.
          2.Expandable to AlphaNet operation with remote sites, using transparent dialing between remote modules.
          3.(Note to specifier: indicate size and capacity of audio server(s)
 
          D.System Scope: Include features and functions specified and equipment shown on the Drawings.
          1.Capable of adding optional features, equipment and interfaces listed in specifications, even if not initially included or shown on the Drawings.
 
          E.Complete Operational System: Functions in public areas such as elevators, lobbies and parking areas must comply with ADA requirements.
 
          2.3SYSTEM CONFIGURATION
 
          A.Central Audio Servers: Power supplies to be in an appropriate secure data processing room, separate from telephone equipment room.
          1.Configured in AlphaNet configuration and connected via IP to customers' LAN/WAN or internet and be able to be connected in such a matter to create a single system that can consist of up to 254 ICX-500's.
          2.Data and audio routing between ICX-500 audio servers to be via IP and only require the necessary AlphaNet VoIP software licenses based on the system design.
          3.No additional hardware boards or proprietary black boxes will be necessary to do the networking via IP between ICX-500 audio servers.
 
          B.System consists of master stations with direct access buttons with LCD displays, as indicated on the Drawings. Each master can call other stations in the system unless specifically restricted through programming.
          1.Capable of having IP active noise cancellation-based stations along with SIP stations to meet the needs of the system design.
          2.A "supervisor's" display type master control station at or near the central audio server to function as a system maintenance and fault indication station.
 
          C.Security Control Room Masters: And all other master stations to be desk, flush or surface wall mounted as shown on the Drawings.
 
          D.Substations: Flush or surface mounted. Tamper and weather resistant where needed and located as required for direct access calling to masters, as shown on the plans.
          1.Elevator company will install elevator car substations.
 
          E.All features and functions shall be programmed on site with a standard PC via IP.
 
          F.(Note to specifier: Indicate project requirements)
 
          2.4STANDARD SYSTEM FEATURES
 
          A.Master Calls: Unless specifically restricted, a call may be placed from any master station to any other station in the system by dialing the number of the desired station, or using a direct access button. Either party can cancel call by pressing the 'C' button.
 
          B.Substation Calls: Each substation to be programmed to call specific master stations. Pressing button on substation provides a call request verification by blinking LED on station and standard voice message. A substation "call-request" call is identified on a display master, with text message and flashing LED and sound a ringing tone on a master station.
 
          C.Direct Access Buttons: Desk master stations include 10 direct access buttons, programmed for direct access calling, to allow single button speed dialing of other stations, features, or telephone lines.
          1.Station user can program direct access buttons at any time.
          2.Control room masters (CRM-V-2) have button modules available in 48 direct access button size with each CRM type capable of up to 96 direct access buttons.
          3.Dual Display Master Station: Capable of up to 20 direct access buttons.
 
          D.All-Call: Master stations can initiate an all-call page to other system stations. Remove stations, through programming, from receiving all-call and restrict any station from initiating an all-call.
 
          E.Group Call: Master stations can initiate selective paging to predetermined groups of stations in the system. Ability to initiate group call to be restricted to designated stations.
          1.A station may be programmed for membership in up to 250 groups.
          2.No limitations to number of stations in any group.
          3.Program 20 adjacent stations out of a group call to eliminate audio feedback.
          4.Send out several group calls simultaneously.
          5.Priority Levels: 4.
          6.Each group to be able to program one of 4 call announce chime tones.
 
          F.Overhead Paging: Master stations can dial or direct access into one, or more, voice paging systems for zoned and/or department paging over amplified speakers, unless specifically restricted through programming.
 
          G.Automatic Search Feature: Each station has a pre-programmed list of actions that can automatically take place when their station is called but they are either busy, private, absent, or unattended call request.
          1.Allows call to be rerouted to another station, call request, group call etc.
          2.Each station can have 3 different search call numbers.
 
          H.Reply Feature: A person hearing a page or group call can begin an immediate normal hands free conversation with the person who initiated the page, by simply pressing an answer code, '99' on any convenient master station in the group.
          1.System allows multiple page/reply to functions simultaneously.
          2.Waiting time is programmable.
 
          I.Duplex and Manual Operation: Once call connection is established, normal conversation takes place in the "duplex" mode, whereby each person may talk "hands-free." Each master shall have a manual "M" button that when used shall control the direction of the conversation (press to talk, release to listen). Momentarily depressing 'M' button shall restore duplex mode.
 
          J.Tone Signals:
          1.Features and functions such as off hook, call connection, busy, call forward, all call, group call, etc., to be accompanied or preceded by a distinguishable tone.
          2.Group Call tone signals are programmable.
          3.Tones are harmonic and undistorted.
          4.It is possible to customize and change the length and frequency of All/Group tones.
 
          K.Microphone Mute: During a conversation, a person can momentarily block the microphone on any master by holding down one button ' 0'.
 
          L.Call Hold, Inquiry, and Transfer: Once call is connected, it is possible to place call on "hold" by pressing one button (No. 2), dialing, and conversing with a third party, switching back and forth or transferring the call by pressing one button (No. 3).
 
          M.Simplex Conference: Establish and/or join a conference by dialing a four-digit code.
          1.Include any number or all stations in a conference.
          2.System is capable of 100 conferences.
          3.Voice Control: Manual, (press-to-talk, release-to-listen).
          4.In a standard conference, intercom and paging announcements will temporarily interrupt the conference.
          5.One person at a time talks in an individual conference.
          6.Stations can be programmed with ability to override and take control of talking into or speaking into the conference.
 
          N.Pre-Set Group Conference: Set up a group conference by dialing a two-digit code, then a group number followed by the conference number.
          1.Allow 100 conference groups.
          2.Dialing pre-set group conference number includes all members of the group, and all members of the group shall be able to hear whoever is talking.
          3.Each group member will be able to speak to the group by holding down the [M] button on the master. It shall be possible to have a pre-set conference automatically activated by a remote alarm contact or data command.
          4.One person at a time shall talk in an individual conference.
          5.Certain stations can be programmed with ability to override and take control of talking into or feeding the conference.
 
          O.Open Duplex Conference: Set up an open duplex conference by dialing a four-digit code.
          1.Allow 20 different conferences.
          2.Upon dialing code, station will enter the conference.
          a.By placing handset back on hook or pressing C key you will leave the conference.
          3.To rejoin the open duplex conference you simply dial the four-digit code.
          4.Start a preset open duplex conference to include a preset group of stations.
          5.Program DAK Keys on stations to allow for single button dialing to enter conference and start a preset conference.
          6.Maximum number of participants is 64 stations in any combination of open duplex conferences.
 
          P.Priority and Class Service:
          1.Four levels of priority to allow or deny access to features, such as voice or pocket paging, all-call, group-calls, preset conferences, telephone lines, groups of stations and text display of alarm messages.
          2.System includes 16 classes of service which allow the ability to customize features/functions available to stations.
 
          Q.Do-Not-Disturb: IP master stations are equipped with a privacy option activated by pressing and holding the C button to allow user to place station in the 'privacy' mode.
          1.Privacy Mode: An incoming call shall sound a unique 'privacy ring tone' at both the initiating station and station being called.
          a.Call may be answered by pressing the ' M' button.
          b.Program selected stations with 'Privacy Override' whereby calls will be heard even if stations are in the privacy mode.
 
          R.Station Numbering: A true flexible numbering plan feature. Any number from "0" to "99999999" may be assigned to stations or feature codes.
          1.Dialing between remote audio servers to be transparent.
          2.Factory programmed with an "autoload" numbering plan that may be changed on-site as required.
          3.Change numbers any time through programming without any rewiring.
 
          S.Music Distribution: Allow music to be distributed to stations.
          1.Each master may select a desired channel by simply dialing a four-digit code.
          2.Music is interrupted during intercom calls and returns upon completion of call.
          3.For each program distribution channel needed, a TKIE-2 unit will be required along with the use of a simplex conference channel.
 
          T.Informational Channel: Allow one or more audio channels to be programmed to distribute audio information pertinent to operation of facility.
          1.Channel accessed and operated as described for music distribution.
          2.TKIE-2 unit will be required along with the use of a simplex conference channel.
 
          U.Remote Set Up Of Programs: Individually program stations, or groups of stations to receive a channel from a remote master station.
 
          V.Text Messages: Allow multiple alpha/numeric text messages to be stored in queue on each master. The sequence of display to be based on priority of each message.
 
          W.Technical Alarms: Activate a preset 16 character text message on a selected display master, group of masters or activate an audio message on the information channel, from remote alarm contacts.
          1.Each message can be customized and set with a priority level through programming.
          2.Support 140 inputs for technical alarms.
 
          X.Audio Alert of Text Massage: Four distinct types of audible alert tones to sound at the master, when messages are activated.
          1.Allow connection of external alarm indicators; lamps, buzzers, or bells, to sound for high priority messages in noisy environments.
 
          Y.Call Requests to Multiple Masters: Program up to 20 masters to simultaneously receive and display text message call requests from substations.
          1.When calls are answered at one master, messages are deleted from other masters.
          2.If receiving a call request with a certain high priority level, alert receiving stations with a faster repetitive tone.
 
          Z.Transfer of Call Requests: From substations, while allowing standard calls, to different masters by simply dialing a 4 digit transfer code plus the number of the master or group of masters that will receive the transferred calls.
 
          AA.Transfer of Standard Calls: Redirect, Call Forward, all calls to another master, telephone number, or group number simply by dialing a two-digit code 71, plus the redirected number.
          1.When in the "transferred" mode, only the station selected to receive the diverted calls will be able to call or transfer calls to the forwarded station.
          2.Redirect calls while at the receiving station (Follow me) by dialing a two-digit code 72 plus the number of the forwarded station.
          3.System simultaneously handles up to 100 call forward commands.
 
          AB."Camp-On" Busy: Call a busy station, or feature, hear a busy tone (reduced in volume after 5 seconds), wait for a preset time and automatically connect when the called station or feature is free.
          1.Upon connection, both parties hear the normal "connection tone."
          2.Number of "camp-on" calls in system to be unlimited and length of camp-on busy feature is programmable.
 
          AC.Text Call Back Message: If calling party does not wish to remain "camped-on," place the call back and display a callback message on the called party's station by dialing an additional digit '8'.
          1.The message will be registered on the display.
          2.Leave up to 9 pre-set text messages on display of called station.
          3.Number of "call-back messages" on any station, or in whole system, is unlimited.
 
          AD.Voice Call Back Message: Leave a "pre-set" audio voice message, by dialing a voice message code 7 on initiating intercom station. The audio message will be played back at the receiving station by dialing '70'.
 
          AE.Group Hunt: Allow programming of multiple "Hunt" groups, whereby calls to a group number will search and connect to first available station in group.
          1.May be programmed to have a rotational or fixed start point.
          2.Allow substation calls to be directed to a primary master but if it is busy, search for an available master in the group.
          3.Automatic transfer on busy.
 
          AF.Call Request Transfer "Preset:" Stations will divert call request calls to a pre-selected station or group of stations simply by dialing a pre-set code '7870' then the station number or group number.
 
          AG.Software Protection: IP related settings and software licenses to be retained in flash memory. Store customer's program on a PC using AlphaPro and be able to download via ICX Web the customer's program contents of the FLASH memory as a file for troubleshooting.
 
          AH.Emergency Alarm Calls: Selected stations can initiate priority alarm calls to groups of stations in system.
          1.Alarm calls override conversations in progress, override station volume settings, and be heard even if handset is off hook on desk master stations.
          2.Stations can be exempt from receiving emergency calls.
          3.Initiate an alarm call from external equipment and give an automatic voice message.
 
          AI.Wake Up Reminder Calls: 200 separate automatic date and time calls that will cause individual stations to ring at preset times.
          1.Wake-up time is entered at selected station itself. Duration and number of rings is programmable.
          2.After initiation, dialing a digit or lifting the handset cancels the ring.
 
          AJ.Fault/Alarm Logging: Archive via text file fault conditions within system (faulty boards, wiring or software), and external alarm conditions input through the intercom system (prints time and source of alarm) as well as call logging between intercom stations for entire system.
          1.View via ICX Web and inspect contents of the file.
          2.Using an OEM Syslog viewer can allow for faults/alarm logging and call logging events to be sent to remote/external IP address for remote monitoring of the system and the possibility to send these events via Syslog viewer to an email address.
 
          AK.Alarm Override: Allow priority calls and voice alarm messages to override standard intercom calls and come through speaker at full volume, even when handset is in use, privacy switch on and volume set low.
 
          AL.Tone Test: For entire system. Test speaker and microphone circuits of standard stations.
          1.Performed automatically every day at a certain time or manually started to provide a system evaluation for troubleshooting purposes.
          2.Results are sent to log file and saved so results can be looked at a later time that is convenient via ICX Web.
 
          AM.Hotline Call: From any master station with a handset, perform a hotline call.
          1.Performed by lifting handset on a master station, which in turn will place a call to a station or feature that is programmable per station in 5 seconds.
          2.Timer of 5 seconds is programmable; however, this is a system wide timer for all stations.
 
          AN.Event Handling: Programming of custom scripts allows for custom software functions or features not provided in basic system.
          1.Can include actions such as ASCII data outputs strings to external computers for interfacing to CCTV or card access or specific events related to transfers, call requests to multiple stations in multiple audio servers simultaneously, and many other non-standard features that a customer desires that are unique to or needed for their intercom system.
 
          AO.SIP Interface: Provide ability for VoIP telephones which support SIP protocol to interface and register to ICX-500 series audio server.
          1.VoIP telephone can be a single IP telephone device or can be a soft phone client running on a PC.
          2.Interface allows point to point calling between any intercom station and SIP telephone devices with call number and text shown on both ends of call.
          3.Requires No. 1002600700 SIP license which is dependent on number of SIP users required.
          4.IP SIP capable phone by others. Consult Zenitel for recommended models.
 
          AP.Active Noise Cancellation: Provided at audio edge device, i.e. IP station. IP stations use an advanced signal processing algorithm to identify and filter out background repetitive noise signal audio. Integrated into IP station onboard DSP and software. Adjustable from IP station integrated web server.
 
          AQ.IP Networking and Security: Provided at the audio edge device.
          1.IP stations will have the IEEE 802.1X standard for port-based Network Access Control which provides an authentication mechanism to devices that attach to the LAN.
          a.It establishes a point-to-point connection on authentication, or it prevents such a connection if authentication fails.
          2.Specific IP stations have a managed data switch supporting VLAN which allows single network connection to be shared for the IP station and IP CCTV camera without disrupting service quality or violating security.
          3.IP stations also support spanning tree and rapid spanning tree protocol
 
          AR.Scheduling of Events and Actions: Built-in scheduler allows any events or actions to be executed based on time of day, month, or year.
          1.Multiple scheduled events or actions can be programmed as needed.
          2.Any feature or function of the AlphaCom can be set to occur using the built-in scheduler.
 
          AS.Built in DHCP Server: Used in place of DHCP server on a customer's network or for standalone closed network where DCHP IP addressing is desired. The IP range used by the built-in DHCP server has a programmable IP range.
 
          AT.Voice Activity Detection: IP stations have standard feature of VAD (also known as sound detection) where the station microphone samples the audio level and converts it to dB level. If sampled audio is continuously above the trigger amplitude setting and time duration programmed for the IP station, then a call or feature can be activated in the server. VAD as standard isn't enabled for each IP stations and is enabled and configured via the IP stations' web interface.
 
          2.5SYSTEM OPERATIONFOR CRM-V-2
 
          A.Master-To-Master Calls: All masters can call all other masters individually, point to point, unless restricted through programming, by simply touch dialing a 1 to 8-digit number, or by using direct access buttons.
          1.Once dialed, both stations can converse "hands free."Standard features listed to be available to all masters.
 
          B.Security Substation to CRM-V-2 Master: Call requests are initiated from a substation by activating an alarm button, or call-in button on substation. The call request indicates to the calling party with a flashing LED and an audible call acknowledgment voice message to comply with ADA (see options). Call request is annunciated at CRM-V-2 Control Room Master station as follows:
          1.LCD will show you have received a call request from a station.
          2.A rapidly repeating tone signal sound. Call request to be answered at the CRM-V-2 by pressing direct access button preprogrammed to answer all call requests from stations.
          3.When call is answered the following shall occur:
          a.A connection tone is heard at the CRM-V-2 and the calling station.
          b.Flashing LED illuminates "solid" on the appropriate button if direct dial unit (CRM-V-DAK48) is used.
          c.The Number and Text of the station that is connected appears in the LCD.
          d.An in-use LED illuminates on the calling substation.
          e.Clear, two-way communication shall take place.
          4.Other calls from substations to the CRM-V-2 station will each flash their appropriate direct access button LED if direct dial unit (CRM-V-DAK48) is used and sound the call-in tone.
 
          C.Call From a CRM-V-2 Station to any Other Station: Place call by dialing station number on the digit keypad. LCD on the CRM-V-2 station indicates the number and text of the called station. When calling any other master station, "duplex" hands-free communication is possible between the two stations. When calling an elevator car, or other security substation, the press-to-talk button is used to control the conversation, if needed.
 
          D.Group Call From CRM-V-2 Station: Initiated at CRM-V-2 by dialing number assigned to preprogrammed group of stations. This sounds an alert tone and allow paging to all stations in group. There is no limitation to quantity of stations in a group. Group calls have priority over other conversations in progress.
 
          E.Programming Buttons on the CRM-V-2 Station: Direct access buttons on CRM-V-2 master station to be programmed and changed by station user.
          1.Once programmed, button assignments remain in memory. This feature is valid if CRM-V-2 is equipped with CRM-V-DAK48 button modules.
 
          2.6EQUIPMENT AND PRODUCTS
          ** NOTE TO SPECIFIER ** Delete equipment and products not required.
 
          A.IP Touch Screen Desk Master Station: Model ITSV-2. No. 1490002010.
          1.Equipped with full keypad and touchscreen video display.
          2.Android based OS system user interface.
          3.Video: H.264 HD or MJPEG. Audi Codecs: G.722 and G.729.
          4.Video Conference with other ITSV-2's, Call Forwarding, Call Queuing and Multicast.
          5.Wired LAN network connection. Bluetooth for wireless headset. WIFI connectivity.
          6.DAK key shortcuts: Stored on touchscreen for quick dialing of stations or features.
          7.Connection is to a PoE switch or power injector.
 
          B.IP Touch Screen Desk Master Station: Model ITSV-3 No. 1490003010.
          1.Seven inch (1024x600) capacitive 5-point touch screen TFT LCD video display.
          2.Android based OS system user interface.
          3.Video: H.264 HD or MJPEG. Audi Codecs: G.722 and G.729.
          4.Video Conference with other ITSV-3's, Call Forwarding, Call Queuing and Multicast.
          5.Wired LAN network connection. Bluetooth for wireless headset. WIFI connectivity.
          6.DAK key shortcuts: Stored on touchscreen for quick dialing of stations or features.
          7.Connection is to a PoE switch or power injector.
 
          C.IP Cleanroom / Operating Room Master Station: Model IP-CROR Cleanroom/OR Master No. 1008415000. Chemical resistant and anti-bacterial front surface for easy cleaning.
          1.Large high contrast display with backlight. 4 lines with 20 characters and lighting behind each key providing readability in locations where lighting is a problem.
          2.Connects directly to IP network. Integrated web server. Configuration, monitoring, and remote automatic software updates are built in features.
          3.Advanced signal-processing algorithm identifies and filters out background repetitive noise signal audio. Integrated into IP station onboard DSP and software adjustable from IP station integrated web server.
          4.Wideband audio.
          5.Powered locally, connected to a POE switch or power injector.
          6.Flush Mount: No. 1008098700 back box.
          7.Sound detection is a standard software feature included with the station.
          ** NOTE TO SPECIFIER ** Handset is optional. Delete if not required.
          8.Handset unit No. 008097100.
 
          D.IP Desk Master Station: For offices and control rooms.
          ** NOTE TO SPECIFIER ** Delete model options not required.
          1.Model IPDMH-V2 IP Desk Master w/handset (White) No. 1008401000
          2.Model IPDMHB-V2 IP Desk Master w/handset (Black) No. 1008401100)
          3.Model IPDM-V2 IP Desk Master (White) No. 1008400000.
          4.Large high contrast display with backlight,
          5.10 DAK keys for single touch access to stations, group calls, feature codes.
          6.Handset for confidential conversations.
          7.Connects directly to IP networks. Integrated web server for easy configuration, monitoring, and remote automatic software updates.
          8.Advanced signal-processing algorithm identifies and filters out background repetitive noise signal audio. Feature is integrated into IP station onboard DSP and software adjustable from IP station integrated web server.
          9.Sound detection is a standard software feature included with the station.
          10.Wideband audio.
          11.Connection to be a PoE switch or power injector.
 
          E.IP Dual Display Master Station No. 1008007000: For use in offices and control rooms.
          1.High contrast display with backlight.
          2.10 physical DAK keys for single touch access to stations, group calls, feature codes but by using navigation keys will allow the station to have 20 DAK's.
          3.Four navigation keys for quick access to system menus and directory entries.
          4.Connect directly to IP networks. Integrated web server for configuration, monitoring, and remote automatic software updates.
          5.Advanced signal-processing algorithm identifies and filters out background repetitive noise signal audio. Integrated into IP station onboard DSP and software adjustable from integrated web server.
          6.Sound detection is a standard software feature included with the station.
          ** NOTE TO SPECIFIER ** Microphone is optional. Delete if not required.
          7.Gooseneck microphone No. 10007007GM.
 
          F.CRM-V-2 IP Flush Master with Display: Model CRM-V-2 IP. Flush Master No. 1008431000. General-purpose intercom station intended for use where a desktop station is impractical.
          1.Large high contrast display with backlight
          2.Four DAK keys providing single-touch access to stations and features.
          3.Connects directly to IP network. Integrated web server for configuration, monitoring and remote automatic software updates are built in features.
          4.Advanced signal-processing algorithm identifies and filters out background repetitive noise signal audio. Integrated into IP station onboard DSP and software adjustable from integrated web server.
          5.Wideband audio.
          6.Powered locally connected to a POE switch or power injector.
          7.Flush Mounted: No. 1008098700 back box
          8.Surface Mounted: No. 1008098600 back box.
          9.Sound detection is a standard software feature included with the station.
          ** NOTE TO SPECIFIER ** The remaining items are optional Delete options not required.
          10.Handset Unit: No. 1008097100
          11.Gooseneck Microphone: No. 1008097500.
          12.Desk Stand CRM-V Triple, Handset + Station + CRM-V-DAK48: No. 2810020004.
          13.Desk Stand CRM-V Dual, Handset + Station: No. 2810020005.
          14.Desk Stand CRM-V Single: No. 2810020006.
 
          G.CRM-V-DAK48 Unit No. 1008010100. Extends the IP Flush Master Station with DAK buttons and visual indicators (LEDs) that provide 48 auto dial keys per unit.
          1.IP Flush Master: Can be equipped with 2 units.
          a.Allows a wide range of applications; advanced call request handling, CCTV and intercom integration, dynamic group call and PA zone selection.
          b.Must be equipped with ICX IP CRM station license.
          2.Flush Mounted: No. 1008098700 back box
          3.Surface Mounted: No. 1008098699 back box.
 
          H.Soft Client Intercom Station: No. 1009648011. Provides access and ability to make intercom calls, PA calls and perform any feature a traditional or IP master provides from your PC.
          1.Allows direct dialing from PC keyboard or via mouse and M and C keys on PC from the keyboard.
          2.Operates on touch screens. Headset for speakers and microphone for PC provided by others.
 
          I.Turbine IP Vandal Resistant Substation: Model TCIS-1 No.1008111010.
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate.
          6.Yellow thermoplastic front plate with call button along with M and C key.
          7.Supports PoE. Integrated web server.
          8.Sound detection is a standard software feature included with the station.
          9.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          10.Surface Mount: Zenitel No.1008140010.
 
          J.Turbine IP Vandal Resistant Substation: Model TCIS-2 No.1008111020.
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a 0.12 inch stainless steel faceplate.
          6.Equipped with stainless steel front plate with call button.
          7.Supports PoE. Integrated web server.
          8.Sound detection is a standard software feature included with the station.
          9.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          10.Surface Mount: Zenitel No.1008140010.
 
          K.Turbine IP Vandal Resistant Substation: Model TCIS-3 No.1008111030
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate.
          6.Equipped with black thermoplastic front plate with call button.
          7.Supports PoE. Integrated web server.
          8.Sound detection is a standard software feature included with the station.
          9.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          10.Surface Mount: Zenitel No.1008140010.
 
          L.Turbine IP Vandal Resistant Substation: Model TCIS-4 No.1008111040.
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Station has PMOLED Display to show text related to call button.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate.
          7.Equipped with black thermoplastic front plate with call button.
          8.Supports PoE. Integrated web server.
          9.Sound detection is a standard software feature included with the station.
          10.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          11.Surface Mount: Zenitel No.1008140010.
 
          M.Turbine IP Vandal Resistant Substation: Model TCIS-5 No.1008111050.
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Station has PMOLED Display to show text related to call button.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate.
          7.Equipped with black thermoplastic front plate and two call buttons.
          8.Supports PoE. Integrated web server.
          9.Sound detection is a standard software feature included with the station.
          10.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          11.Surface Mount: Zenitel No.1008140010.
 
          N.Turbine IP Vandal Resistant Substation: Model TCIS-6 No.1008111060.
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Station has PMOLED Display and 2 navigation buttons to scroll up and down in the name list along with call button and cancel button.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate.
          7.Equipped with black thermoplastic front plate with call button.
          8.Supports PoE. Integrated web server.
          9.Sound detection is a standard software feature included with the station.
          10.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          11.Surface Mount: Zenitel No.1008140010.
 
          O.Turbine Mini IP Substation: Model TMIS-1 No.1008116010.
          1.Rating: IP42 for indoor use.
          2.Front Plate: White thermoplastic with one red call button.
          3.Active noise cancellation, digital MEMS microphone and Class D amplifier.
          4.Supports PoE. Integrated web server. Sound detection is a standard software feature.
          5.Die-cast aluminum frame.
          ** NOTE TO SPECIFIER ** Delete mounting option not required.
          6.Surface Mount: Into surface back box No.1008140120.
          7.Flush Mount: 2-gang electrical back box No.1008140020.
 
          P.Turbine Mini IP Substation: Model TMIS-2 No.1008116020.
          1.Rating: IP64 for correctional/detention areas indoors.
          2.Front Plate: 11-gauge stainless steel with silver tamper proof call button.
          3.Active noise cancellation, electret microphone and Class D amplifier.
          4.Supports PoE. Integrated web server. Sound detection is a standard software feature.
          ** NOTE TO SPECIFIER ** Delete mounting option not required.
          5.Surface Mount: Into surface back box No.1008140120.
          6.Flush Mount: 2-gang electrical back box No.1008140020.
 
          Q.Turbine Mini IP Substation: Model TMIS-4 No.1008116040.
          1.Rating: IP42 for indoor use.
          2.Front Plate: White thermoplastic with two call buttons.
          3.Active noise cancellation, electret microphone and Class D amplifier.
          4.Supports PoE. Integrated web server. Sound detection is a standard software feature.
          ** NOTE TO SPECIFIER ** Delete mounting option not required.
          5.Surface Mount: Into surface back box No.1008140120.
          6.Flush Mount: 2-gang electrical back box No.1008140020.
 
          R.Turbine IP Vandal Resistant Substation: Model TCIS-C1 No.1008111901.
          1.Rating: IP66.
          2.Wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Equipped with yellow thermoplastic front plate with 2 buttons.
          a.Two call buttons, Emergency, and Info with Braille labeling for use at a help point in a public area.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate.
          7.Equipped with black thermoplastic front plate with call button.
          8.Supports PoE. Integrated web server.
          9.Sound detection is a standard software feature included with the station.
          10.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          11.Surface Mount: Zenitel No.1008140010.
 
          S.Turbine Mini IP Video Substation: Model TMIV-1+ No. 1008117010
          1.Rating: IP42. For indoor use.
          2.Thermoplastic Front Plate: White with one call button.
          3.HD video, wideband audio (7kHz)
          4.Active noise cancellation.
          5.Digital MEMS microphone and Class D amplifier.
          6.Supports PoE. Integrated web server.
          7.Sound detection included with station
          8.Surface Mount: Into surface back box No. 1008140120.
          9.Flush Mount: Flush mount into 2 gang electrical back box No. 1008140020.
 
          T.Turbine IP Vandal Resistant Video Substation: Model TCIV-2+ No.1008315020.
          1.Rating: IP66.
          2.HD video and wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          a.Supports dual video stream functionality, which includes ONVIF-S, HTTP MJPG, RTSP H.264 and RTSP MJPG along with different codecs and resolutions. Both audio and video are lip-synced using RTCP protocol.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Equipped with yellow thermoplastic front plate with 2 buttons.
          a.Two call buttons, Emergency, and Info with Braille labeling for use at a help point in a public area.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a 0.12 inch (3 mm) stainless steel faceplate with call button.
          7.Equipped with black thermoplastic front plate with call button.
          8.Supports PoE. Integrated web server.
          9.Sound detection is a standard software feature included with the station.
          10.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          11.Surface Mount: Zenitel No.1008140010.
 
          U.Turbine IP Vandal Resistant Video Substation: Model TCIV-3+ No.1008315030.
          1.Rating: IP66.
          2.HD video and wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          a.Supports dual video stream functionality, which includes ONVIF-S, HTTP MJPG, RTSP H.264 and RTSP MJPG along with different codecs and resolutions. Both audio and video are lip-synced using RTCP protocol.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate with call button.
          6.Supports PoE. Integrated web server.
          7.Sound detection is a standard software feature included with the station.
          8.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          9.Surface Mount: Zenitel No.1008140010.
 
          V.Turbine IP Vandal Resistant Video Substation: Model TCIV-5+ No.1008315050.
          1.Rating: IP66.
          2.HD video and wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          a.Supports dual video stream functionality, which includes ONVIF-S, HTTP MJPG, RTSP H.264 and RTSP MJPG along with different codecs and resolutions. Both audio and video are lip-synced using RTCP protocol.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.PMOLED display with 2 call buttons that are used to place calls to 2 different call locations.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate with call button.
          7.Supports PoE. Integrated web server.
          8.Sound detection is a standard software feature included with the station.
          9.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          10.Surface Mount: Zenitel No.1008140010.
 
          W.Turbine IP Vandal Resistant Video Substation: Model TCIV-6+ No.1008315060.
          1.Rating: IP66.
          2.HD video and wideband audio (7kHz), active noise cancellation, automatic gain control and sound pressure levels of up to 105 dB from Class D 10-watt output amplifier.
          a.Supports dual video stream functionality, which includes ONVIF-S, HTTP MJPG, RTSP H.264 and RTSP MJPG along with different codecs and resolutions. Both audio and video are lip-synced using RTCP protocol.
          3.Digital MEMS microphone immune to electromagnetic radiation interference.
          4.Acoustically transparent poke screen that makes speaker tamper resistant while maintaining audio flow.
          5.PMOLED display with 2 navigation buttons that are used to scroll up and down the name list along with call button and cancel button.
          6.Electronics are covered by a 1/8 inch 3 mm thick aluminum die-cast base and further reinforced by a thermoplastic faceplate with call button.
          7.Supports PoE. Integrated web server.
          8.Sound detection is a standard software feature included with the station.
          9.Flush Mount: In 2 gang electrical back box No.1008140020 along with Zenitel TA-5 bracket No.1008140050
          10.Surface Mount: Zenitel No.1008140010.
 
          X.Turbine IP Industrial intercom Master Station: Model TFIE-1 No.1008122010.
          1.Rating: IP66. Harsh environments and meets industrial and offshore requirements.
          2.Housing: Plastic. Withstands chemical and environmental hazards on or offshore.
          3.Full keypad. One programmable button. Keys for manual override (PTT) and Cancel.
          4.Digital, crystal clear audio with high output through a 10 W Class D amplifier.
          5.Active Noise Reduction and Acoustic Echo Cancelling.
          6.Hands-free two-way communication.
          7.Sound detection is a standard software feature.
 
          Y.Turbine IP Industrial Substation: Model TFIE-2 No.1008122020.
          1.Rating: IP66. Harsh environments and meets industrial and offshore requirements.
          2.Housing: Plastic. Withstands chemical and environmental hazards on or offshore.
          3.Six programmable labelled buttons and optional key covers. Keys for manual override (PTT) and Cancel.
          4.Digital, crystal clear audio with high output through a 10 W Class D amplifier.
          5.Active Noise Reduction and Acoustic Echo Cancelling.
          6.Hands-free two-way communication.
          7.Sound detection is a standard software feature.
 
          Z.Turbine IP Industrial Master Station: Model TFIE-6 No.1008122060.
          1.Rating: IP66. Harsh environments and meets industrial and offshore requirements.
          2.Housing: Plastic. Withstands chemical and environmental hazards on or offshore.
          3.Full keypad and 4 programmable DAK buttons that are used to call intercom or feature numbers.
          4.Active noise reduction, acoustic echo cancellation, automatic volume control.
          5.Hands-free two-way communications.
          6.Class D 10W amplifier, 2 relay contacts, 6 I/O's.
          7.Handset: No.1008140230.
          8.Headset: No. AK5850HS.
          9.PMOLED display with scrolling unit for calling stations and features.
          10.Powered by PoE connection or locally powered.
          11.Sound detection is a standard software.
 
          AA.Turbine IP Ex-Rated Industrial Intercom Master Station: Model TFIX-1-V2 No.1008123011.
          1.Rating: IP66 for harsh environments, Meets industrial and offshore requirements and explosion proof areas.
          2.Housing: Plastic. Withstands most chemical and environmental hazards found on or offshore.
          3.Full keypad. One programmable button and keys for manual override (PTT) and Cancel.
          4.Digital, crystal clear audio. Active Noise Reduction and Acoustic Echo Cancelling.
          5.Hands-free two-way communication.
 
          AB.Turbine IP Ex-Rated Industrial Intercom Substation: Model TFIX-2-V2 No.1008123021.
          1.Rating: IP66 for harsh environments, Meets industrial and offshore requirements and explosion proof areas.
          2.Housing: Plastic. Withstands most chemical and environmental hazards found on or offshore.
          3.Six programmable, labelled buttons and optional key covers.
          4.Digital, crystal clear audio. Active Noise Reduction and Acoustic Echo Cancelling.
          5.Hands-free two-way communication.
 
          AC.Turbine IP Ex-Rated Industrial Intercom Substation: Model TFIX-3-V2 No.1008123031.
          1.Rating: IP66 for harsh environments, Meets industrial and offshore requirements and explosion proof areas.
          2.Housing: Plastic. Withstands most chemical and environmental hazards found on or offshore.
          3.One programmable, labelled button and optional key cover.
          4.Digital, crystal clear audio. Active Noise Reduction and Acoustic Echo Cancelling.
          5.Hands-free two-way communication.
 
          AD.Exigo Call Panel Unit: Model ECPIR-3P No.1023200033.
          1.Direct access call panel featuring 3 DAK buttons and PTT button.
          a.DAK buttons are used to call intercom stations or features.
          b.DAK buttons are equipped with LEDS to provide status related to DAK buttons.
          2.Access Panel:
          a.Can be equipped with gooseneck microphone or handheld mic with PTT.
          b.Can be connected to extension panel EMBDR-8 module if more DAK buttons are desired.
          3.Active noise reduction, acoustic echo cancellation, automatic volume control.
          4.Hands-free two-way communications.
          5.Powered by PoE or via local power supply.
          6.Unit is mounted in desk housing that can be surface mounted.
          7.Desk Mount Unit: EMBR-1 No.1023595010.
 
          AE.EXIGO Button Expansion Module: Model EBMDR-8 No.1023253008.
          1.Connects to ECPIR-3P call panel providing additional DAK buttons if needed to call stations or features. Connects via flat ribbon cable as no IP connection is made directly to the expansion modules.
          2.Units mount in desk housing that can also be surface mounted.
          ** NOTE TO SPECIFIER ** Delete desk mount unit option not required.
          3.Desk Mount Unit: Model EMBR-1 No. 1023595010.
          4.Desk Mount Unit: Model EMBR-2 No. 023595020.
 
          AF.Emergency Wall and Tower Units:
          1.Units have a blue LED light unit glowing blue and flashing during intercom calls.
          2.Deluxe Tower and Wall Unit: Ultra bright LEDs illuminating substation faceplate.
          3.LED Units: Blue prismatic Lexan lenses with clear UV protected polycarbonate outer lenses.
          4.Wall Units: 10 gauge stainless steel. Can be wall or pole mounted. Weatherproof housings with silk screened "emergency" signs.
          5.Mass Notification Applications:
          ** NOTE TO SPECIFIER ** Delete product options and adapter plate options not required.
          a.No. 2809016002
          b.No. 160000MN
          1)1600 Series Turbine Adapter Plate No. 1072160000.
          2)1600 Series Turbine Adapter Plate-Yellow No. 1000160906.
          c.No. 2809016022
          d.No. 160200MN
          1)1600 Series Turbine Adapter Plate No. 1072160000.
          2)1600 Series Turbine Adapter Plate-Yellow No. 1000160906.
 
          AG.Audio Server: Model ICX-500 Audio Server No. 1002000100. Provide all control, logic, signaling, "duplex" switching amplification, power and operating features listed throughout this specification. C
          1.Comply with CE, FCC Part 15, EN61000-6-x, EN60945 and EN50121-4 certifications. Circuitry and components: Solid-state. Employing the latest "state-of-the-art" design.
          2.Expansion to ultimate audio server capacity:
          a.Requires addition of IP stations with the necessary software licenses.
          b.No additional hardware boards or proprietary black boxes are necessary for networking via IP between audio servers.
          c.System Nodes: Up to 254 nodes.
          d.Total IP Station Capacity: 140,208.
          3.Support SIP protocol to allow for interfacing to VoIP telephones and or systems and equipment.
          a.Provide special features such as ability for redundancy via IP, wideband audio (7kHz), built in firewall, integrated web and SIP sever as well as low latency switching.
          b.Allow remote programming, logging and maintenance via IP using AlphaPro as well as additional maintenance and statistical information via IP using web browser to interface to ICX Web.
          4.Capacity for 125 simultaneous conversations.
          a.All stations have access to all speech channels.
          b.Malfunction of one speech channel shall not affect operation of the system.
          c.Every speech channel includes "software-based compression" circuits to automatically control and limit sound volume during conversation.
          5.A custom-made software program, stored in FLASH memory, specifically designed for the system. Programming software (AlphaPro) to operate on a PC with Window 7, 8 and 10 and include a menu for standard features and directory numbers, which may be entered by one operation.
          a.AlphaPro Software: Unlimited flexible numbering and programmable features. Microprocessor includes two Ethernet IP ports to allow direct transfer of call processing information, to and from other microprocessor-controlled equipment.
          6.Reprogram audio server at sever location or remotely through IP. Programming takes effect immediately.
          a.Programmable information is protected against a power failure, reset, and maintained in FLASH memory.
          b.FLASH Memory: Located on processor board.
          1)Possible to export via AlphaPro the user information along with the AlphaNet audio and data links and open using Microsoft Excel.
          c.Regulated power supply shall power the audio server.
          7.Self-diagnostic software to monitor IP station connectivity and AlphaNet links.
 
          AH.ICX-500 Intelligent Communication Gateway w/HD Audio
          ** NOTE TO SPECIFIER ** Delete options not required.
 
          2.7OPTIONS (Available with additional equipment)
 
          A.AlphaPro Software: No 1009291120. An offline or online programming tool for configuring the ICX-500 system.
          1.AlphaPro M: Doesn't require a USB hardware key and provides access to first 36 physical ports only and doesn't allow programming AlphaNet data and audio routing.
          a.Available free of charge to download from web.
          2.AlphaPro Professional: Runs with USB hardware key and provides access to all features of the programming software.
 
          B.SIP Gateway Telephone Interface: Allows telephone calls to be directed in and out, of the system for two-way communication between intercom stations and remote telephones via IP using SIP protocol.
          1.Model MP-114 SIP Gateway No. 3006204094
          2.Model MP-118 SIP Gateway No. 3006204099.
          3.Selected master stations can dial an access code '0', receive PABX or Central Office dial tone, and dial any unrestricted telephone number and vice versa.
          4.Requires ICX SIP trunking license No. 100260210x. License is dependent on how many telephone lines used.
 
          C.IP Ceiling Speaker with Microphone: Model ELSIR-10CM No. 1023300011.
          1.Individually addressable and for applications requiring a limited number of speakers.
          2.PoE capable.
          3.Built-in omni-directional microphone
          4.Provides 10 watts of output power.
          5.Remote software upgrade and configuration via built in web server.
 
          D.IP Horn Speaker with Microphone: Model ELSII-10HM No. 1023301311.
          1.Individually addressable. For applications that require a limited number of speakers.
          2.IP66-rating
          3.PoE capable.
          4.Built-in omni-directional microphone
          5.Output Power: 10 watts.
          6.Remote software upgrade and configuration: Via built in web server.
 
          E.IP Horn Long Speaker with Microphone: Model ELSII-10LHM No. 1023301321.
          1.Individually addressable. For applications that require a limited number of speakers.
          2.IP66-rating
          3.PoE capable.
          4.Built-in omni-directional microphone
          5.Output Power: 10 watts.
          6.Remote software upgrade and configuration: Via built in web server.
 
          F.Network Projector Speaker with Microphone: Model ELSII-10PM No. 1023302340
          1.Individually addressable. For applications that require a limited number of speakers.
          2.IP65-rating
          3.PoE capable.
          4.Built-in omni-directional microphone
          5.Output Power: 10 watts.
          6.Remote software upgrade and configuration: Via built in web server.
 
          G.Network On-wall cabinet speaker: Model ELSII-10WM No. 1023302330
          1.Individually addressable. For applications that require a limited number of speakers.
          2.IP65-rating
          3.PoE capable.
          4.Built-in omni-directional microphone
          5.Output Power: 10 watts.
          6.Remote software upgrade and configuration: Via built in web server.
 
          H.TCIA-2-P Analog Over IP Gateway Kit: No. 1008113120. Allows a Turbine analog substation to work as an IP station with limited software features.
          1.Connection to IP network is done via TKIS-2 kit which connects via copper wire to a TKIA-1 unit that then connects via copper wire to a TCIA-1 unit in the field.
          a.TCIA-1 station can be up to 200 feet from the TKIA-1 connection using CAT5 wire.
          2.Consists of 3 Parts: Turbine modified analog station TCIA-2, TKIA-2, and TKIS-2.
 
          I.IP Audio Remote I/O Unit: Model ARIO No. 1008095100. Provide ability for PA, radio interface over IP and digital inputs/outputs that can be used for door opening or strobe control, etc.
          1.When used with VPA series of amplifiers speaker loop monitoring is possible.
          2.Powered locally or connected to PoE switch.
          3.Supervised by ICX-500 audio server.
          4.If interfaced to PA system or radio system, No. 1009641601 ARIO audio license is required.
 
          J.TKIS-2 VOIP Intercom Module: Model TKIS-2 No. 1008131020. Allows user to to build their own IP intercom station, IP help point or interface to PA systems.
          1.Utilizes same PCB used in Turbine IP station which provides a 10W Class D amplifier, active noise cancellation along with HD voice quality.
          2.Tool less connections. Powered locally or via PoE.
          3.Supports 6 call buttons and one dry contact closure for door/gate or strobe control.
 
          K.Turbine No 1008132020 TKIE-2 IP Extended Kit.
          1.Multiple capabilities: Function as IP substation, PA interface to existing analog PA amps, IP paging zone, and line level input for radio interface.
          2.Class D 10 W amplifier. PA line level audio output, line level audio input, 2 relay outputs, and 6 input/outputs that can be used for call buttons or LEDs.
 
          L.Turbine 1008331010 TKIV+ Video and VOIP Intercom Module:
          1.Unit functions as IP Video substation, PA interface to existing analog PA amps, IP paging zone, and line level input for radio interface.
          2.Equipped with Class D 10 W amplifier, PA line level audio output, line level audio input, 2 relay outputs, and 6 input/outputs that can be used for call buttons or LEDs.
 
          M.IP Line Connection Module: Model IP-LCM-A No. 1008095201. Has all TKIS-2 features available and in addition 8 relay outs and 8 control inputs.
          1.Power is via PoE or local power. Push in connections.
 
          N.Flowire Converter Unit: Model FCDC3 No. 1008080310. Enables Ethernet to run on the same two wires as power, providing ability to reuse existing wire infrastructure. Allows IP devices to run over long distances. Single pair of wire provides necessary power and data to IP device.
 
          O.Touchless Sensor: Model No. 2390020100. Used to activate intercom calls by gesture recognition, e.g. swipe of the hand. Includes backbox for on-wall mounting.
 
          P.Gooseneck Microphone: Model MB-30G No. 3005020033. Electret microphone with 5-pin DIN connector for use with ECPIR-3P and ECPIR-R Call Panels.
 
          Q.Handheld Microphone W/ PTT Button: Model PAM1H No. 1023533012. 1.5 m coiled cord equipped with 5-pin DIN connector for use with ECPIR-3P.
 
          R.Industrial Handset for Turbine: Model TA-23 No. 1008140230. For industrial use.
          1.Side mount PTT key for simplex operation in dynamic noise applications.
          2.Rating: IP66. Comes with mounting hanger.
 
          S.Industrial Ex Handset for Turbine: Model TAX-3 No. 1008150030. For use in EX rated locations. Side mount PTT key for simplex operate in dynamic noise applications.
          1.Rating: IP66. Comes with mounting hanger.
 
          T.Industrial Headset EX Rated: No. AK5850HS. Used with TFIX TFIE Turbine Industrial stations. Adjustable boom microphone and coiled cord for ease of use using a 4-oin Nexus connector.
          1.Used in connection with TAX-2b EX approved cable and plug box with PTT and 33 feet of cable.
 
          U.Desk Mounting Unit Kits: For ECPIR-3P and EMBDR-8. It is possible to connect housings together using mounting kit No. 1023595060.
          1.Single Unit: Model EMBR-1 No. 1023595010.
          2.Double Unit: Model EMBR-2 No. 1023595020.
 
          V.Turbine Adapter Plate: No. 1072160000. 11-gauge stainless steel and used in conjunction with Turbine stations when installed in Emergency Signaling Units.
          1.Includes attached mounting gasket on back of faceplate and gasket for Turbine station.
 
          W.Turbine Adapter Plate Yellow: No. 1000160906. 11-gauge stainless steel painted safety yellow and used in conjunction with Turbine station when installed in Emergency Signaling Units.
          1.Includes attached mounting gasket on back of faceplate and gasket for Turbine station.
 
          X.Standalone Strobe and Strobe Bracket: Connect to relay contact on any IP substation or flush master station as required for light indication.
          ** NOTE TO SPECIFIER ** Delete model option not required.
          1.Model 120VAC Lamp Strobe LED: No. 95900306160
          2.Model 12/24v DC Lamp Strobe LED: No. 9590030616
          3.Mounting Bracket: No. 95900306161.
          4.Bracket attaches to a 2-gang electrical box of your choice.
 
          2.8ICX SOFTWARE LICENSES
          ** NOTE TO SPECIFIER ** Delete software licenses not required.
 
          A.ICX Alphanet VOIP License: No. 100260200x where x is determined depending on the design scope of the system on a node by node basis.
          1.Makes it possible to establish audio communication between ICX-500 audio servers connected in an IP configuration.
          2.Each ICX-500 audio server will require a software license.
          3.Software license shall be AlphaNet VoIP License.
 
          B.ICX IP Station License: No. 1002600100 which registers 1 IP station.
          1.Connect and register IP stations (masters and substations) via IP to an ICX-500 audio server.
          2.Once IP station is registered it can then place intercom calls.
          3.The number of IP stations required for the job will determine the number of IP station licenses.
          4.Software license shall be ICX IP Station License
 
          C.ICX SIP Trunking License: No. 100260210x where x is determined depending on the design scope of the system.
          1.Connect ICX-500 to VOIP IP Phone systems or traditional PBX that aren't IP capable if combined and used with a MP-114 or MP-118 SIP Gateway.
          2.SIP trunking gives a seamless integration between the ICX-500 and other telecom systems supporting SIP which allows for advanced functions.
          3.Software license shall be ICX SIP Trunking License
 
          D.ICX SIP Station License: No. 1002600700 which registers 1 SIP phone.
          1.Connect and register SIP based phones via IP with the ICX-500 system. Once the SIP based phone is registered it can then place and receive intercom calls much like a traditional intercom station.
          2.The number of SIP phones required for the job will determine the number of SIP station licenses.
          3.Software license shall be ICX SIP Station License
 
          E.ICX API License: No. 100260230x where x is determined by how many stations you wish to monitor.
          1.Connect and register details regarding events occurring in the ICX-500 intercom system to external OPC based management systems.
          2.Greatly reduces need to write specific interface protocol as OPC is an industry standard based on OPC and Microsoft.Net.
 
          F.ICX Audio Messaging Licenses-Basic and Enhanced:
          ** NOTE TO SPECIFIER ** Delete model option not required.
          1.Model Basic No. 1002604000
          2.Model Enhanced No. 1002604100.
          3.Store and play audio messages from the ICX-500 audio server.
          4.Messages are stored in flash memory on the ICX-500 or SD card provided by others.
          5.Licenses are compatible with the feature set of the ASVP card but offer some important functionality possibilities such as allowing the modification of default messages as well as adding new messages.
          6.New and modified messages can be entered via any intercom station.
          7.Make messages on a PC and upload to the audio server via ICX Web.
          8.Allows pre-recorded messages to be played during emergency or scheduled times based on system application.
 
          G.ICX CRM License: No. 1002600200. Expand ability of Mo. 1008031000 IP Flush Master by using up to two No. 1008010100 CRM-V-DAK48 units for auto dial-up to a maximum of 96 directory numbers or features.
 
          H.ICX Redundancy License: IP Redundancy License No. 100260600x where x is determined depending on the design scope of the system.
          1.Register to a backup ICX-500 audio server in case fault occurs on the primary ICX-500 audio server.
          2.Backup server must be an identical version as primary audio server and when a fault occurs the IP stations will automatically register to the backup AlphaCom.
 
          I.ICX Active Recording License and Recording Software:
          1.License No. 100260220x where x is determined depending on the design scope of the system.
          2.Recording Software for PC: No. 11901101xx where xx is determined depending on the design scope of the system.
          a.Record audio events such as intercom calls, all/group calls, simplex and open duplex conference and SIP calls via IP by creating a SIP call session for each event.
          b.Audio: Recorded externally via IP to PC with Recording Software installed on it.
 
          J.ICX ARIO Audio License: No. 1002600400. Makes it possible to use No. 1008095100 ARIO unit and allows interface to a PA or radio system.
          1.One license required per unit that interfaces to PA or radio system.
 
          K.VS Operator: PC based system management package providing access to the features of the ICX-500 audio server.
          1.VS Operator Basic License: No. 1191101000
          2.VS Operator Enhanced License: No. 1191101010.
          3.For control room applications. Allows user to answer calls, call requests, make all/group calls etc.
          4.Stores history of events that have occurred.
          5.Graphical GUI for building maps, call queuing, video queuing, RCI and RCO status is provided.
 
          L.ICX Interface Enabling License. No. 1002602400.
          1.Interface with any external equipment that would interface to ICX-500 using legacy data protocols such as MPC data, EDO/EDI data and Simple Link Layer.
          2.Various Access Control Systems require this license to interface to ICX-500.
 
          PART 3EXECUTION
 
          3.1EXAMINATION
 
          A.Do not begin installation until substrates have been properly constructed and prepared.
 
          B.If substrate preparation is the responsibility of another installer, notify Architect in writing of unsatisfactory preparation before proceeding.
 
          3.2PREPARATION
 
          A.Clean surfaces thoroughly prior to installation.
 
          B.Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
 
          3.3INSTALLATION
 
          A.Shall be installed by qualified technicians who have been factory trained and certified.
 
          B.Wiring shall be uniform and in accordance with national electric codes and manufacturers' instructions.
 
          C.Equipment shall be firmly secured, plumb, and level.
 
          D.All cable runs at the main terminal board and in all connection, boxes shall be tagged and identified.
 
          E.Coordinate all work with other effected trades and contractors.
 
          F.Product shall be configured in accordance with manufacturer-supplied hardening guide. Systems for which the manufacturer does not provide a hardened installation option are not acceptable.
 
          3.4SYSTEM INITIALIZING AND PROGRAMMING
 
          A.System shall include all software necessary for system configuration.
 
          B.System shall be turned on and adjustments made to meet requirements of specifications and on-site conditions.
 
          C.System shall be programmed to function as specified.
 
          D.Directory numbers, feature codes, and special programming shall be documented, printed, and made available to owner.
 
          3.5SYSTEM TEST PROCEDURES
 
          A.System shall be completely tested to assure that the Intelligent Communication Gateway with HD Audio and all components, stations, speakers, and accessories are hooked-up and in working order.
 
          B.System shall be pre-tested by contractor and certified to function in accordance with plans and specifications.
 
          C.System shall be tested in presence of owner's representative.
 
          3.6OWNER INSTRUCTIONS
 
          A.Installation contractor shall conduct up to (4) hours of instruction in use and operation of the system to designated owner representatives, within (30) days of system acceptance. Owner will print and distribute directory number plan to users.
 
          B.Installation contractor shall conduct up to (4) hours of technical training, in programming, troubleshooting, and service of the system, to designated owner representatives within (90) days of system acceptance.
 
          C.Manufacturer shall conduct periodic technical training seminars and make them available to those responsible for on-going maintenance of the system.
 
          3.7MANUALS AND DRAWINGS
 
          A.Contractor shall provide owner with (2) copies of standard factory prepared operation, installation, and maintenance manuals. Manuals shall include typical wiring diagrams.
 
          B.Contractor shall provide owner with (2) copies of any risers, layouts, and special wiring diagrams showing any changes to standard drawings, if required on project.
 
          3.8CLEANING AND PROTECTION
 
          A.Clean products in accordance with the manufacturer's recommendations.
 
          B.Touch-up, repair or replace damaged products before Substantial Completion.
 
         
END OF SECTION